PN1-63

Switch-disconnector 3p 63A

Trade Price

£198.20

Per

1

Unit

EACH

Pack Quantity

1

PN1-63
PN1-63
PN1-63

Information

Eaton Moeller series NZM - Molded Case Circuit Breaker. Switch-disconnector 3p, 63A

Technical Specifications

Product Length/Depth

88 mm

Product Height

145 mm

Product Width

90 mm

Product Weight

0.84 kg

Compliances

RoHS conform

Certifications

IEC

IEC/EN 60947

Application

Use in unearthed supply systems at 690 V

Type

Switch-disconnector

Circuit breaker frame type

PN1

Number of poles

Three-pole

Features

Version as maintenance-/service switch

Version as main switch

Version as emergency stop installation

Special features

Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.

Isolating characteristics to IEC/EN 60947-3 and VDE 0660.

Busbar tag shroud to VDE 0160 Part 100.

Rated current = rated uninterrupted current: 63 A

Rated operating voltage (Ue) at AC - max

690 V

Rated operating power at AC-23, 400 V

30 kW

Rated operational current

160 A (415 V AC-22/23A, making and breaking capacity)

160 A (690 V AC-22/23A, making and breaking capacity)

Rated permanent current at AC-21, 400 V

0 A

Rated conditional short-circuit current with back-up fuse

80 kA at 690 V

63 gG/gL

100 kA at 400/415 V

Rated conditional short-circuit current with downstream fuse

100 kA at 400/415 V

63 gG/gL

10 kA at 690 V

Rated short-time withstand current (Icw)

2 kA

Rated short-time withstand current (t = 0.3 s)

2 kA

Rated short-time withstand current (t = 1 s)

2 kA

Amperage Rating

63 A

Rated operating frequency

50 Hz

Rated short-circuit making capacity Icm at 690 V, 50/60 Hz

2.8 kA

Rated operating power at AC-3, 400 V

0 kW

Switching power at 400 V

0 kW

Short-circuit protective device fuses - max

125 A gL

Electrical connection type of main circuit

Frame clamp

Isolation

500 V AC (between auxiliary contacts and main contacts)

300 V AC (between the auxiliary contacts)

Number of operations per hour - max

120

Handle type

Rocker lever

Overvoltage category

III

Pollution degree

3

Lifespan, electrical

1000 operations at 690 V AC-23A

10000 operations at 415 V AC-1

1000 operations at 400 V AC-23A

1000 operations at 415 V AC-23A

10000 operations at 400 V AC-1

7500 operations at 690 V AC-1

Direction of incoming supply

As required

Voltage rating

690 V - 690 V

Rated insulation voltage (Ui)

690 V

Rated impulse withstand voltage (Uimp) at auxiliary contacts

6000 V

Rated impulse withstand voltage (Uimp) at main contacts

6000 V

Rated conditional short-circuit current (Iq)

0 kA

Mounting Method

Fixed

Distribution board installation

Ground mounting

Built-in device fixed built-in technique

Intermediate mounting

Degree of protection

IP20 (basic protection type, in the area of the HMI devices)

Degree of protection (IP), front side

IP20

IP40 (with insulating surround)

IP66 (with door coupling rotary handle)

Degree of protection (terminations)

IP10 (tunnel terminal)

IP00 (terminations, phase isolator and band terminal)

Protection against direct contact

Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110

Shock resistance

20 g (half-sinusoidal shock 20 ms)

Number of auxiliary contacts (change-over contacts)

0

Number of auxiliary contacts (normally closed contacts)

0

Number of auxiliary contacts (normally open contacts)

0

Number of switches

1

Handle color

Black

Switch positions

I, 0

Climatic proofing

Damp heat, constant, to IEC 60068-2-78

Damp heat, cyclic, to IEC 60068-2-30

Lifespan, mechanical

20000 operations

Document Links

Datasheet