Trade Price
£2,137.48
Per
1
Unit
EA
Pack Quantity
1
Range
MasterPacT
Product name
MasterPact MTZ1
Device short name
MTZ1 08 H1
Product or component type
Circuit breaker
Device application
Power distribution protection
Poles description
3P
Control unit
Without control unit
Product compatibility
control unit MicroLogic 2.0 X control unit MicroLogic 5.0 X control unit MicroLogic 6.0 X control unit MicroLogic 7.0 X control unit MicroLogic 2.0 Xi control unit MicroLogic 5.0 Xi control unit MicroLogic 6.0 Xi control unit MicroLogic 7.0 Xi
[In] rated current
800 A at 40 °C
Performance type
H1 42 kA 415 V AC
[Ue] rated operational voltage
690 V AC 50/60 Hz
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Selectivity category
Category B
Control type
Push-button
Mounting mode
Drawout
[Icu] rated ultimate short-circuit breaking capacity
42 kA at 220/415 V AC 50/60 Hz 42 kA at 440 V AC 50/60 Hz 42 kA at 500/525 V AC 50/60 Hz 42 kA at 660/690 V AC 50/60 Hz
[Ics] rated service breaking capacity
42 kA at 220/415 V AC 50/60 Hz 42 kA at 440 V AC 50/60 Hz 42 kA at 500/525 V AC 50/60 Hz 42 kA at 660/690 V AC 50/60 Hz
[Icw] rated short-time withstand current
42 kA 0.5 s 42 kA 1 s 24 kA 3 s
[Icm] rated short-circuit making capacity
88 kA 220/415 V AC at 50/60 Hz 88 kA 440 V AC at 50/60 Hz 88 kA 500/525 V AC at 50/60 Hz 88 kA 660/690 V AC at 50/60 Hz
Sensor rating
400 A 630 A 800 A
[Ui] rated insulation voltage
1000 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
12 kV
Power dissipation in W
90 W
Maximum breaking time
25 ms
maximum closing response time
50 ms
mounting support
Rails Base plate
Upside connection
Front Rear
downside connection
Front Rear
Connection pitch
70 mm
Mechanical durability
12500 cycles with periodic preventive maintenance
Electrical durability
3000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 3000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3
Height
Drawout circuit breaker with chassis: 322 mm Drawout circuit breaker without chassis: 259.5 mm
Width
Drawout circuit breaker with chassis: 288 mm Drawout circuit breaker without chassis: 236.5 mm
Depth
Drawout circuit breaker with chassis: 291 mm Drawout circuit breaker without chassis: 207.5 mm
Net weight
30 kg
standards
EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12
product certifications
CE IECEE CB Scheme
IP degree of protection
IP30 conforming to EN 60529
Pollution degree
3 conforming to IEC 60947-1
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…85 °C
Operating altitude
0...2000 m without derating 2000...5000 m with derating
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
25.0 cm
Package 1 Width
40.0 cm
Package 1 Length
40.0 cm
Package 1 Weight
23.068 kg
Warranty
18 months
Datasheet