1SDA066809R1

XT1B 160 TMD 160-1600 3p F F

Trade Price

£392.69

Per

1

Unit

EA

Pack Quantity

1

1SDA066809R1
1SDA066809R1
1SDA066809R1
1SDA066809R1

Information

160A 25kA MCCB - XT1B160 (Thermal Magnetic) * Front connection kits required

Technical Specifications

ABB EcoSolutions

Yes

Circular Design Principles Recyclability Rate

Design for Closing Resource Loops - Standard EN45555 - 55.9 %

Group Waste to Landfill Target

UL 2799 Zero Waste To Landfill Validation available

RoHS Status

Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

SCIP

4ff9b03b-1cf2-4837-8d24-93dc6121834d Italy (IT)

Simplified SCIP

4da9f204-50cc-48b7-b553-1da097a7c855 Finland (FI)d5ace655-c799-4282-b3ae-2598d9667b08 Netherlands (NL)a6bea1a2-aa2e-4fe2-bcab-e3f7f257dee4 Germany (DE)9675f1d6-1131-47e6-bd74-fbc792671b86 Denmark (DK)1c694b3b-5fe7-4a27-b730-11e35f757d5e Germany (DE)d7c05fd5-cc87-4458-8302-2f636925db52 Croatia (HR)ef885e92-d9b1-45c6-8cb6-c4ad6bb41325 Czech Republic (CZ)b47804c6-d053-4df3-b4c0-7c0fa2a57582 Poland (PL)204e69d2-52b6-4c7b-82d5-984ad6f0f7a8 Norway (NO)6b900579-62ee-4ae6-a47c-92aae85ceef4 Poland (PL)c5f40fc3-0ccb-4d26-9c25-78659538a6eb Germany (DE)9c041414-51e7-418a-be70-326cd293602c Germany (DE)3d472ef2-2bb2-43b6-ada4-c165d9ff695d France (FR)6ab977b3-e668-479a-b7d7-7aafb217dbf7 Netherlands (NL)83fa4ab8-1066-451f-a5c6-3227f47b9f96 Spain (ES)a788f342-f7f6-4916-be29-4fee5c9d7806 Netherlands (NL)66fc5a77-91a7-4570-9d07-534457120ddc Netherlands (NL)8bf595ce-3c04-4fb3-a7e8-898a7663ba35 Netherlands (NL)66a3997e-83ef-40cf-ba5f-5ec5ca01372c Estonia (EE)ad0a0ab9-ebde-471a-9cb3-0296bc863d67 Greece (GR)ad2768e5-aa41-4d1e-8d83-bd13e0d23b34 Portugal (PT)7b0da51d-f9cc-40f1-ac31-f8b0ab9af686 Bulgaria (BG)8c92815f-fcb1-4f59-9a66-c01580e417a2 Sweden (SE)845a2832-1626-48c6-b53d-7f7eaa93c390 Poland (PL)d1422ba9-8bd5-4eb1-a791-d8c3f4d6901f France (FR)e29f066c-15c8-4974-954d-4bc2a7fdaee4 Sweden (SE)

Order Code US and Canada

XT1BE3160AFF000XXX

E-Number (Finland)

3638199

EAN

8015644694494

Minimum Order Quantity

1 piece

Customs Tariff Number

85362090

Product Net Width

76.2 mm

Product Net Height

130 mm

Product Net Depth / Length

70 mm

Product Net Weight

1.1 kg

Package Level 1 Units

box 1 piece

Package Level 1 Width

128 mm

Package Level 1 Height

135 mm

Package Level 1 Depth / Length

143 mm

Package Level 1 Gross Weight

1.139 kg

Package Level 1 EAN

8015644694494

Circuit Breaker Type to be Associated

Power Distribution

Connecting Capacity Main Circuit

Busbar 45.5 ... 80 mm²

Current Type

AC/DC

Electrical Durability

120 cycles per hour8000 cycle

Mechanical Durability

240 cycles per hour25000 cycle

Number of Poles

3

Opening Time

CB with SOR 15 msCB with UVR 15 ms

Order Multiple

1 piece

Power Loss

at Rated Operating Conditions per Pole 15 W

Product Main Type

SACE Tmax XT

Product Name

Moulded Case Circuit Breaker

Product Type

Automatic Circuit Breaker

Rated Current (In)

160 A

Rated Frequency (f)

50 / 60 Hz

Rated Voltage (Ur)

690 V

Rated Impulse Withstand Voltage (Uimp)

8 kV

Rated Instantaneous Short-Circuit Current Setting (Ii)

1600 A

Rated Insulation Voltage (Ui)

800 V

Rated Operational Voltage

690 V AC500 V DC

Rated Service Short-Circuit Breaking Capacity (Ics)

(220 V AC) 25 kA(230 V AC) 25 kA(240 V AC) 25 kA(380 V AC) 18 kA(415 V AC) 18 kA(440 V AC) 11.25 kA(500 V AC) 8 kA(525 V AC) 6 kA(690 V AC) 3 kA(250 V DC) 2 Poles in Series 18 kA(500 V DC) 3 Poles in Series 18 kA

Rated Ultimate Short-Circuit Breaking Capacity (Icu)

(220 V AC) 25 kA(230 V AC) 25 kA(240 V AC) 25 kA(380 V AC) 18 kA(415 V AC) 18 kA(440 V AC) 15 kA(500 V AC) 8 kA(525 V AC) 6 kA(690 V AC) 3 kA(250 V DC) 2 Poles in Series 18 kA(500 V DC) 3 Poles in Series 18 kA

Rated Uninterrupted Current (Iu)

160 A

Recommended Screw Driver

Main Circuit M6

Release

TMD

Release Type

TM

RoHS Date

NA

Setting Range

112...160 A

Short-Circuit Performance Level

B

Standards

IEC

Sub-type

XT1

Terminal Connection Type

Front

Terminal Type

Bolt

Tightening Torque

6 N·m

Version

F

ETIM 7

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 8

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 9

EC000228 - Power circuit-breaker for trafo/generator/installation protection

Object Classification Code

Q

WEEE Category

5. Small Equipment (No External Dimension More Than 50 cm)

eClass

V11.1 : 27370409