Trade Price
£1,080.86
Per
1
Unit
EA
Pack Quantity
1
C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSI R 25 A
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 58.1 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
2106b44b-be3f-4c3c-9a01-fd84137ef969 Italy (IT)
Simplified SCIP
2aceea2a-1acc-43ae-b555-f0a775044831 Spain (ES)d64ed949-c6dd-4490-9692-19d973d88d8f Netherlands (NL)62ce2102-7109-4a9a-a6e1-1e46947f63f1 Bulgaria (BG)61920386-0fc5-4405-b6b8-e51400070e53 Sweden (SE)30a4ccb1-2ea9-4a11-aa73-02176605785b Poland (PL)9e83677e-29a1-4808-912d-16590d5f6b89 France (FR)3b6ef031-b7c1-42f3-a1e0-0586a5ede4e4 Sweden (SE)4bb8d337-ee96-4da1-a701-683420ed2f30 Czech Republic (CZ)113470e5-4497-45a7-b1d6-7f5b4c8352ce Poland (PL)c8b931e9-93ec-48ff-bbdc-8f16aa621b5d Netherlands (NL)52ae7242-322f-4c2a-bc1d-6048c5c4be11 Germany (DE)886166e9-6a6b-4815-a06d-4e8e6f40d5b3 Germany (DE)9db71cba-35b0-4123-8ffd-6cd4836f57a8 France (FR)bf3428c6-93ab-4a0e-90a8-a392e9346283 Netherlands (NL)10a52efc-f384-4bb2-a34e-27eff6f77071 Poland (PL)c89e19b9-18a6-4d47-a821-9c727a36b4c1 Norway (NO)e5404139-e9c1-4812-8b3f-75b6813a5e86 Finland (FI)c98f1102-294a-47aa-8847-ed1e244d395b Netherlands (NL)47516cb5-5d0f-4b5c-924e-f18d009697d5 Germany (DE)ce4d041d-5abd-4db4-befd-899e6925c0a2 Denmark (DK)81609064-7abd-4df8-b92d-63f9b91ef620 Netherlands (NL)ee2ec47e-df40-4ece-9c72-6bab12e42e97 Estonia (EE)1a83d47b-eac9-407b-8bd3-5af7aa4c1901 Greece (GR)96917fd6-4ba2-4c16-9713-5c0dd645cd60 Portugal (PT)bcff678c-2790-4886-9594-e6673e410200 Germany (DE)ff198d09-d985-4a3a-9184-5f98fe7527c2 Croatia (HR)
Order Code US and Canada
XT2HE3025FFF000XXX
EAN
8015644017644
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.22 kg
Package Level 1 EAN
8015644017644
Circuit Breaker Type to be Associated
Power Distribution
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour8000 cycle
Mechanical Durability
240 cycles per hour25000 cycle
Number of Poles
3
Opening Time
CB with SOR 15 msCB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 0.80 W
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Rated Current (In)
25 A
Rated Frequency (f)
50/60 Hz
Rated Voltage (Ur)
690 V AC
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA(230 V AC) 100 kA(240 V AC) 100 kA(380 V AC) 70 kA(415 V AC) 70 kA(440 V AC) 65 kA(500 V AC) 50 kA(525 V AC) 30 kA(690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA(230 V AC) 100 kA(240 V AC) 100 kA(380 V AC) 70 kA(415 V AC) 70 kA(440 V AC) 65 kA(500 V AC) 50 kA(525 V AC) 30 kA(690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Recommended Screw Driver
Main Circuit M6
Release
Ekip LSI
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Version
F
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet