1SDA067729R1

XT2N 160 TMG 25-160 4p F F

Trade Price

£402.09

Per

1

Unit

EA

Pack Quantity

1

1SDA067729R1
1SDA067729R1
1SDA067729R1
1SDA067729R1

Information

C.BREAKER TMAX XT2N 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMG R 25-160 A

Technical Specifications

ABB EcoSolutions

Yes

Circular Design Principles Recyclability Rate

Design for Closing Resource Loops - Standard EN45555 - 58.1 %

Group Waste to Landfill Target

UL 2799 Zero Waste To Landfill Validation available

RoHS Status

Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Order Code US and Canada

XT2NE4025NFF000XXX

EAN

8015644016258

Minimum Order Quantity

1 piece

Customs Tariff Number

85362090

Product Net Width

120 mm

Product Net Height

130 mm

Product Net Depth / Length

82.5 mm

Product Net Weight

1.45 kg

Package Level 1 Units

box 1 piece

Package Level 1 Width

131 mm

Package Level 1 Height

212 mm

Package Level 1 Depth / Length

147 mm

Package Level 1 Gross Weight

1.55 kg

Package Level 1 EAN

8015644016258

Circuit Breaker Type to be Associated

Generator Protection

Connecting Capacity Main Circuit

Busbar 32.5..100 mm²

Current Type

AC/DC

Electrical Durability

120 cycles per hour8000 cycle

Mechanical Durability

240 cycles per hour25000 cycle

Number of Poles

4

Opening Time

CB with SOR 15 msCB with UVR 15 ms

Order Multiple

1 piece

Power Loss

at Rated Operating Conditions per Pole 2 W

Product Main Type

SACE Tmax XT

Product Name

Moulded Case Circuit Breaker

Product Type

Automatic Circuit Breaker

Rated Current (In)

25 A

Rated Frequency (f)

50 / 60 Hz

Rated Voltage (Ur)

690 V

Rated Impulse Withstand Voltage (Uimp)

8 kV

Rated Instantaneous Short-Circuit Current Setting (Ii)

160 A

Rated Insulation Voltage (Ui)

1000 V

Rated Operational Voltage

690 V AC500 V DC

Rated Service Short-Circuit Breaking Capacity (Ics)

(220 V AC) 65 kA(230 V AC) 65 kA(240 V AC) 65 kA(380 V AC) 36 kA(415 V AC) 36 kA(440 V AC) 36 kA(500 V AC) 30 kA(525 V AC) 20 kA(690 V AC) 10 kA(250 V DC) 2 Poles in Series 36 kA(500 V DC) 3 Poles in Series 36 kA

Rated Ultimate Short-Circuit Breaking Capacity (Icu)

(220 V AC) 65 kA(230 V AC) 65 kA(240 V AC) 65 kA(380 V AC) 36 kA(415 V AC) 36 kA(440 V AC) 36 kA(500 V AC) 30 kA(525 V AC) 20 kA(690 V AC) 10 kA(250 V DC) 2 Poles in Series 36 kA(500 V DC) 3 Poles in Series 36 kA

Rated Uninterrupted Current (Iu)

160 A

Recommended Screw Driver

Main Circuit M6

Release

TMG

Release Type

TM

Setting Range

17.5...25 A

Short-Circuit Performance Level

N

Standards

IEC

Sub-type

XT2

Terminal Connection Type

Front

Terminal Type

Bolt

Tightening Torque

6 N·m

Version

F

ETIM 7

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 8

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 9

EC000228 - Power circuit-breaker for trafo/generator/installation protection

Object Classification Code

Q

UNSPSC

39120000

WEEE Category

5. Small Equipment (No External Dimension More Than 50 cm)

eClass

V11.1 : 27370409

Document Links

Catalogue page

Datasheet