1SDA067627R1

XT2H 160 TMA 160-1600 4p F F InN=100%

Trade Price

£757.65

Per

1

Unit

EA

Pack Quantity

1

1SDA067627R1
1SDA067627R1
1SDA067627R1
1SDA067627R1

Information

C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 160 I3=800...1600 A FULLY RATED NEUTRAL

Technical Specifications

ABB EcoSolutions

Yes

Circular Design Principles Recyclability Rate

Design for Closing Resource Loops - Standard EN45555 - 58.1 %

Group Waste to Landfill Target

UL 2799 Zero Waste To Landfill Validation available

RoHS Status

Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

SCIP

faa3f41f-8e61-4b91-a07b-0511a963944a Italy (IT)

Simplified SCIP

60a571f5-3995-40b3-bb49-1f11025e1807 Norway (NO)c5ed6e67-4749-4b2d-932d-f3ef7de7429e Finland (FI)dea9951f-fe91-4b90-a5ac-4c4b9aa83f4d Netherlands (NL)2fb06f6f-179e-4c09-8639-d4d63fecc4a1 Germany (DE)1ead897c-f009-4721-a055-fb14f0466a41 Denmark (DK)aab8bcc9-e7a8-41b6-9b79-8c4a80db47e7 Netherlands (NL)d31902ec-b49c-488c-8549-32b80cc76379 Netherlands (NL)adaceaea-852c-429a-8d3e-671ac095aa06 Estonia (EE)5e7686f0-862d-484f-a2bb-643aec8a2b32 Greece (GR)3f6eb64c-9ef0-43b2-b18c-bf5730a12049 Portugal (PT)570d9a49-b217-4f41-ae89-8d7cefbacc00 Germany (DE)d8cda10f-1790-4ebf-b4f3-be09afda7e3e Croatia (HR)7f4a32e3-1b4f-4d23-9f5d-d3bb9c4f57dc Czech Republic (CZ)ab6edb75-3838-4598-9763-3b0f985814a8 Poland (PL)58b1600a-81c9-49d9-ad45-879c5081e6e8 Germany (DE)f48e9ad7-4c91-4613-a6f1-d071cce66ee6 Germany (DE)bba7cff5-5854-4af1-b8a0-591df187d1c6 France (FR)de3ffc45-8d4a-4112-a65f-649200337fee Netherlands (NL)8abb20d7-4a55-4921-a3f3-5c6c59b130bb Spain (ES)31fd3c19-6def-462b-8679-a424495abf89 Netherlands (NL)4112504e-f9ca-4eb0-91fe-eeec620426ec Bulgaria (BG)f90e61fc-0e9b-4145-aeb0-bff1c6ea6a91 Sweden (SE)25c39475-3da8-418b-bdaa-b30159b9c9ae Poland (PL)95c15571-9d49-4e79-ab92-f4228c724cdd France (FR)356a6754-a76d-4f59-ac81-3ce4e44deb82 Sweden (SE)c1481159-c29c-431d-9a47-5e94a08d116c Poland (PL)

Order Code US and Canada

XT2HE4160BFF000XXX

EAN

8015644015237

Minimum Order Quantity

1 piece

Customs Tariff Number

85362090

Product Net Width

120 mm

Product Net Height

130 mm

Product Net Depth / Length

82.5 mm

Product Net Weight

1.6 kg

Package Level 1 Units

box 1 piece

Package Level 1 Width

130 mm

Package Level 1 Height

208 mm

Package Level 1 Depth / Length

145 mm

Package Level 1 Gross Weight

2.101 kg

Package Level 1 EAN

8015644015237

Circuit Breaker Type to be Associated

Power Distribution

Connecting Capacity Main Circuit

Busbar 32.5..100 mm²

Current Type

AC/DC

Electrical Durability

120 cycles per hour8000 cycle

Mechanical Durability

240 cycles per hour25000 cycle

Number of Poles

4

Opening Time

CB with SOR 15 msCB with UVR 15 ms

Order Multiple

1 piece

Power Loss

at Rated Operating Conditions per Pole 16.15 W

Product Main Type

SACE Tmax XT

Product Name

Moulded Case Circuit Breaker

Product Type

Automatic Circuit Breaker

Rated Current (In)

160 A

Rated Frequency (f)

50 / 60 Hz

Rated Voltage (Ur)

690 V

Rated Impulse Withstand Voltage (Uimp)

8 kV

Rated Instantaneous Short-Circuit Current Setting (Ii)

800…1600 A

Rated Insulation Voltage (Ui)

1000 V

Rated Operational Voltage

690 V AC500 V DC

Rated Service Short-Circuit Breaking Capacity (Ics)

(220 V AC) 100 kA(230 V AC) 100 kA(240 V AC) 100 kA(380 V AC) 70 kA(415 V AC) 70 kA(440 V AC) 65 kA(500 V AC) 50 kA(525 V AC) 30 kA(690 V AC) 15 kA(250 V DC) 2 Poles in Series 70 kA(500 V DC) 3 Poles in Series 70 kA

Rated Ultimate Short-Circuit Breaking Capacity (Icu)

(220 V AC) 100 kA(230 V AC) 100 kA(240 V AC) 100 kA(380 V AC) 70 kA(415 V AC) 70 kA(440 V AC) 65 kA(500 V AC) 50 kA(525 V AC) 30 kA(690 V AC) 15 kA(250 V DC) 2 Poles in Series 70 kA(500 V DC) 3 Poles in Series 70 kA

Rated Uninterrupted Current (Iu)

160 A

Recommended Screw Driver

Main Circuit M6

Release

TMA

Release Type

TM

Setting Range

112...160 A

Short-Circuit Performance Level

H

Standards

IEC

Sub-type

XT2

Terminal Connection Type

Front

Terminal Type

Bolt

Tightening Torque

6 N·m

Version

F

ETIM 7

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 8

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 9

EC000228 - Power circuit-breaker for trafo/generator/installation protection

Object Classification Code

Q

UNSPSC

39120000

WEEE Category

5. Small Equipment (No External Dimension More Than 50 cm)

eClass

V11.1 : 27370409

Document Links

Catalogue page

Datasheet