Trade Price
£66.52
Per
1
Unit
EA
Pack Quantity
1
6-pole, front operated, base mounted, DIN-rail mountable switch-diconnector / non-fusible diconnect switch with protected clamp terminals, handle and shaft are not included
Minimum Order Quantity:
1 piece
Customs Tariff Number:
85365080
Country of Origin:
Finland (FI)
Product Net Width:
70 mm
Product Net Height:
68 mm
Product Net Depth / Length:
68 mm
Product Net Weight:
0.21 kg
Rated Operational Current AC-21A (Ie):
(380 ... 415 V) 16 A(500 V) 16 A(690 V) 16 A
Rated Operational Current AC-22A (Ie):
(380 ... 415 V) 16 A(500 V) 16 A(690 V) 16 A
Rated Operational Current AC-23A (Ie):
(380 ... 415 V) 16 A(500 V) 16 A(690 V) 10 A
Rated Operational Power AC-23A (Pe):
(220 ... 240 V) 3 kW(400 ... 415 V) 7.5 kW(500 V) 7.5 kW(690 V) 7.5 kW
Conventional Free-air Thermal Current (Ith):
Θ = 40 °C 25 A
Conventional Thermal Current (Ithe):
Fully Enclosed 25 A
Rated Impulse Withstand Voltage (Uimp):
8 kV
Rated Insulation Voltage (Ui):
acc. to IEC/EN 60664-1 750 V
Rated Operational Voltage:
Main Circuit 750 V
Rated Short-Circuit Making Capacity (Icm):
(690 V) 0.71 kA
Rated Short-time Withstand Current Low Voltage (Icw):
for 1 s 0.5 kA
Rated Conditional Short-Circuit Current (Inc):
(40 A fuse, <=415V) 50 kA(25 A fuse, 690 V) 50 kA
Power Loss:
at Rated Operating Conditions per Pole 0.3 W
Pollution Degree:
3
Handle Type:
KnobHandle and shaft not included
Switches Operating Mechanism:
Mechanism on Top of the Switch
Distance Between Phases:
Standard
Position of Line Terminals:
Top In - Bottom OutBottom In - Top Out
Operating Mode:
Front operated
Standards:
IEC 60947-3 / UL 508 / CSA C22.2 No. 14
Special Functions:
No
Mounting Type:
Base mounting
Number of Poles:
6
Cable Cross-Section:
Cu 0.75 ... 10 mm²
Degree of Protection:
Front IP20
Terminal Type:
Screw Terminals
Tightening Torque:
acc. IEC 60947-1 0.8 N·m
Mechanical Durability:
20000
Lock Type:
No
Maximum Operating Voltage UL/CSA:
600 V
Ampere Rating:
20 A
Horsepower Rating UL/CSA:
(110 ... 120 V AC) Single Phase 1 Hp(240 V AC) Single Phase 2 Hp(440 ... 480 V AC) Single Phase 5 Hp(550 ... 600 V AC) Single Phase 7.5 Hp(220 ... 240 V AC) Three Phase 5 Hp(440 ... 480 V AC) Three Phase 10 Hp(550 ... 600 V AC) Three Phase 10 Hp
Tightening Torque UL/CSA:
7 in·lb
RoHS Status:
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Package Level 1 Units:
box 1 piece
Package Level 1 Width:
80 mm
Package Level 1 Depth / Length:
112 mm
Package Level 1 Height:
80 mm
Package Level 1 Gross Weight:
0.25 kg
Package Level 1 EAN:
6417019389783
Object Classification Code:
Q
ETIM 7:
EC000216 - Switch disconnector
ETIM 8:
EC000216 - Switch disconnector
ETIM 9:
EC000216 - Switch disconnector (low voltage)
UNSPSC:
39122233
IDEA Granular Category Code (IGCC):
5290 >> Disconnect switch
eClass:
V11.1 : 27371403
WEEE Category:
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland):
3601424