Trade Price
£801.00
Per
1
Unit
EA
Pack Quantity
1
C.BREAKER TMAX XT3S 250 FIXED THREE-POLE WITH FRONT TERMINALS AND MAGNETIC RELEASE MA Iu 200 A I3=1200...2400 A
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 56.6 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Order Code US and Canada
XT3SE3200MFF000XXX
EAN
8015644021887
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
105 mm
Product Net Height
150 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.7 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
150 mm
Package Level 1 Height
190 mm
Package Level 1 Depth / Length
155 mm
Package Level 1 Gross Weight
1.7 kg
Package Level 1 EAN
8015644021887
Circuit Breaker Type to be Associated
Motor Protection
Connecting Capacity Main Circuit
Busbar 85..192 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour8000 cycle
Mechanical Durability
240 cycles per hour25000 cycle
Number of Poles
3
Opening Time
CB with SOR 15 msCB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 13.2 W
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Rated Current (In)
200 A
Rated Frequency (f)
50 / 60 Hz
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
1200…2400 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 42.5 kA(230 V AC) 42.5 kA(240 V AC) 42.5 kA(380 V AC) 27 kA(415 V AC) 27 kA(440 V AC) 20 kA(500 V AC) 15 kA(525 V AC) 10 kA(690 V AC) 3 kA(250 V DC) 2 Poles in Series 27 kA(500 V DC) 3 Poles in Series 37.5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA(230 V AC) 85 kA(240 V AC) 85 kA(380 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 40 kA(500 V AC) 30 kA(525 V AC) 20 kA(690 V AC) 6 kA(250 V DC) 2 Poles in Series 36 kA(500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
250 A
Recommended Screw Driver
Main Circuit M8
Release
MA
Release Type
M
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
XT3
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
8 N·m
Version
F
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet