Trade Price
£620.97
Per
1
Unit
EACH
Pack Quantity
1
Eaton Moeller series NZM - Molded Case Circuit Breaker. Delay unit
Product Length/Depth
100 mm
Product Height
114 mm
Product Width
74 mm
Product Weight
0.847 kg
Compliances
IEC
RoHS conform
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Frame
NZM1/2/3/4
Rated control supply voltage (Us) at AC, 50 Hz - min
24 V
10.4 Clearances and creepage distances
Meets the product standard's requirements.
Suitable for
Off-load switch
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
Voltage rating at AC
220 - 550 V AC
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
Rated control supply voltage (Us) at DC - min
24 V
Delay time
70 - 4000 ms (undervoltage releases, off-delayed)
Power consumption
50 VA
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
Rated control supply voltage (Us) at AC, 50 Hz - max
550 V
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.8 Connections for external conductors
Is the panel builder's responsibility.
Connection type
With bolt connection
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Special features
Delay unit for combination with special undervoltage releases.
For use with emergency-stop devices in connection with an emergency-stop button.
not UL/CSA approved
Voltage dips of less than the setting between 0.06 – 16 s do not cause disconnection of the NZM circuit-breaker or N switch-disconnector.
Delay time can be set from: 70 ms – 4 s.
With additional external capacitor: 30,000 µF ≧ 35 V to 8 s, 90,000 µF ≧ 35 V to 16 s.
A special release is required.
Cannot be installed simultaneously with separate NZM...-XHIV early-make auxiliary contact or NZM...-XA... shunt release.
Delay unit for separate installation. Fixing: top-hat rail or screws.
For other operating voltages use a control transformer.
Rated operation current (Ie)
< 0.5 A
Undelayed short-circuit release - min
0 A
Rated control supply voltage (Us) at AC, 60 Hz - min
24 V
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
Terminal capacity (solid/flexible conductor)
20 - 14 AWG (1x) at shunt release
20 - 16 AWG (2x) at shunt release
0.5 mm² - 1.5 mm² (2x) at shunt release with ferrule
0.5 mm² - 1.5 mm² (2x) for undervoltage releases, off-delayed with ferrule
0.5 mm² - 2.5 mm² (1x) at shunt release with ferrule
18 - 14 AWG (1x) for undervoltage releases, off-delayed
0.5 mm² - 2.5 mm² (1x) for undervoltage releases, off-delayed with ferrule
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Voltage rating at DC
24 V DC
Functions
Delayed
Rated control supply voltage (Us) at DC - max
24 V
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Delay time with additional external capacitor
8 s (30 mF)
16 s (90 mF)
Type
Accessory
Undervoltage release
Undervoltage release, off-delayed
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Rated control supply voltage (Us) at AC, 60 Hz - max
550 V
Used with
N(S)1(-4), 2(-4), 3(-4), 4(-4)
50/60 Hz
220 V - 240 V
380 V - 440 V
480 V - 550 V
DC/AC
24 V
NZM1(-4), 2(-4), 3(-4), 4(-4)
N(S)1(-4), 2(-4), 3(-4), 4(-4)
50/60 Hz
220 V - 240 V
380 V - 440 V
480 V - 550 V
DC/AC
24 V
Number of contacts (normally open contacts)
0
Undelayed short-circuit release - max
0 A
Electric connection type
Screw connection
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Number of contacts (normally closed contacts)
0
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
Number of contacts (change-over contacts)
0
Voltage type
AC/DC
Datasheet