NZMH2-ME90

MCCB NZM2 3pole 90A 150kA motor protection electronic

Trade Price

£632.44

Per

1

Unit

EACH

Pack Quantity

1

NZMH2-ME90

Information

Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3p, 90A, H2-ME90

Technical Specifications

Product Length/Depth

149 mm

Product Height

184 mm

Product Width

105 mm

Product Weight

2.438 kg

Compliances

RoHS conform

Certifications

IEC

IEC/EN 60947

Voltage rating

690 V - 690 V

Rated insulation voltage (Ui)

1000 V

Rated impulse withstand voltage (Uimp) at auxiliary contacts

6000 V

Rated impulse withstand voltage (Uimp) at main contacts

8000 V

Rated operational current

78 A (690 V AC-3)

81 A (400 V AC-3)

Rated short-time withstand current (t = 0.3 s)

1.9 kA

Rated short-time withstand current (t = 1 s)

1.9 kA

Amperage Rating

90 A

Instantaneous current setting (Ii) - min

90 A

Instantaneous current setting (Ii) - max

1260 A

Overload current setting (Ir) - min

45 A

Overload current setting (Ir) - max

90 A

Short-circuit release non-delayed setting - min

180 A

Short-circuit release non-delayed setting - max

1260 A

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz

150 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz

130 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz

130 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz

37.5 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz

5 kA

Rated short-circuit making capacity Icm at 240 V, 50/60 Hz

330 kA

Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz

330 kA

Rated short-circuit making capacity Icm at 440 V, 50/60 Hz

286 kA

Rated short-circuit making capacity Icm at 525 V, 50/60 Hz

105 kA

Rated short-circuit making capacity Icm at 690 V, 50/60 Hz

40 kA

Rated operating power at AC-3, 230 V

22 kW

Rated operating power at AC-3, 400 V

45 kW

Short-circuit total breaktime

< 10 ms

Electrical connection type of main circuit

Screw connection

Isolation

300 V AC (between the auxiliary contacts)

500 V AC (between auxiliary contacts and main contacts)

Number of operations per hour - max

120

Handle type

Rocker lever

Utilization category

A (IEC/EN 60947-2)

Overvoltage category

III

Pollution degree

3

Lifespan, electrical

6500 operations at 415 V AC-3

10000 operations at 400 V AC-1

5000 operations at 690 V AC-3

6500 operations at 400 V AC-3

7500 operations at 690 V AC-1

10000 operations at 415 V AC-1

Direction of incoming supply

As required

Mounting Method

Built-in device fixed built-in technique

Fixed

Degree of protection

IP20

IP20 (basic degree of protection, in the operating controls area)

Degree of protection (IP), front side

IP40 (with insulating surround)

IP66 (with door coupling rotary handle)

Degree of protection (terminations)

IP00 (terminations, phase isolator and strip terminal)

IP10 (tunnel terminal)

Protection against direct contact

Finger and back-of-hand proof to VDE 0106 part 100

Shock resistance

20 g (half-sinusoidal shock 20 ms)

Switch off technique

Electronic

Climatic proofing

Damp heat, cyclic, to IEC 60068-2-30

Damp heat, constant, to IEC 60068-2-78

Lifespan, mechanical

20000 operations

Document Links

Datasheet