1SDA068221R1

XT3S 250 TMD 250-2500 3p F F

Trade Price

£812.37

Per

1

Unit

EA

Pack Quantity

1

1SDA068221R1
1SDA068221R1
1SDA068221R1
1SDA068221R1

Information

C.BREAKER TMAX XT3S 250 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 250-2500 A

Technical Specifications

ABB EcoSolutions

Yes

Circular Design Principles Recyclability Rate

Design for Closing Resource Loops - Standard EN45555 - 56.6 %

Group Waste to Landfill Target

UL 2799 Zero Waste To Landfill Validation available

RoHS Status

Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

SCIP

fe1eb3d5-8c63-44e3-bb9c-10a9d49206e0 Italy (IT)

Simplified SCIP

395af62d-3166-4330-85a8-57f13e3c4cd6 Czech Republic (CZ)a87e088c-bfca-4bca-bd82-2e3996b21c8d Portugal (PT)bf0b7bc2-795b-4a18-97b5-d0d8f5a7acdc Bulgaria (BG)3e4f51cf-72a5-492e-be25-a7d2dd6ff282 Sweden (SE)69f60869-d4b2-4daa-9fd5-36d197f51f10 Poland (PL)0d7c7b1b-a443-4df0-a06f-7af825c37f11 Poland (PL)a6b4a186-2c57-4b75-9f4d-9eaccfd9b7b0 Netherlands (NL)6fb29b1b-0ca7-4e33-a44c-024aabc4956d Netherlands (NL)b78f8949-00db-4428-b91c-0646514f9dcc Estonia (EE)675b8a00-d9a4-4f9a-bf6a-dc94fba0328e Greece (GR)fa62de05-56c7-44bc-a54e-9f790f893580 France (FR)f5455b37-8cfa-43a9-8b42-d5f752252d31 Sweden (SE)e06e5780-042d-4a05-8556-540e6750fb61 Germany (DE)40296efb-f1d5-4dd8-b88a-4f2a333352a8 Germany (DE)43c357e0-c904-4461-a29a-3201d177fc76 France (FR)7af40e2c-a3e3-41bb-a8d9-1bec85a0444f Netherlands (NL)a9044156-da7f-49a2-9254-b458c64e50af Spain (ES)bf63fa76-4f5c-4a04-aeda-6f6a7da8d9d9 Netherlands (NL)f3d1d321-20ae-4580-92e0-be2d07fb2753 Poland (PL)0cdbbb9a-2229-4d94-b659-4674ff269e38 Norway (NO)d0cc30b8-ea6d-49d7-9945-8ca15b360ca5 Finland (FI)553e89f6-94d8-4d6e-a8bd-a6515c266c0f Netherlands (NL)01a99f56-8375-449a-bef4-a2a245564d95 Germany (DE)f8a5a84b-dc9b-4dab-ac2b-3d255af93191 Denmark (DK)ca7d45d8-fe72-41ce-af50-92639318b638 Germany (DE)9f1b92ef-6563-4865-afb4-37f962d0b9ca Croatia (HR)

Order Code US and Canada

XT3SE3250AFF000XXX

E-Number (Finland)

3641020

E-Number (Sweden)

3182436

EAN

8015644021276

Minimum Order Quantity

1 piece

Customs Tariff Number

85362090

Product Net Width

105 mm

Product Net Height

150 mm

Product Net Depth / Length

70 mm

Product Net Weight

1.7 kg

Package Level 1 Units

box 1 piece

Package Level 1 Width

155 mm

Package Level 1 Height

190 mm

Package Level 1 Depth / Length

155 mm

Package Level 1 Gross Weight

1.71 kg

Package Level 1 EAN

8015644021276

Circuit Breaker Type to be Associated

Power Distribution

Connecting Capacity Main Circuit

Busbar 85..192 mm²

Current Type

AC/DC

Electrical Durability

120 cycles per hour8000 cycle

Mechanical Durability

240 cycles per hour25000 cycle

Number of Poles

3

Opening Time

CB with SOR 15 msCB with UVR 15 ms

Order Multiple

1 piece

Power Loss

at Rated Operating Conditions per Pole 17.8 W

Product Main Type

SACE Tmax XT

Product Name

Moulded Case Circuit Breaker

Product Type

Automatic Circuit Breaker

Rated Current (In)

250 A

Rated Frequency (f)

50 / 60 Hz

Rated Voltage (Ur)

690 V

Rated Impulse Withstand Voltage (Uimp)

8 kV

Rated Instantaneous Short-Circuit Current Setting (Ii)

2500 A

Rated Insulation Voltage (Ui)

800 V

Rated Operational Voltage

690 V AC500 V DC

Rated Service Short-Circuit Breaking Capacity (Ics)

(220 V AC) 42.5 kA(230 V AC) 42.5 kA(240 V AC) 42.5 kA(380 V AC) 27 kA(415 V AC) 27 kA(440 V AC) 20 kA(500 V AC) 15 kA(525 V AC) 10 kA(690 V AC) 3 kA(250 V DC) 2 Poles in Series 27 kA(500 V DC) 3 Poles in Series 37.5 kA

Rated Ultimate Short-Circuit Breaking Capacity (Icu)

(220 V AC) 85 kA(230 V AC) 85 kA(240 V AC) 85 kA(380 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 40 kA(500 V AC) 30 kA(525 V AC) 20 kA(690 V AC) 6 kA(250 V DC) 2 Poles in Series 36 kA(500 V DC) 3 Poles in Series 50 kA

Rated Uninterrupted Current (Iu)

250 A

Recommended Screw Driver

Main Circuit M8

Release

TMD

Release Type

TM

RoHS Date

NA

Setting Range

175...250 A

Short-Circuit Performance Level

S

Standards

IEC

Sub-type

XT3

Terminal Connection Type

Front

Terminal Type

Bolt

Tightening Torque

8 N·m

Version

F

ETIM 7

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 8

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 9

EC000228 - Power circuit-breaker for trafo/generator/installation protection

Object Classification Code

Q

UNSPSC

39120000

WEEE Category

5. Small Equipment (No External Dimension More Than 50 cm)

eClass

V11.1 : 27370409

Document Links

Catalogue page

Datasheet