C.BREAKER TMAX XT2N 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 160 I3=800...1600 A
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 58.1 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
d519e276-d4b0-4b42-8a55-c1a563681fc8 Italy (IT)
Simplified SCIP
a2e7e927-2395-4bdc-be8d-810d0cb0ae45 Portugal (PT)e89088df-21ed-4d26-b95c-a0480b45024d Bulgaria (BG)e5f2f46a-2fd6-4c7e-bb25-a46cf48987e3 France (FR)6e917ee4-4216-40f5-a8a3-e310dc60dc70 Norway (NO)e5692b23-c0ac-4f4c-8b6c-d1ade35c30c2 Finland (FI)45c61df3-6641-4084-81a3-7d93bafd3854 Netherlands (NL)911050ef-ac90-4e21-b4b9-a662112db80f Spain (ES)24003ffc-e1a5-47bb-a8b8-451202db8f05 Netherlands (NL)eda1b4f0-a70f-4d5d-9cd4-b12af82bd479 Poland (PL)6a135342-7f65-41e7-bf92-aafb3e7dba8f Sweden (SE)e90f788c-8237-4208-bcbb-b57b6e8c6f34 Poland (PL)6bde395d-b3ce-4547-bfe6-9d0f2acce853 Sweden (SE)7baa1ff8-47fc-47fa-9a52-115afb224150 Germany (DE)21953dfb-88b7-46f1-aef2-9ca2ee14f1ce Germany (DE)80fdd440-e1f4-40c8-84f2-ebdf68d25284 France (FR)7e70c592-6fe7-42ff-b672-c12bef9daa96 Netherlands (NL)ca62c6c8-a70f-4cc1-aaa4-dca46695e677 Germany (DE)cbc6c65f-2667-4430-9264-3c5c6ef91dd8 Denmark (DK)b8480e5f-7d16-408a-8c42-d667687e8b3c Germany (DE)d5a93a62-0ed3-46a8-bbb0-0a366c1f5015 Croatia (HR)49681ffe-e667-4540-8372-39afd4cfc136 Czech Republic (CZ)86caf239-3aec-4c05-be83-437f0192df0c Poland (PL)c2be7ce5-f3a1-4875-a255-24d9e26372b6 Netherlands (NL)c4510edb-e303-4d7c-a5e9-ec2994672c7b Netherlands (NL)08c21b77-eaa8-4840-ad41-8c49aec664ef Estonia (EE)aeaa3db2-98c3-4a85-998b-8b9815801ce8 Greece (GR)
Order Code US and Canada
XT2NE3160BFF000XXX
E-Number (Finland)
3638177
EAN
8015644009267
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.4 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.657 kg
Package Level 1 EAN
8015644009267
Circuit Breaker Type to be Associated
Power Distribution
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour8000 cycle
Mechanical Durability
240 cycles per hour25000 cycle
Number of Poles
3
Opening Time
CB with SOR 15 msCB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 16.15 W
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Rated Current (In)
160 A
Rated Frequency (f)
50 / 60 Hz
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
800…1600 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 kA(230 V AC) 65 kA(240 V AC) 65 kA(380 V AC) 36 kA(415 V AC) 36 kA(440 V AC) 36 kA(500 V AC) 30 kA(525 V AC) 20 kA(690 V AC) 10 kA(250 V DC) 2 Poles in Series 36 kA(500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 65 kA(230 V AC) 65 kA(240 V AC) 65 kA(380 V AC) 36 kA(415 V AC) 36 kA(440 V AC) 36 kA(500 V AC) 30 kA(525 V AC) 20 kA(690 V AC) 10 kA(250 V DC) 2 Poles in Series 36 kA(500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
160 A
Recommended Screw Driver
Main Circuit M6
Release
TMA
Release Type
TM
RoHS Date
NA
Setting Range
112...160 A
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Version
F
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409