DILA-XHI11

aux.contact module, 2-poles, front

Trade Price

£9.10

Per

1

Unit

EACH

Pack Quantity

1

DILA-XHI11
DILA-XHI11
DILA-XHI11
DILA-XHI11

Information

Eaton Moeller® series DILA Auxiliary contact module, 2 pole, Ith= 16 A, 1 N/O, 1 NC, Front fixing, Screw terminals, DILA, DILM7 - DILM38

Technical Specifications

UPC

782116354566

Product Length/Depth

45 mm

Product Height

38 mm

Product Width

36 mm

Product Weight

0.039 kg

Certifications

CE

UL Category Control No.: NKCR

CSA-C22.2 No. 14-05

IEC/EN 60947

CSA

UL

UL 508

UL File No.: E29184

CSA File No.: 012528

IEC/EN 60947-4-1

VDE 0660

CSA Class No.: 3211-03

Features

Interlocked opposing contacts within an auxiliary contact module (according to IEC 60947-5-1 Annex L)

Functions

For standard applications

Fitted with:

Switching elements according to EN 50005

Interlocked opposing contacts

Number of poles

Two-pole

Electric connection type

Screw connection

Degree of protection

IP20

Shock resistance

5 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms

7 g, N/O auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms

Lifespan, electrical

1,300,000 Operations (at 230 V, AC-15, 3 A)

Lifespan, mechanical

10,000,000 Operations (AC operated)

10,000,000 Operations (DC operated)

Model

Top mounting

Mounting method

Front fastening

Operating frequency

9000 Operations/h

Overvoltage category

III

Pollution degree

3

Protection

Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)

Rated impulse withstand voltage (Uimp)

6000 V AC

Type

Front mounting auxiliary contact

Ambient operating temperature - min

-25 °C

Ambient operating temperature - max

60 °C

Ambient operating temperature (enclosed) - min

25 °C

Ambient operating temperature (enclosed) - max

40 °C

Ambient storage temperature - min

40 °C

Ambient storage temperature - max

80 °C

Climatic proofing

Damp heat, cyclic, to IEC 60068-2-30

Damp heat, constant, to IEC 60068-2-78

Terminal capacity (flexible with ferrule)

2 x (0.75 - 2.5) mm², Screw terminals

1 x (0.75 - 2.5) mm², Screw terminals

Terminal capacity (solid)

1 x (0.75 - 2.5) mm², Screw terminals

2 x (0.75 - 2.5) mm², Screw terminals

Terminal capacity (solid/stranded AWG)

18 - 14

Screw size

M3.5, Terminal screw

Screwdriver size

0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver

2, Terminal screw, Pozidriv screwdriver

Tightening torque

1.2 Nm, Screw terminals

Conventional thermal current ith at 60°C (3-pole, open)

16 A

Rated operational current (Ie)

6 A at 110 V, DC L/R <= 15 ms (with 3 contacts in series)

1 A at 60 V, DC L/R <= 50 ms (with 3 contacts in series)

10 A at 60 V, DC L/R <= 15 ms (with 2 contacts in series)

0.5 A at 110 V, DC L/R <= 50 ms (with 3 contacts in series)

3 A at 110 V, DC L/R <= 15 ms (with 1 contact in series)

5 A at 220 V, DC L/R <= 15 ms (with 3 contacts in series)

6 A at 60 V, DC L/R <= 15 ms (with 1 contact in series)

1 A at 220 V, DC L/R <= 15 ms (with 1 contact in series)

2.5 A at 24 V, DC L/R <= 50 ms (with 3 contacts in series)

10 A at 24 V, DC L/R <= 15 ms (with 1 contact in series)

0.25 A at 220 V, DC L/R <= 50 ms (with 3 contacts in series)

Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V

4 A

Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V

4 A

Rated operational current (Ie) at AC-15, 500 V

1.5 A

Rated operational current (Ie) at DC-13, 60 V

1 A

Rated operational current (Ie) at DC-13, 110 V

0.5 A

Rated operational current (Ie) at DC-13, 220 V, 230 V

0.25 A

Rated insulation voltage (Ui)

690 V

Rated operational voltage (Ue) at AC - max

500 V

Short-circuit protection rating

Max. 10 A gG/gL, Fuse, Without welding, Auxiliary contacts

Short-circuit protection rating without welding

10 A gG/gL, 500 V, Max. Fuse, Contacts

Safe isolation

400 V AC, Between auxiliary contacts, According to EN 61140

400 V AC, Between coil and auxiliary contacts, According to EN 61140

Switching capacity (auxiliary contacts, general use)

10 A, 600 V AC, (UL/CSA)

1 A, 250 V DC, (UL/CSA)

Switching capacity (auxiliary contacts, pilot duty)

A600, AC operated (UL/CSA)

P300, DC operated (UL/CSA)

Connection type

Screw connection

Code number

42 in combination with DILA(C)-31

33 in combination with DILA(C)-22

51E in combination with DILA(C)-40

Control circuit reliability

λ < 5 x 10-7 (1 failure at 2,000,000 operations for Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA)

Number of contacts (change-over contacts)

0

Number of contacts (normally closed contacts)

1

Number of contacts (normally open contacts)

1

Equipment heat dissipation, current-dependent Pvid

0 W

Heat dissipation capacity Pdiss

0 W

Heat dissipation per pole, current-dependent Pvid

0.16 W

Rated operational current for specified heat dissipation (In)

4 A

Static heat dissipation, non-current-dependent Pvs

0 W

10.2.2 Corrosion resistance

Meets the product standard's requirements.

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions

Meets the product standard's requirements.

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

10.4 Clearances and creepage distances

Meets the product standard's requirements.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

10.8 Connections for external conductors

Is the panel builder's responsibility.

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

10.11 Short-circuit rating

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Document Links

Datasheet