DILM65(220V50/60HZ)

Contactor, 3-pole 30kW

Trade Price

£257.27

Per

1

Unit

EACH

Pack Quantity

1

DILM65(220V50/60HZ)
DILM65(220V50/60HZ)
DILM65(220V50/60HZ)
DILM65(220V50/60HZ)

Information

Eaton Moeller® series DILM Contactor, 3 pole, 380 V 400 V 30 kW, 220 V 50/60 Hz, AC operation, Screw terminals

Technical Specifications

Product Length/Depth

132.1 mm

Product Height

115 mm

Product Width

55 mm

Product Weight

0.872 kg

Certifications

IEC/EN 60947-4-1

UL File No.: E29096

CE

UL

UL 60947-4-1

UL Category Control No.: NLDX

CSA Class No.: 2411-03, 3211-04

IEC/EN 60947

CSA-C22.2 No. 60947-4-1-14

CSA File No.: 012528

VDE 0660

CSA

Catalog Notes

Contacts according to EN 50012

Number Of Poles

Three-pole

Application

Contactors for Motors

Frame size

FS3

Lifespan, mechanical

10,000,000 Operations (AC operated)

7,000,000 Operations (Coil 50/60 Hz)

Operating frequency

5000 mechanical Operations/h (AC operated)

Overvoltage category

III

Pollution degree

3

Product category

Contactors

Protection

Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)

Rated impulse withstand voltage (Uimp)

8000 V AC

Resistance per pole

1.9 mΩ

Suitable for

Also motors with efficiency class IE3

Utilization category

AC-4: Normal AC induction motors: starting, plugging, reversing, inching

AC-1: Non-inductive or slightly inductive loads, resistance furnaces

AC-3: Normal AC induction motors: starting, switch off during running

Voltage type

AC

Shock resistance

7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms

5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms

10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms

10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms

7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms

5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms

Ambient operating temperature - min

-25 °C

Ambient operating temperature - max

60 °C

Ambient operating temperature (enclosed) - min

25 °C

Ambient operating temperature (enclosed) - max

40 °C

Ambient storage temperature - min

40 °C

Ambient storage temperature - max

80 °C

Climatic proofing

Damp heat, cyclic, to IEC 60068-2-30

Damp heat, constant, to IEC 60068-2-78

Emitted interference

According to EN 60947-1

Interference immunity

According to EN 60947-1

Terminal capacity (copper band)

2 x (6 x 9 x 0.8) mm (Number of segments x width x thickness), Main cables

Terminal capacity (flexible with ferrule)

2 x (0.75 - 25) mm², Main cables

1 x (0.75 - 35) mm², Main cables

1 x (0.75 - 2.5) mm², Control circuit cables

2 x (0.75 - 2.5) mm², Control circuit cables

Terminal capacity (solid)

1 x (0.75 - 4) mm², Control circuit cables

2 x (0.75 - 2.5) mm², Control circuit cables

2 x (0.75 - 16) mm², Main cables

1 x (0.75 - 16) mm², Main cables

Terminal capacity (solid/stranded AWG)

18 - 14, Control circuit cables

Single 14 - 1, double 14 - 2, Main cables

Terminal capacity (stranded)

2 x (16 - 35) mm², Main cables

1 x (16 - 50) mm², Main cables

Stripping length (main cable)

14 mm

Stripping length (control circuit cable)

10 mm

Screw size

M6, Terminal screw, Main cables

M3.5, Terminal screw, Control circuit cables

Screwdriver size

0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver

2, Terminal screw, Pozidriv screwdriver

Tightening torque

3.3 Nm, Screw terminals, Main cables

1.2 Nm, Screw terminals, Control circuit cables

Rated breaking capacity at 220/230 V

650 A

Rated breaking capacity at 380/400 V

650 A

Rated breaking capacity at 500 V

650 A

Rated breaking capacity at 660/690 V

370 A

Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V

98 A

Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V

65 A

Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V

65 A

Rated operational current (Ie) at AC-3, 440 V

65 A

Rated operational current (Ie) at AC-3, 500 V

65 A

Rated operational current (Ie) at AC-3, 660 V, 690 V

37 A

Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V

25 A

Rated operational current (Ie) at AC-4, 400 V

25 A

Rated operational current (Ie) at AC-4, 500 V

25 A

Rated operational current (Ie) at AC-4, 660 V, 690 V

20 A

Rated operational current (Ie) at DC-1, 60 V

72 A

Rated operational current (Ie) at DC-1, 110 V

72 A

Rated operational current (Ie) at DC-1, 220 V

65 A

Rated insulation voltage (Ui)

690 V

Rated operational power at AC-3, 240 V, 50 Hz

22 kW

Rated operational power at AC-3, 380/400 V, 50 Hz

30 kW

Rated operational power at AC-3, 415 V, 50 Hz

39 kW

Rated operational power at AC-4, 220/230 V, 50 Hz

7 kW

Rated operational power at AC-4, 240 V, 50 Hz

7.5 kW

Rated operational power at AC-4, 415 V, 50 Hz

13 kW

Rated operational power at AC-4, 440 V, 50 Hz

14 kW

Rated operational power at AC-4, 500 V, 50 Hz

16 kW

Rated operational power at AC-4, 660/690 V, 50 Hz

17 kW

Rated operational voltage (Ue) at AC - max

690 V

Short-circuit current rating (basic rating)

10 kA, SCCR (UL/CSA)

250 A, max. CB, SCCR (UL/CSA)

250 A, max. Fuse, SCCR (UL/CSA)

Short-circuit current rating (high fault at 480 V)

65 kA, CB, SCCR (UL/CSA)

250/150 A, Class J, max. Fuse, SCCR (UL/CSA)

30/100 kA, Fuse, SCCR (UL/CSA)

100 A, max. CB, SCCR (UL/CSA)

Short-circuit current rating (high fault at 600 V)

30/100 kA, Fuse, SCCR (UL/CSA)

250 A, max. CB, SCCR (UL/CSA)

30 kA, CB, SCCR (UL/CSA)

250/150 A, Class J, max. Fuse, SCCR (UL/CSA)

Short-circuit protection rating (type 1 coordination) at 400 V

250 A gG/gL

Short-circuit protection rating (type 1 coordination) at 690 V

100 A gG/gL

Short-circuit protection rating (type 2 coordination) at 400 V

125 A gG/gL

Short-circuit protection rating (type 2 coordination) at 690 V

80 A gG/gL

Conventional thermal current ith (1-pole, enclosed)

180 A

Conventional thermal current ith (3-pole, enclosed)

72 A

Conventional thermal current ith at 55°C (3-pole, open)

83 A

Conventional thermal current ith of main contacts (1-pole, open)

200 A

Switching capacity (main contacts, general use)

88 A, Maximum motor rating (UL/CSA)

Arcing time

10 ms

Switching time (AC operated, make contacts, closing delay) - min

12 ms

Switching time (AC operated, make contacts, closing delay) - max

18 ms

Switching time (AC operated, make contacts, opening delay) - min

8 ms

Switching time (AC operated, make contacts, opening delay) - max

13 ms

Drop-out voltage

AC operated: 0.6 - 0.3 x UC, AC operated

Duty factor

100 %

Pick-up voltage

0.8 - 1.1 V AC x Uc

Power consumption

30 kW

Power consumption, pick-up, 50 Hz

168 VA, Dual-frequency coil in a cold state and 1.0 x Us

154 VA, Dual-frequency coil in a cold state and 1.0 x Us

Power consumption, pick-up, 60 Hz

154 VA, Dual-frequency coil in a cold state and 1.0 x Us

168 VA, Dual-frequency coil in a cold state and 1.0 x Us

Power consumption, sealing, 50 Hz

4.1 W, Dual-frequency coil in a cold state and 1.0 x Us

Power consumption, sealing, 60 Hz

14 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz

22 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz

4.1 W, Dual-frequency coil in a cold state and 1.0 x Us

Rated control supply voltage (Us) at AC, 50 Hz - min

220 V

Rated control supply voltage (Us) at AC, 50 Hz - max

220 V

Rated control supply voltage (Us) at AC, 60 Hz - min

220 V

Rated control supply voltage (Us) at AC, 60 Hz - max

220 V

Rated control supply voltage (Us) at DC - min

0 V

Rated control supply voltage (Us) at DC - max

0 V

Assigned motor power at 115/120 V, 60 Hz, 1-phase

5 HP

Assigned motor power at 200/208 V, 60 Hz, 3-phase

20 HP

Assigned motor power at 230/240 V, 60 Hz, 1-phase

15 HP

Assigned motor power at 230/240 V, 60 Hz, 3-phase

25 HP

Assigned motor power at 460/480 V, 60 Hz, 3-phase

50 HP

Assigned motor power at 575/600 V, 60 Hz, 3-phase

60 HP

Connection

Screw terminals

Connection to SmartWire-DT

No

Number of auxiliary contacts (normally closed contacts)

0

Number of auxiliary contacts (normally open contacts)

0

Safe isolation

440 V AC, Between the contacts, According to EN 61140

440 V AC, Between coil and contacts, According to EN 61140

Special purpose rating of ballast electrical discharge lamps

88 A (600V 60Hz 3phase, 347V 60Hz 1phase)

88 A (480V 60Hz 3phase, 277V 60Hz 1phase)

Special purpose rating of definite purpose rating

65 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)

390 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)

Special purpose rating of elevator control

32.2 A, 200 V 60 Hz 3-ph, (UL/CSA)

30 HP, 480 V 60 Hz 3-ph, (UL/CSA)

40 HP, 600 V 60 Hz 3-ph, (UL/CSA)

40 A, 480 V 60 Hz 3-ph, (UL/CSA)

42 A, 240 V 60 Hz 3-ph, (UL/CSA)

41 A, 600 V 60 Hz 3-ph, (UL/CSA)

10 HP, 200 V 60 Hz 3-ph, (UL/CSA)

15 HP, 240 V 60 Hz 3-ph, (UL/CSA)

Special purpose rating of resistance air heating

88 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)

88 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)

Special purpose rating of tungsten incandescent lamps

88 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)

88 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)

Equipment heat dissipation, current-dependent Pvid

17.1 W

Heat dissipation capacity Pdiss

0 W

Rated operational current for specified heat dissipation (In)

65 A

10.2.2 Corrosion resistance

Meets the product standard's requirements.

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions

Meets the product standard's requirements.

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

10.4 Clearances and creepage distances

Meets the product standard's requirements.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

10.8 Connections for external conductors

Is the panel builder's responsibility.

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

10.11 Short-circuit rating

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Document Links

Datasheet