NLGF36400U31XTW

400A TP 35kA Powerpact MCCB - L-Frame -

Trade Price

£1,962.30

Per

1

Unit

EA

Pack Quantity

1

NLGF36400U31XTW

Technical Specifications

Range of product

PowerPact multistandard

Range

PowerPact

Product name

L-Frame

Device short name

L-Frame

Product or component type

Circuit breaker

Device application

Distribution

Poles description

3P

Control type

Toggle

Mounting mode

Unit mount

mounting support

Flush DIN rail Backplate

Electrical connection

Terminal nut, line side Terminal nut, load side

[In] rated current

400 A at 40 °C

[Ui] rated insulation voltage

750 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage

8 kV conforming to IEC 60947-2

[Ue] rated operational voltage

525 V AC 50/60 Hz conforming to IEC 60947-2 690 V AC 50/60 Hz conforming to IEC 947-2 600 V AC 50/60 Hz conforming to UL 489

Breaking capacity code

LG

Suitability for isolation

Yes

utilisation category

Category A

Mechanical durability

5000 cycles

Electrical durability

1000 cycles

Connection pitch

45 mm

Local signalling

ON/OFF indication

Contact position indicator

Yes

Trip unit name

MicroLogic 3.0

Trip unit technology

Electronic

Trip unit protection functions

LI

Trip unit rating

400 A

Thermal memory

20 mn

Display type

3 LEDs

Breaking capacity

Icu: 65 kA at 220/240 V - AC conforming to IEC 947-2 Icu: 35 kA at 380/415 V - AC conforming to IEC 947-2 Icu: 35 kA at 440/480 V - AC conforming to IEC 947-2 Icu: 18 kA at 500/525 V - AC conforming to IEC 947-2 65 kA at 240 V - AC conforming to UL 489 35 kA at 480 V - AC conforming to UL 489 18 kA at 600 V - AC conforming to UL 489

[Ics] rated service breaking capacity

Ics: 65 kA at 220/240 V - AC conforming to IEC 947-2 Ics: 35 kA at 380/415 V - AC conforming to IEC 947-2 Ics: 35 kA at 440/480 V - AC conforming to IEC 947-2 Ics: 18 kA at 500/525 V - AC conforming to IEC 947-2

Long time pick-up adjustment type Ir

Adjustable 9 settings

long time pick-up adjustment range

0.31...1 x In

[tr] long-time delay adjustment range

2 s 4 s 0.5 s 16 s 8 s 1 s

instantaneous pick-up adjustment type Ii

Adjustable 9 settings

instantaneous pick-up adjustment range

1.5...15 x In

Overvoltage category

II

Provision for padlocking

Non padlockable

height

340 mm

Width

140 mm

Depth

110 mm

standards

NMX J-266 NEMA AB1 IEC 60947-2 UL 489 W-C-375B/GEN CSA C22.2 No 5

product certifications

CCC CE

Net weight

6 kg

IP degree of protection

IP40 conforming to IEC 60529

IK degree of protection

IK07 conforming to IEC 62262

Pollution degree

3 conforming to IEC 60947-1 3 conforming to IEC 60664-1

Ambient air temperature for operation

40 °C

Ambient air temperature for storage

-50…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

25.6 cm

Package 1 Width

28.0 cm

Package 1 Length

51.1 cm

Package 1 Weight

6.664 kg

Unit Type of Package 2

P12

Number of Units in Package 2

6

Package 2 Height

37.0 cm

Package 2 Width

80.0 cm

Package 2 Length

120.0 cm

Package 2 Weight

51.984 kg

Warranty

18 months

Document Links

Datasheet