LV847202

MTZ1 L1 630A 3P D/O w/o MLogic

Trade Price

£3,303.74

Per

1

Unit

EA

Pack Quantity

1

LV847202

Technical Specifications

Range

MasterPacT

Product name

MasterPact MTZ1

Device short name

MTZ1 06 L1

Product or component type

Circuit breaker

Device application

Power distribution protection

Poles description

3P

Control unit

Without control unit

Product compatibility

control unit MicroLogic 2.0 X control unit MicroLogic 5.0 X control unit MicroLogic 6.0 X control unit MicroLogic 7.0 X control unit MicroLogic 2.0 Xi control unit MicroLogic 5.0 Xi control unit MicroLogic 6.0 Xi control unit MicroLogic 7.0 Xi

[In] rated current

630 A at 40 °C

Performance type

L1 150 kA 415 V AC

[Ue] rated operational voltage

690 V AC 50/60 Hz

Suitability for isolation

Yes conforming to EN/IEC 60947-2

Selectivity category

Category A

Control type

Push-button

Mounting mode

Drawout

[Icu] rated ultimate short-circuit breaking capacity

150 kA at 220/415 V AC 50/60 Hz 130 kA at 440 V AC 50/60 Hz 100 kA at 500/525 V AC 50/60 Hz

[Ics] rated service breaking capacity

150 kA at 220/415 V AC 50/60 Hz 130 kA at 440 V AC 50/60 Hz 100 kA at 500/525 V AC 50/60 Hz

[Icw] rated short-time withstand current

10 kA 0.5 s

[Icm] rated short-circuit making capacity

330 kA 220/415 V AC at 50/60 Hz 286 kA 440 V AC at 50/60 Hz 220 kA 500/525 V AC at 50/60 Hz 52 kA 660/690 V AC at 50/60 Hz

Integrated instantaneous protection (DIN in kA peak)

5.67…6.93 kA

Sensor rating

400 A 630 A

[Ui] rated insulation voltage

1000 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage

12 kV

Power dissipation in W

115 W

Maximum breaking time

9 ms

maximum closing response time

50 ms

mounting support

Rails Base plate

Upside connection

Front Rear

downside connection

Front Rear

Connection pitch

70 mm

Mechanical durability

12500 cycles with periodic preventive maintenance

Electrical durability

AC-23A: 3000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 2000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 3000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2

Height

Drawout circuit breaker with chassis: 322 mm Drawout circuit breaker without chassis: 259.5 mm

Width

Drawout circuit breaker with chassis: 288 mm Drawout circuit breaker without chassis: 236.5 mm

Depth

Drawout circuit breaker with chassis: 291 mm Drawout circuit breaker without chassis: 207.5 mm

Net weight

30 kg

standards

EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12

product certifications

CE IECEE CB Scheme

IP degree of protection

IP30 conforming to EN 60529

Pollution degree

3 conforming to IEC 60947-1

Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-40…85 °C

Operating altitude

0...2000 m without derating 2000...5000 m with derating

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

36.0 cm

Package 1 Width

40.0 cm

Package 1 Length

23.0 cm

Package 1 Weight

16.224 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet