Trade Price
£1,294.19
Per
1
Unit
EA
Pack Quantity
1
C.BREAKER TMAX XT4H 250 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 250 I3=1250...2500 A NEUTRAL = 50% PHASES
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 58.5 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
571db8c6-6a5f-4ae7-9512-95139f2f36eb Italy (IT)
Simplified SCIP
92508ba4-e381-457a-803d-4c20fceaec96 France (FR)536d64b3-3620-4c75-aa4f-6580c6bb36a9 Sweden (SE)6b8d14fd-2e34-47e4-bdf2-5df52e44af64 Germany (DE)d9330861-203a-4513-99bc-d0e392d86712 Germany (DE)ccd3f77c-730a-4c24-b18d-bfd975905f58 France (FR)fee1db6e-ae87-4b16-b47b-797614a84c33 Netherlands (NL)e86a4794-5d20-4c90-bbd3-ca6048f5d30a Spain (ES)24f1af20-ad04-49a6-9a43-673595650f39 Netherlands (NL)a7937485-98f9-48fa-bab7-51dbf5def2e4 Poland (PL)0a4f61b4-9c67-45d3-90a5-e62eb6aa1f0d Norway (NO)5224b044-d956-4588-ad85-a409979e79b0 Finland (FI)d4a47e4f-d8d7-48ed-8fa3-67423918b192 Netherlands (NL)e42866ab-67f9-4e16-942d-0dc9e1e44cda Germany (DE)71dc626c-7226-4a7c-acfb-274b65c2f20f Denmark (DK)74a45bf5-394f-47ec-81ed-82fe2dcb605b Germany (DE)c46d23ce-a8a2-4a12-9985-b3d83b2ae571 Croatia (HR)e706a55a-9588-4736-8046-49db473baf81 Czech Republic (CZ)b9d8b2df-1346-4b5c-8ebc-c7c5b049bb6f Poland (PL)0873d7ea-c065-49fd-b4eb-f951b105e712 Netherlands (NL)d8bd6c62-f9fb-43a1-a617-718a05e878d0 Netherlands (NL)40034fe5-617c-4e1b-bf07-0021e575ff36 Estonia (EE)b2dce1bc-5eb9-4124-bfc4-fc3e542d345a Greece (GR)21267a55-5a49-415b-a24e-4682d763496f Portugal (PT)9c1d8b1f-46d8-4616-a816-02a76c6990de Bulgaria (BG)a434ab62-0b6c-4b4a-bdd8-b7c66123b7f7 Sweden (SE)22d7c79e-67e9-4fa3-8b57-07f8dc221157 Poland (PL)
Order Code US and Canada
XT4HEN250BFF000XXX
EAN
8015644022655
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
140 mm
Product Net Height
160 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
3.5 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
145 mm
Package Level 1 Height
210 mm
Package Level 1 Depth / Length
168 mm
Package Level 1 Gross Weight
3.5 kg
Package Level 1 EAN
8015644022655
Circuit Breaker Type to be Associated
Power Distribution
Connecting Capacity Main Circuit
Busbar 85..200 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour8000 cycle
Mechanical Durability
240 cycles per hour25000 cycle
Number of Poles
4
Opening Time
CB with SOR 15 msCB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 16.44 W
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Rated Current (In)
250 A
Rated Frequency (f)
50 / 60 Hz
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
1250…2500 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA(230 V AC) 100 kA(240 V AC) 100 kA(380 V AC) 70 kA(415 V AC) 70 kA(440 V AC) 65 kA(500 V AC) 50 kA(525 V AC) 45 kA(690 V AC) 15 kA(250 V DC) 2 Poles in Series 70 kA(500 V DC) 2 Poles in Series 70 kA(500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA(230 V AC) 100 kA(240 V AC) 100 kA(380 V AC) 70 kA(415 V AC) 70 kA(440 V AC) 65 kA(500 V AC) 50 kA(525 V AC) 45 kA(690 V AC) 15 kA(250 V DC) 2 Poles in Series 70 kA(500 V DC) 2 Poles in Series 70 kA(500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
250 A
Recommended Screw Driver
Main Circuit M8
Release
TMA
Release Type
TM
Setting Range
175...250 A
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
XT4
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
8 N·m
Version
F
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet