NZM2-XR220-250DC

Remote operator suit.for synchronisation

Trade Price

£679.03

Per

1

Unit

EACH

Pack Quantity

1

NZM2-XR220-250DC

Information

Eaton Moeller series NZM - Molded Case Circuit Breaker. Remote operator, 220-250VAC, for size 2

Technical Specifications

Product Length/Depth

150 mm

Product Height

105 mm

Product Width

105 mm

Product Weight

1.728 kg

Compliances

IEC

UL/CSA

RoHS conform

Certifications

CSA (Class No. 1437-01)

IEC60947

CSA certified

UL (File No. E140305)

CE marking

CSA-C22.2 No. 5-09

UL (Category Control Number DIHS)

UL listed

CSA (File No. 22086)

UL489

10.11 Short-circuit rating

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

Operating voltage - max

1.1 x Us

Frame

NZM2

Signal duration of remote operator at switch off - min

150 ms

Rated control supply voltage (Us) at AC, 50 Hz - min

0 V

10.4 Clearances and creepage distances

Meets the product standard's requirements.

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

Voltage tolerance - min

.85

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

Rated control supply voltage (Us) at DC - min

220 V

Power consumption

250 W (24 - 30 V DC)

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

Rated control supply voltage (Us) at AC, 50 Hz - max

0 V

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

10.8 Connections for external conductors

Is the panel builder's responsibility.

Lifespan, mechanical

20000 operations

Closing delay

60 ms

Voltage rating

220 - 250 V DC

Switch drive type

Motor drive

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

Special features

Cannot be combined with switch-disconnector PN...

Do not install M22-CK11(20/02) dual auxiliary contacts in the center auxiliary contact slot in NZM2-XRD

Voltage tolerance - max

1.1

Rated control supply voltage (Us) at AC, 60 Hz - min

0 V

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

Terminal capacity (solid/flexible conductor)

0.75 mm² - 2.5 mm² with ferrule

18 - 14 AWG

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

Rated control supply voltage (Us) at DC - max

250 V

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

Number of poles

Three-pole/Four-pole

Type

Accessory

Remote operator, can be synchronized

10.2.2 Corrosion resistance

Meets the product standard's requirements.

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.7 Inscriptions

Meets the product standard's requirements.

Breaking time

300 ms

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

Rated control supply voltage (Us) at AC, 60 Hz - max

0 V

Signal duration of remote operator at switch on - min

30 ms

Used with

N(S)2(-4)

NZM2(-4)

Operating voltage - min

0.85 x Us

Number of operations per hour - max

120

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

Voltage type

DC

Document Links

Datasheet