1SDA067095R1

XT2N 160 Ekip LS/I In=160A 4pFF InN=100%

Trade Price

£886.89

Per

1

Unit

EA

Pack Quantity

1

1SDA067095R1
1SDA067095R1
1SDA067095R1
1SDA067095R1

Information

C.BREAKER TMAX XT2N 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LS/I R 160 A FULLY RATED NEUTRAL

Technical Specifications

ABB EcoSolutions

Yes

Circular Design Principles Recyclability Rate

Design for Closing Resource Loops - Standard EN45555 - 58.1 %

Group Waste to Landfill Target

UL 2799 Zero Waste To Landfill Validation available

RoHS Status

Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

SCIP

060aee7b-5a26-4fae-8f26-8f1c6617efea Italy (IT)

Simplified SCIP

9eedccba-1741-4fb3-832c-b25430f4097a Portugal (PT)ad4eaa00-9906-4f87-84aa-ca6c3f7abc71 Germany (DE)2e034345-ac69-4ed8-8266-e2290d415876 Poland (PL)0c6cb474-c50a-407d-bdd8-7ceb19763ad5 Sweden (SE)2d2833d1-a110-4c1d-8f50-c9893d52e736 Germany (DE)c82ad2c3-f14b-4d68-8b20-9d8e2366b8a5 France (FR)b170c593-db9c-4e08-a9ba-41a71a24ca03 Netherlands (NL)638cccd1-810b-480e-9886-78dfc6d7c333 Spain (ES)fb7cd8d4-c343-45af-a6b4-c37e3f85585e Netherlands (NL)ff541252-0325-4734-955b-630a690a053d Bulgaria (BG)e05a9fa1-1297-44ed-8e6b-72d556defa55 Sweden (SE)191bf99a-6193-4124-99c5-db1c281d4e3d Poland (PL)58371b36-a778-4817-b9ca-4f8b42bbc516 France (FR)22dc3bb0-090d-41d0-9027-c23085688625 Norway (NO)a926e7b1-bd09-4c30-89a0-ff1962ef4325 Finland (FI)82200646-bc7f-4dc3-a52b-aac649a9d008 Netherlands (NL)e682dd60-feee-45ed-9233-0035d9bd145c Germany (DE)14e54362-1193-4281-a740-b2bf446faf41 Denmark (DK)0b648ecd-95bf-4bc0-bf88-525b258e96c4 Germany (DE)ab2c4e17-1358-471f-b9c0-febe9be88731 Croatia (HR)43e6cd2c-a63f-4374-8e95-a0cf137bab6e Czech Republic (CZ)d4b57ea0-cf79-4670-9404-9af0e36832fc Poland (PL)e9134eed-e26d-4c09-8bd6-b74d5013184f Netherlands (NL)0296f209-3e4f-4104-a06a-47dcb425a87e Netherlands (NL)86dbb277-8032-4d4d-b348-98ddd18d920d Estonia (EE)a2f1f056-6fff-4ba1-88df-47543602eb5e Greece (GR)

Order Code US and Canada

XT2NE4160EFF000XXX

E-Number (Finland)

3640567

E-Number (Sweden)

3182035

EAN

8015644010003

Minimum Order Quantity

1 piece

Customs Tariff Number

85362090

Product Net Width

120 mm

Product Net Height

130 mm

Product Net Depth / Length

82.5 mm

Product Net Weight

1.6 kg

Package Level 1 Units

box 1 piece

Package Level 1 Width

130 mm

Package Level 1 Height

208 mm

Package Level 1 Depth / Length

145 mm

Package Level 1 Gross Weight

1.6 kg

Package Level 1 EAN

8015644010003

Circuit Breaker Type to be Associated

Power Distribution

Connecting Capacity Main Circuit

Busbar 32.5..100 mm²

Current Type

AC

Electrical Durability

120 cycles per hour8000 cycle

Mechanical Durability

240 cycles per hour25000 cycle

Number of Poles

4

Opening Time

CB with SOR 15 msCB with UVR 15 ms

Order Multiple

1 piece

Power Loss

at Rated Operating Conditions per Pole 10.8 W

Product Main Type

SACE Tmax XT

Product Name

Moulded Case Circuit Breaker

Product Type

Automatic Circuit Breaker

Rated Current (In)

160 A

Rated Frequency (f)

50 / 60 Hz

Rated Voltage (Ur)

690 V

Rated Impulse Withstand Voltage (Uimp)

8 kV

Rated Insulation Voltage (Ui)

1000 V

Rated Operational Voltage

690 V AC

Rated Service Short-Circuit Breaking Capacity (Ics)

(220 V AC) 65 kA(230 V AC) 65 kA(240 V AC) 65 kA(380 V AC) 36 kA(415 V AC) 36 kA(440 V AC) 36 kA(500 V AC) 30 kA(525 V AC) 20 kA(690 V AC) 10 kA

Rated Ultimate Short-Circuit Breaking Capacity (Icu)

(220 V AC) 65 kA(230 V AC) 65 kA(240 V AC) 65 kA(380 V AC) 36 kA(415 V AC) 36 kA(440 V AC) 36 kA(500 V AC) 30 kA(525 V AC) 20 kA(690 V AC) 10 kA

Rated Uninterrupted Current (Iu)

160 A

Recommended Screw Driver

Main Circuit M6

Release

Ekip LS/I

Release Type

EL

RoHS Date

NA

Short-Circuit Performance Level

N

Standards

IEC

Sub-type

XT2

Terminal Connection Type

Front

Terminal Type

Bolt

Tightening Torque

6 N·m

Version

F

ETIM 7

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 8

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 9

EC000228 - Power circuit-breaker for trafo/generator/installation protection

Object Classification Code

Q

WEEE Category

5. Small Equipment (No External Dimension More Than 50 cm)

eClass

V11.1 : 27370409

Document Links

Catalogue page

Datasheet