1SDA066807R1

XT1B 160 TMD 100-1000 3p F F

Trade Price

£249.29

Per

1

Unit

EA

Pack Quantity

1

1SDA066807R1
1SDA066807R1
1SDA066807R1
1SDA066807R1

Information

100A 25kA MCCB - XT1B160 (Thermal Magnetic) * Front connection kits required

Technical Specifications

ABB EcoSolutions

Yes

Circular Design Principles Recyclability Rate

Design for Closing Resource Loops - Standard EN45555 - 55.9 %

Group Waste to Landfill Target

UL 2799 Zero Waste To Landfill Validation available

RoHS Status

Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

SCIP

87da4ae5-d281-4cf7-89ae-08ea1f34c520 Italy (IT)

Simplified SCIP

9136ee1a-0225-4485-8008-9b9b4f898003 France (FR)baa691e3-fb96-4aa9-9079-885f0ce9ffc7 Netherlands (NL)19009d20-fe0a-406e-a6c7-754e2ce79a04 Spain (ES)0d017bbc-bd89-4cba-9c40-ce382b69c941 Netherlands (NL)1ac23e01-8938-4cfa-9554-5dc725569cd9 Estonia (EE)3caf7a98-6d33-4e3d-9e3c-3696071c018c Greece (GR)b4a8fa85-471c-4024-9dfa-2b3b8002b1fd Portugal (PT)40ae467e-12cd-4ff4-9b7b-0b06c10682c8 Bulgaria (BG)34e0ba7e-9ada-4036-a46c-78818d351a10 Sweden (SE)7688f27b-0303-4931-a1b9-201ec758eed9 Poland (PL)2973e92d-a825-4905-b178-8271043cd3fc Netherlands (NL)88dd4d2a-48ef-40e5-a5a4-8777e0caf1ae Poland (PL)28af0011-3352-4568-ae2e-5c6f712f69ce Norway (NO)139a4e60-c144-4385-9f47-109d95a5e80f Finland (FI)fdaa062c-f086-4a1a-84ad-e07827068768 Netherlands (NL)b45b713c-aac6-486d-860d-62c7bd566c76 Germany (DE)7cd9e27b-8379-4d1d-9c10-2494ae68a5e5 Denmark (DK)b5672789-5124-44cd-b9aa-10e3f35aba7a Germany (DE)4b159a82-b08b-4bd6-9325-11ce5cdf5448 Croatia (HR)dde32885-1587-472c-b2dd-1326e5aad4e2 Czech Republic (CZ)f4f530b5-c734-46f4-9e51-1699fa3f6f95 Poland (PL)7684609b-1286-40fa-be35-8e161c571a09 Netherlands (NL)53567a62-c858-4312-a586-9c3dff2aeb2a France (FR)97a62aeb-f463-485d-802c-da5b271e1915 Sweden (SE)706a0ec2-b9e6-48d8-a2e7-e213302d4bc2 Germany (DE)6f865dc7-914e-4ee1-bd3b-f9f2de603622 Germany (DE)

Order Code US and Canada

XT1BE3100AFF000XXX

E-Number (Finland)

3640495

EAN

8015644694487

Minimum Order Quantity

1 piece

Customs Tariff Number

85362090

Product Net Width

76.2 mm

Product Net Height

130 mm

Product Net Depth / Length

70 mm

Product Net Weight

1.1 kg

Package Level 1 Units

box 1 piece

Package Level 1 Width

128 mm

Package Level 1 Height

135 mm

Package Level 1 Depth / Length

143 mm

Package Level 1 Gross Weight

1.134 kg

Package Level 1 EAN

8015644694487

Circuit Breaker Type to be Associated

Power Distribution

Connecting Capacity Main Circuit

Busbar 45.5 ... 80 mm²

Current Type

AC/DC

Electrical Durability

120 cycles per hour8000 cycle

Mechanical Durability

240 cycles per hour25000 cycle

Number of Poles

3

Opening Time

CB with SOR 15 msCB with UVR 15 ms

Order Multiple

1 piece

Power Loss

at Rated Operating Conditions per Pole 7 W

Product Main Type

SACE Tmax XT

Product Name

Moulded Case Circuit Breaker

Product Type

Automatic Circuit Breaker

Rated Current (In)

100 A

Rated Frequency (f)

50 / 60 Hz

Rated Voltage (Ur)

690 V

Rated Impulse Withstand Voltage (Uimp)

8 kV

Rated Instantaneous Short-Circuit Current Setting (Ii)

1000 A

Rated Insulation Voltage (Ui)

800 V

Rated Operational Voltage

690 V AC500 V DC

Rated Service Short-Circuit Breaking Capacity (Ics)

(220 V AC) 25 kA(230 V AC) 25 kA(240 V AC) 25 kA(380 V AC) 18 kA(415 V AC) 18 kA(440 V AC) 11.25 kA(500 V AC) 8 kA(525 V AC) 6 kA(690 V AC) 3 kA(250 V DC) 2 Poles in Series 18 kA(500 V DC) 3 Poles in Series 18 kA

Rated Ultimate Short-Circuit Breaking Capacity (Icu)

(220 V AC) 25 kA(230 V AC) 25 kA(240 V AC) 25 kA(380 V AC) 18 kA(415 V AC) 18 kA(440 V AC) 15 kA(500 V AC) 8 kA(525 V AC) 6 kA(690 V AC) 3 kA(250 V DC) 2 Poles in Series 18 kA(500 V DC) 3 Poles in Series 18 kA

Rated Uninterrupted Current (Iu)

160 A

Recommended Screw Driver

Main Circuit M6

Release

TMD

Release Type

TM

RoHS Date

NA

Setting Range

70...100 A

Short-Circuit Performance Level

B

Standards

IEC

Sub-type

XT1

Terminal Connection Type

Front

Terminal Type

Bolt

Tightening Torque

6 N·m

Version

F

ETIM 7

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 8

EC000228 - Power circuit-breaker for trafo/generator/installation protection

ETIM 9

EC000228 - Power circuit-breaker for trafo/generator/installation protection

Object Classification Code

Q

WEEE Category

5. Small Equipment (No External Dimension More Than 50 cm)

eClass

V11.1 : 27370409

Document Links

Catalogue page

Datasheet