Trade Price
£4,434.96
Per
1
Unit
EA
Pack Quantity
1
C.BREAKER SACE EMAX2 E1.2B 630 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP/DIP-LSIG R 630 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 76.4 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
5db9272f-d385-4a4a-a0e6-73274e7613b2 Italy (IT)
Simplified SCIP
8b03cfe9-7657-4778-acb1-5e456af5c76a Denmark (DK)64831dac-5718-413a-b2dd-c2a16236b94f Sweden (SE)7635dc57-155c-4b3b-8d16-637f7a9317ca Estonia (EE)bf55e5c1-47fb-4603-bc85-150f2bba6810 Netherlands (NL)8d8d3917-aca7-4875-98c5-244d35793f56 Bulgaria (BG)cc5cb3c7-f20f-4e57-a699-41c96b5a1eef Norway (NO)560d9c18-bf6e-4a6e-b95a-82f0dcbd0d2c Sweden (SE)55ebef71-4502-4891-8767-e9a15ef09392 Poland (PL)7e9377e0-b60f-471e-982f-360fb85b51c6 France (FR)5b96a5ce-08d7-4ea3-9d9d-b2ed25c73f5d Netherlands (NL)7f3be359-1216-4d35-b9d4-eab9cbb290fd Poland (PL)13fc1439-00ad-45bf-abdd-5ede1ce20a7d Netherlands (NL)de9a0119-6bd3-4d97-a5d3-1e74d280ccf7 Netherlands (NL)08ff7a7d-f7c4-4a97-ab1f-2f60e52ccc4e Germany (DE)18044daa-d0c0-4608-bafb-451bb9d8efe4 Croatia (HR)de6447a0-df24-4a20-8466-f5f11a930a19 Finland (FI)5ede7a36-3b83-4497-b7e0-ef217691ad89 Czech Republic (CZ)f49fce99-7561-4c32-880a-478431f7efd7 Greece (GR)e5eed5bf-546a-4db4-a608-d4b83c43c056 Poland (PL)f40ef067-0a7a-4928-831d-6affa0d2f0c7 Germany (DE)8ad28a13-de77-4592-95fd-897a501569c8 Germany (DE)05702ea0-ab49-475f-8469-3cf48dabeb77 Portugal (PT)1ac41cb5-8851-4d50-97e5-9a58e2df1d99 Spain (ES)6e3f01fd-be03-4be8-9d80-b02a9984a4e1 Germany (DE)1c74a6dc-b960-484a-a4e4-4114d79c6a3d Netherlands (NL)a940f727-3880-42c1-bdc0-d5e1d498ddaf France (FR)
Order Code US and Canada
Z1BNEEBC000A000000XX
EAN
8015644745530
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
296 mm
Product Net Depth / Length
183 mm
Product Net Weight
14 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
270 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
330 mm
Package Level 1 Gross Weight
16 kg
Package Level 1 EAN
8015644745530
Current Type
AC
Electrical Durability
Ue =< 440 V 8000 cycleUe = 500 ... 690 V 8000 cycle30 cycles per hour
Mechanical Durability
20000 cycle60 cycles per hour
Number of Poles
3
Power Loss
31 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
630 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 42 kA(230 V AC) 42 kA(380 V AC) 42 kA(400 V AC) 42 kA(415 V AC) 42 kA(440 V AC) 42 kA(500 V AC) 42 kA(660 V AC) 42 kA(690 V AC) 42 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 42 kAfor 3 s 24 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 42 kA(415 V AC) 42 kA(440 V AC) 42 kA(500 V AC) 42 kA(525 V AC) 42 kA(690 V AC) 42 kA
Rated Uninterrupted Current (Iu)
630 A
Recommended Screw Driver
Main Circuit M10
Release
Ekip Dip LSIG
Release Type
EL
Short-Circuit Performance Level
B
Standards
IEC
Sub-type
E1.2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
45 N·m
Version
F
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
UNSPSC
39121615
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet