1SDA073381R1

E6.2X/f 6300 Ekip Dip LI 4p WMP

Trade Price

£72,322.79

Per

1

Unit

EA

Pack Quantity

1

1SDA073381R1
1SDA073381R1
1SDA073381R1

Information

MOVING PART FOR C.BREAKER SACE EMAX2 E6.2X/f 6300 FOUR-POLE FULL SIZE NEUTRAL WITH SOLID-STATE RELEASE IN AC EKIP/DIP-LI R 6300 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED

Technical Specifications

ABB EcoSolutions

Yes

Circular Design Principles Recyclability Rate

Design for Closing Resource Loops - Standard EN45555 - 77 %

Group Waste to Landfill Target

UL 2799 Zero Waste To Landfill Validation available

RoHS Status

Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

SCIP

62d9662b-1fa1-442a-aa0a-ba281aa6a509 Italy (IT)

Simplified SCIP

c7dd754d-26b5-4064-a0e8-b138f86bdaa7 Spain (ES)1730199d-6d8c-40a2-a4cf-b15843579214 Belgium (BE)9cd80f24-7caa-4fab-a66b-326693ad358c Hungary (HU)348eb8da-d912-4e79-90bc-7164ecc1781e France (FR)76cfd2c0-f455-4991-b3d5-0c69171c5632 Norway (NO)989e7b37-de3c-4e05-98e8-710f63668121 Hungary (HU)e1b8829d-8682-43f0-934c-dec08cb0613c Poland (PL)f08df707-599f-4e11-b8aa-61cbbef9c092 Czech Republic (CZ)a5e25d3b-58a5-4962-9003-6f1691e5a526 Estonia (EE)747cde54-74f9-464e-8b9b-01e57e2ba6a7 Netherlands (NL)f3406f8b-9bff-4ed5-babb-016a21b225d5 Finland (FI)ab1eed5c-f914-4062-97c9-f88ee8f48ec2 Germany (DE)67f5bcc3-c98a-4e21-be6b-1b903ce61ff1 Denmark (DK)97cb2b42-073f-4f7d-bd89-9794e60f882d Germany (DE)89bdc8c4-48b1-40fc-8b27-41dc46bbed6c Belgium (BE)b2a9a2d7-267f-41b1-9d1b-d347e5f33fa6 Sweden (SE)ea0a9f0a-2018-4976-ab79-5cf1370d8688 Germany (DE)8e3117d9-ad75-477f-b4b2-b6ec81a7bcf3 France (FR)1d668ce6-5375-49dd-8fcb-e0d0a6f530f6 Germany (DE)e854316c-0958-48e1-ac97-c0acaf76de39 Croatia (HR)482d86eb-0c58-46f8-87aa-963fc21a811a Greece (GR)e569994a-68f0-48fa-8922-4c0c28e0f78f Poland (PL)d3b1b5db-f05d-4c3b-8ca9-3aa1e8adf776 Poland (PL)32e2de42-b647-43c0-ad04-b20c6b374758 Sweden (SE)16a9c29e-6d35-4317-b9c4-af7175e0a0e9 Bulgaria (BG)6557173f-a3fa-4d18-8136-e2e46aa5f6f6 Portugal (PT)

EAN

8015644772314

Minimum Order Quantity

1 piece

Customs Tariff Number

85362090

Product Net Width

1069 mm

Product Net Height

425 mm

Product Net Depth / Length

383 mm

Product Net Weight

148 kg

Package Level 1 Units

box 1 piece

Package Level 1 Width

515 mm

Package Level 1 Height

610 mm

Package Level 1 Depth / Length

1257 mm

Package Level 1 Gross Weight

159 kg

Package Level 1 EAN

8015644772314

Current Type

AC

Electrical Durability

Ue =< 440 V 2000 cycleUe = 500 ... 690 V 2000 cycle10 cycles per hour

Mechanical Durability

12000 cycle60 cycles per hour

Neutral Pole Current ([%Iu])

100 %

Number of Poles

4 / f

Power Loss

1550 W

Product Main Type

SACE Emax 2

Product Name

Air Circuit Breaker

Product Type

Air Circuit Breaker

Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)

100 %

Rated Current (In)

6300 A

Rated Voltage (Ur)

690 V

Rated Impulse Withstand Voltage (Uimp)

acc. to IEC 60947-2 12 kV

Rated Insulation Voltage (Ui)

AC 1000 V

Rated Operational Voltage

690 V AC

Rated Service Short-Circuit Breaking Capacity (Ics)

(220 V AC) 100 kA(230 V AC) 100 kA(380 V AC) 100 kA(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 100 kA(660 V AC) 100 kA(690 V AC) 100 kA

Rated Short-time Withstand Current Low Voltage (Icw)

for 1 s 120 kAfor 3 s 100 kA

Rated Ultimate Short-Circuit Breaking Capacity (Icu)

(440 V AC) 200 kA

Rated Uninterrupted Current (Iu)

6300 A

Release

Ekip Dip LI

Release Type

EL

Short-Circuit Performance Level

X

Standards

IEC

Sub-type

E6.2

Version

W

ETIM 7

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 8

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 9

EC000228 - Power circuit-breaker for trafo/generator/installation protection

Object Classification Code

Q

WEEE Category

4. Large Equipment (Any External Dimension More Than 50 cm)

eClass

V11.1 : 27370409

Document Links

Catalogue page

Datasheet