Trade Price
£11,581.49
Per
1
Unit
EA
Pack Quantity
1
C.BREAKER SACE EMAX2 E2.2N 2000 FIXED THREE-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/G/HI-TOUCH-LSIG R 2000 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 79.1 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
66ae4190-25b7-4428-9454-a5a2943c47f5 Italy (IT)
Simplified SCIP
39f39d09-f69a-436c-bb9a-04f3f8fc75fa Spain (ES)dfa08576-2e86-42cd-848b-ead7bc5c513e Hungary (HU)eac8cdb1-f63e-4f0e-a6d6-0e4bad3910b7 France (FR)bb5b64fa-fb3f-4669-8e29-35d86d6ab771 Norway (NO)5b0b3dd4-4962-48b6-9464-14042fd334da Poland (PL)dafd8080-dde3-4107-be7a-be772b09f017 France (FR)8cb48e5c-d82e-4726-a668-2b5c3dd444a4 Bulgaria (BG)11ac92d9-9caa-4719-98d9-b9c50185d4bd Germany (DE)d8373eb1-df52-4df9-8680-2b2f2a7dda6a Croatia (HR)1000df6e-ad03-4fb1-befa-0c06ab6f3cc9 Germany (DE)65333405-f605-4e4e-8154-fad7040ad03f Germany (DE)fecc2b35-70ec-4db3-a22a-1258ffb989f2 Denmark (DK)b1b77157-98cf-42aa-b6b3-5fe49366330a Germany (DE)6ace8439-036d-46fa-8093-e4ac05b3cc26 Belgium (BE)d6a126f2-7171-42cb-bd14-779ade511c4a Finland (FI)3d3e7920-1845-4826-bb8d-c3b3a99359ee Netherlands (NL)7d47910b-d3bb-4736-bbd8-6c3192b8532a Sweden (SE)51c7a8fa-c35b-4b11-b5bd-133a44b38ca1 Estonia (EE)c18249e9-4fd3-4e30-8fa9-b56e050d052a Greece (GR)d6940327-68d4-470c-89bc-1d4074331f40 Poland (PL)c1ebe785-9750-42c7-8292-7e9b24b4b944 Czech Republic (CZ)47f9ad1b-bdcb-4d6d-bb90-4dd1c765c0a8 Poland (PL)554b7eef-427b-4e28-a88f-8048472afca1 Sweden (SE)904fa438-d5e0-4b33-a2cc-fb4d3bf645d6 Portugal (PT)44c082ed-df70-4a37-b79c-00bfb5224820 Hungary (HU)98f07ae4-7f11-4ef8-afa7-b01a454fa2da Belgium (BE)
Order Code US and Canada
Z2NTEKBQ200A000000XX
EAN
8015644748906
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
276 mm
Product Net Height
371 mm
Product Net Depth / Length
270 mm
Product Net Weight
41 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
515 mm
Package Level 1 Height
610 mm
Package Level 1 Depth / Length
515 mm
Package Level 1 Gross Weight
46 kg
Package Level 1 EAN
8015644748906
Current Type
AC
Electrical Durability
Ue =< 440 V 10000 cycleUe = 500 ... 690 V 8000 cycle30 cycles per hour
Mechanical Durability
25000 cycle60 cycles per hour
Number of Poles
3
Power Loss
212 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
2000 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 66 kA(230 V AC) 66 kA(380 V AC) 66 kA(400 V AC) 66 kA(415 V AC) 66 kA(440 V AC) 66 kA(500 V AC) 66 kA(660 V AC) 66 kA(690 V AC) 66 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 66 kAfor 3 s 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 66 kA(415 V AC) 66 kA(440 V AC) 66 kA(500 V AC) 66 kA(525 V AC) 66 kA(690 V AC) 66 kA
Rated Uninterrupted Current (Iu)
2000 A
Release
Ekip G Hi-Touch LSIG
Release Type
EL
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
E2.2
Terminal Connection Type
Rear flat Horizontal
Version
F
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
UNSPSC
39121615
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet