DS7-340SX009N0-N

Softstart 4kW 9A, 24VDC

Trade Price

£299.61

Per

1

Unit

EACH

Pack Quantity

1

DS7-340SX009N0-N
DS7-340SX009N0-N
DS7-340SX009N0-N
DS7-340SX009N0-N

Information

Eaton DS7 Soft starter, 9 A, 200 - 480 V AC, Us= 24 V AC/DC, Frame size FS1

Technical Specifications

Product Length/Depth

94 mm

Product Height

130 mm

Product Width

45 mm

Product Weight

0.35 kg

Certifications

UL File No.: E251034

CSA Class No.: 321106

CE

CSA File No.: 2511305

CSA-C22.2 No 14-05

UL

C-Tick

GB 14048.6

UL 508

CSA22.2-14

CSA-C22.2 No 0-M91

UkrSEPRO

IEC/EN 60947-4-2

CSA

Fitted with:

Internal bypass contacts

Internal bypass

Functions

Soft start function

Suppression of DC components for motors

Potential isolation between power and control sections

Suppression of closing transients

Min. ramp time 1 s - fast switching (semiconductor contactor)

Single direction

Class

Other

Connection to SmartWire-DT

No

Degree of protection

IP20

NEMA 1

Frame size

FS1

Mains voltage - max

480 V

Mains voltage - min

200 V

Overvoltage category

II

Pollution degree

2

Radio interference class

Class B (EN 55011)

Suitable for

Branch circuits, (UL/CSA)

Type

Soft starter for three-phase loads

Voltage type

AC/DC

Mounting position

Vertical

Shock resistance

8 g, 11 ms, Mechanical

Vibration resistance

2M2 to EN 60721-3-2

Altitude

Max. 2000 m

Above 1000 m with 1 % derating per 100 m

Ambient operating temperature - max

40 °C

Ambient operating temperature - min

-5 °C

Climatic proofing

Damp heat, constant, to IEC 60068-2-3

Damp heat, cyclic, to IEC 60068-2-30

Overload cycle

AC-53a: 3 - 5: 75 - 10

Rated operational current (Ie) at AC-53

9 A

Rated operational voltage (Ue) - max

480 V

Rated operational voltage (Ue) - min

230 V

Short-circuit protection rating

PKM0-10 (+ CL-PKZ0), Type “1” coordination, Main conducting paths

3 x 170M1362, Type „2“ coordination (additional with the fuses for coordination type „1“), Main conducting paths

Supply frequency

50/60 Hz, fLN, Main circuit

Voltage rating - max

480 V

Assigned motor power at 200/208 V, 60 Hz, 3-phase

2 HP

Assigned motor power at 220/230 V, 60 Hz, 3-phase

3 HP

Assigned motor power at 460/480 V, 60 Hz, 3-phase

5 HP

Rated operational power at 220/230 V, 50 Hz

2.2 kW

Rated operational power at 400 V, 50 Hz

4 kW

Terminal capacity (flexible with ferrule)

1 x (0.75 - 2.5) mm², Main cables

2 x (0.75 - 2.5) mm², Main cables

1 x (0.75 - 2.5) mm², Control circuit cables

2 x (0.75 - 2.5) mm², Control circuit cables

Terminal capacity (solid)

2 x (0.75 - 2.5) mm², Main cables

2 x (0.75 - 2.5) mm², Control circuit cables

1 x (0.75 - 4) mm², Control circuit cables

1 x (0.75 - 4) mm², Main cables

Terminal capacity (solid/stranded AWG)

18 - 10, Control circuit cables

18 - 10, Main cables

Screwdriver size

PZ2, 1 x 6 mm, Terminal screw, Standard screwdriver

0.6 x 5.5 mm/1 x 6 mm, Terminal screws, Control circuit cables

Tightening torque

1.2 Nm, Screw terminals, Control circuit cables

1.2 Nm

Current consumption

50 mA, Control circuit, Regulator supply

1.6 mA, Control circuit, Digital inputs, External 24 V

Drop-out time

350 ms, Control circuit, Digital Inputs, DC operated

Drop-out voltage

0 - 3 V, DC operated

AC operated: 0 - 3 V, AC operated

Rated control supply voltage (Us) at AC, 50 Hz - min

24 V

Rated control supply voltage (Us) at AC, 60 Hz - max

24 V

Rated control supply voltage (Us) at AC, 60 Hz - min

24 V

Rated control supply voltage (Us) at DC - max

24 V

Rated control supply voltage (Us) at DC - min

24 V

Number of outputs

1 Relay Output (TOR)

Output voltage

24 V AC/DC

Protection

Finger and back-of-hand proof, Protection against direct contact

Rated control voltage (Uc)

24 V DC (-15 %/+10 %)

24 V AC (-15 %/+10 %)

24 V DC

24 V AC

Rated operational current (Ie) at AC-11

1 A

Application

1-phase motors: No

3-phase motors: Yes

Soft starting of three-phase asynchronous motors

Delay time

0 - 30 s, Soft start function, Ramp times

Ramp/run-up time

1 - 30 s

Start voltage

Min. 30 %, Soft start function, Start voltage = turn-off voltage

Max. 100 %, Soft start function, Start voltage = turn-off voltage

Equipment heat dissipation, current-dependent Pvid

0.45 W

Heat dissipation capacity Pdiss

0 W

Heat dissipation per pole, current-dependent Pvid

0 W

Rated operational current for specified heat dissipation (In)

9 A

Static heat dissipation, non-current-dependent Pvs

0.45 W

10.2.2 Corrosion resistance

Meets the product standard's requirements.

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions

Meets the product standard's requirements.

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

10.4 Clearances and creepage distances

Meets the product standard's requirements.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

10.8 Connections for external conductors

Is the panel builder's responsibility.

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

10.11 Short-circuit rating

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Document Links

Datasheet