Trade Price
£2,247.56
Per
1
Unit
EA
Pack Quantity
1
Range
MasterPacT
Device short name
MicroLogic 7.0 X
Product or component type
Control unit
Device application
Equipment protection, monitoring and control
circuit breaker application
Distribution IEC standard
Range compatibility
MasterPact MTZ1 circuit breaker MasterPact MTZ2 circuit breaker
Poles
4P 3P
Protected poles description
3P 3d 4P 3d 4P 3d + N/2 4P 4d 4P 3d + OSN
[Ue] rated operational voltage
600 V AC, +/- 10 %
Network type
AC
Network frequency
50/60 Hz
Trip unit technology
Electronic
Trip unit protection functions
LSIV
Protection type
Overload protection (long time) conforming to ANSI 49 Instantaneous short-circuit protection conforming to ANSI 50 Short time short-circuit protection conforming to ANSI 51 Earth-leakage protection conforming to ANSI 51G
Trip unit rating
400 A 630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A
Mounting mode
Fixed
Neutral protection setting
1 x Ir (4P 4d) 0.5 x Ir (4P 3d + N/2) 1.6 x Ir (4P 3d + OSN) No protection (4P 3d)
[Ir] long time pick-up adjustment range
0.4...1 x In adjustable in step of 1 A
Long time delay adjustment type
Adjustable in step of 0.5 s
[tr] long-time delay adjustment range
12.5…600 s at 1.5 x Ir 0.5…24 s at 6 x Ir 0.7…16.6 s at 7.2 x Ir
Thermal memory
Yes
[Isd] short-time pick-up adjustment range
1.5...10 x Ir adjustable in step of 0.5 x Ir with embedded HMI 1.5...10 x Ir adjustable in step of 0.1 x Ir with Ecoreach software or MasterPact MTZ mobile app
Short-time delay adjustment type
Adjustable
[tsd] short-time delay adjustment range
0.1…0.4 s I²t=on 0…0.4 s I²t=off
instantaneous pick-up adjustment type Ii
Adjustable
[Ii] instantaneous pick-up adjustment range
2...15 x In adjustable in step of 0.5 x In with embedded HMI 2...15 x In adjustable in step of 0.1 x In with Ecoreach software or MasterPact MTZ mobile app Ii enable on/off
[li mode] instantaneous delay adjustment range
0 ms in fast 20 ms in standard
earth-leakage protection
With
[IΔn] residual earth-leakage sensitive adjustment
0.5…30 A adjustable in step of 0.1 A
Residual earth-leakage time delay adjustment type
Adjustable
[Δt] residual earth-leakage time delay adjustment
60…800 ms resettable time 140…1000 ms break time
Zone selective interlocking ZSI
With
Network and machine diagnosis type
System (HMI) health state overview: circuit breaker health state Contacts state: circuit breaker health state MicroLogic service life: circuit breaker health state Tripping cause indication: circuit breaker tripping cause Identification card: diagnostic data Configured alarms synthesis: diagnostic data Monitored function: diagnostic data Operation: diagnostic data MicroLogic test: test Protection test: test Selectivity test: test Trip context information: crisis management Operation: advanced diagnostic Breaker service life: circuit breaker health state
Type of measurement
Power meter
Energy management
Measurement ,active, reactive and apparent energy Measurement ,electrical network Measurement ,energy
Metering type
Current I1, I2, I3, Iavg RMS Neutral current IN RMS Ground fault current Ig RMS Voltage V12, V23, V31, VLLavg RMS Voltage V1N, V2N, V3N, VLNavg RMS Active power P, P1, P2, P3 total Reactive power Q, Q1, Q2, Q3 total Apparent power S, S1, S2, S3 total Power factor Active energy Ep IN/OUT/tot Reactive energy Eq IN/OUT/tot Apparent energy Es IN/OUT/tot Demand current I1, I2, I3, In, Iavg Demand power P, Q, S Frequency Phase sequence Earth leakage current Total current harmonic distortion THD (I) Total voltage harmonic distortion THD (V) Unbalance current Unbalance voltage
Measurement voltage
208…828 V AC 50/60 Hz phase to phase 120…480 V AC 50/60 Hz phase to neutral
Frequency measurement range
40…70 Hz
Measurement accuracy
Current I1, I2, I3, Iavg, Idemand for MTZ1: +/- 0.5 % 40...1600 x 1.2 A Current I1, I2, I3, Iavg, Idemand for MTZ2: +/- 0.5 % 40...4000 x 1.2 A Current I1, I2, I3, Iavg, Idemand for MTZ3: +/- 0.5 % 80...6300 x 1.2 A Neutral current IN: +/- 1 % Ground fault current Ig: +/- 5 % Voltage V12, V23, V31, VLLavg: +/- 0.5 % 208...690 x 1.2 V Voltage V1N, V2N, V3N, VLNavg: +/- 0.5 % 120...400 x 1.2 V Active power P, P1, P2, P3, Pdemand: +/- 1 % Reactive power Q, Q1, Q2, Q3, Qdemand: +/- 2 % Apparent power S, S1, S2, S3, Sdemand: +/- 1 % Power factor: +/- 2 % Active energy Ep IN/OUT/tot: +/- 1 % Reactive energy Ep IN/OUT/tot: +/- 2 % Apparent energy Es IN/OUT/tot: +/- 1 % Frequency: +/- 0.005 Hz Earth leakage current: +/- 10 % Unbalance current: +/- 0.5 %
Accuracy class
Class 5: total current harmonic distortion THD (I) Class 0.5: unbalance voltage Class 1: active and reactive energy by pulse counting (+/- W.h, +/- VAR.h) Class 2: total voltage harmonic distortion THD (V)
Display type
LCD display - 128 x 96 pixels
Communication port protocol
Bluetooth 4.0 LE peer to peer 30 kbit/s NFC peer to peer 28800 bauds conforming to ISO 15963 USB peer to peer 115 kbauds
data recording
Event logs Min/max of instantaneous values Data logs Alarm logs Time stamping Maintenance logs
standards
EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60092-202 EN/IEC 60255-1 EN/IEC 61010-1
Mounting location
Indoor use only
Environmental characteristic
Wet location not approved for use conforming to IEC 61010-1
Electromagnetic compatibility
Electrostatic discharge immunity test conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5 Conducted RF disturbances conforming to IEC 61000-4-6 Conducted and radiated emissions A conforming to CISPR 22
Overvoltage category
IV conforming to IEC 61010-1
Measurement category
Category IV conforming to IEC 61010-2-30
Pollution degree
3 conforming to IEC 60947-1
Ambient air temperature for operation
-25…70 °C (operating) -35 °C (for start-up of product)
Relative humidity
95 % at 55 °C conforming to IEC 60068-2-30
Operating altitude
<= 2000 m without derating <= 4000 m with operational voltage derating 600 V AC <= 5000 m with operational voltage derating 560 V AC
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
8.0 cm
Package 1 Width
22.0 cm
Package 1 Length
7.0 cm
Package 1 Weight
407.0 g
Warranty
18 months