N1-125

MCCB NZM Switch-disconnector 125A 3P

Trade Price

£368.86

Per

1

Unit

EACH

Pack Quantity

1

N1-125
N1-125
N1-125

Information

Eaton Moeller series NZM - Molded Case Circuit Breaker. Switch-disconnector 3p 125A BG1

Technical Specifications

Product Length/Depth

88 mm

Product Height

145 mm

Product Width

90 mm

Product Weight

0.843 kg

Compliances

RoHS conform

Certifications

IEC

IEC/EN 60947

Rated operational current for specified heat dissipation (In)

125 A

10.11 Short-circuit rating

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.4 Clearances and creepage distances

Meets the product standard's requirements.

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

Mounting Method

Fixed

Built-in device fixed built-in technique

Ground mounting

Intermediate mounting

Distribution board installation

Amperage Rating

125 A

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

Terminal capacity (copper strip)

Min. 2 segments of 9 mm x 0.8 mm at box terminal

Max. 9 segments of 9 mm x 0.8 mm at box terminal

Handle type

Rocker lever

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

Ambient storage temperature - min

40 °C

Number of switches

1

Protection against direct contact

Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110

Terminal capacity (copper busbar)

Min. 12 mm x 5 mm direct at switch rear-side connection

M6 at rear-side screw connection

Max. 16 mm x 5 mm direct at switch rear-side connection

10.8 Connections for external conductors

Is the panel builder's responsibility.

Short-circuit protective device fuses - max

125 A gL

Special features

Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.

Isolating characteristics to IEC/EN 60947-3 and VDE 0660.

Busbar tag shroud to VDE 0160 Part 100.

Rated current = rated uninterrupted current: 125 A

Ambient operating temperature - max

70 °C

Rated permanent current at AC-21, 400 V

0 A

Climatic proofing

Damp heat, cyclic, to IEC 60068-2-30

Damp heat, constant, to IEC 60068-2-78

Terminal capacity (copper stranded conductor/cable)

6 mm² - 25 mm² (2x) at box terminal

Terminal capacity hint: Up to 95 mm² can be connected depending on the cable manufacturer

25 mm² - 70 mm² (1x) direct at switch rear-side connection

10 mm² - 70 mm² (1x) at box terminal

25 mm² - 95 mm² (1x) at 1-hole tunnel terminal

25 mm² (2x) direct at switch rear-side connection

Features

Version as maintenance-/service switch

Version as emergency stop installation

Version as main switch

Lifespan, electrical

7500 operations at 690 V AC-1

1000 operations at 415 V AC-23A

1000 operations at 400 V AC-23A

10000 operations at 400 V AC-1

1000 operations at 690 V AC-23A

10000 operations at 415 V AC-1

Electrical connection type of main circuit

Frame clamp

Rated impulse withstand voltage (Uimp) at main contacts

6000 V

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

Number of poles

Three-pole

Switch positions

I, +, 0

Ambient operating temperature - min

-25 °C

Handle color

Black

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

Equipment heat dissipation, current-dependent

17.81 W

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

Rated operational current

160 A (690 V AC-22/23A, making and breaking capacity)

160 A (415 V AC-22/23A, making and breaking capacity)

Application

Use in unearthed supply systems at 690 V

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

Rated operating voltage (Ue) at AC - max

690 V

Degree of protection (IP), front side

IP40 (with insulating surround)

IP20

IP66 (with door coupling rotary handle)

Rated short-circuit making capacity Icm at 690 V, 50/60 Hz

2.8 kA

Rated conditional short-circuit current with back-up fuse

80 kA at 690 V

125 gG/gL

100 kA at 400/415 V

Number of auxiliary contacts (normally closed contacts)

0

Rated conditional short-circuit current (Iq)

0 kA

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

Lifespan, mechanical

20000 operations

Rated operating power at AC-23, 400 V

55 kW

Rated operating frequency

50 Hz

Voltage rating

690 V - 690 V

Terminal capacity (copper solid conductor/cable)

6 mm² - 16 mm² (2x) direct at switch rear-side connection

16 mm² (1x) at tunnel terminal

10 mm² - 16 mm² (1x) at box terminal

10 mm² - 16 mm² (1x) direct at switch rear-side connection

6 mm² - 16 mm² (2x) at box terminal

Degree of protection (terminations)

IP10 (tunnel terminal)

IP00 (terminations, phase isolator and band terminal)

Terminal capacity (aluminum stranded conductor/cable)

25 mm² - 95 mm² (1x) at 1-hole tunnel terminal

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

Degree of protection

IP20 (basic protection type, in the area of the HMI devices)

Overvoltage category

III

Rated short-time withstand current (t = 1 s)

2 kA

Rated impulse withstand voltage (Uimp) at auxiliary contacts

6000 V

Rated short-time withstand current (Icw)

2 kA

Number of auxiliary contacts (change-over contacts)

0

Rated short-time withstand current (t = 0.3 s)

2 kA

Ambient storage temperature - max

70 °C

Optional terminals

Connection on rear. Screw terminal. Tunnel terminal

Pollution degree

3

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

Functions

Voltage release optional

Disconnectors/main switches

Interlockable

Switching power at 400 V

0 kW

Rated conditional short-circuit current with downstream fuse

10 kA at 690 V

125 gG/gL

100 kA at 400/415 V

Standard terminals

Box terminal

Rated operating power at AC-3, 400 V

0 kW

Type

Switch-disconnector

10.2.2 Corrosion resistance

Meets the product standard's requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.7 Inscriptions

Meets the product standard's requirements.

Rated permanent current at AC-23, 400 V

0 A

Number of auxiliary contacts (normally open contacts)

0

Isolation

300 V AC (between the auxiliary contacts)

500 V AC (between auxiliary contacts and main contacts)

Number of operations per hour - max

120

Circuit breaker frame type

N1

Direction of incoming supply

As required

Shock resistance

20 g (half-sinusoidal shock 20 ms)

Rated insulation voltage (Ui)

690 V

Terminal capacity (aluminum solid conductor/cable)

10 mm² - 16 mm² (1x) direct at switch rear-side connection

10 mm² - 16 mm² (2x) direct at switch rear-side connection

16 mm² (1x) at tunnel terminal

Document Links

Datasheet