Trade Price
£949.41
Per
1
Unit
EA
Pack Quantity
1
C.BREAKER TMGX XT2S 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMG R 125-375 A FULLY RATED NEUTRAL
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 58.1 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Order Code US and Canada
XT2SE4125NFF000XXX
EAN
8015644016548
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.55 kg
Package Level 1 EAN
8015644016548
Circuit Breaker Type to be Associated
Generator Protection
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour8000 cycle
Mechanical Durability
240 cycles per hour25000 cycle
Number of Poles
4
Opening Time
CB with SOR 15 msCB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 11.4 W
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Rated Current (In)
125 A
Rated Frequency (f)
50 / 60 Hz
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
375 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA(230 V AC) 85 kA(240 V AC) 85 kA(380 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 36 kA(525 V AC) 25 kA(690 V AC) 12 kA(250 V DC) 2 Poles in Series 50 kA(500 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA(230 V AC) 85 kA(240 V AC) 85 kA(380 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 36 kA(525 V AC) 25 kA(690 V AC) 12 kA(250 V DC) 2 Poles in Series 50 kA(500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Recommended Screw Driver
Main Circuit M6
Release
TMG
Release Type
TM
Setting Range
87.5...125 A
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Version
F
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet