NHDF36125TW

125A TP 18kA Powerpact MCCB - H-Frame -

Trade Price

£587.38

Per

1

Unit

EA

Pack Quantity

1

NHDF36125TW

Technical Specifications

Range of product

PowerPact multistandard

Range

PowerPact

Product name

H-Frame

Device short name

H-Frame

Product or component type

Circuit breaker

Device application

Distribution

Poles description

3P

Control type

Toggle

Mounting mode

Unit mount

mounting support

DIN rail Flush Backplate

Electrical connection

Terminal nut line side Terminal nut load side

[In] rated current

125 A at 40 °C

[Ui] rated insulation voltage

750 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage

8 kV conforming to IEC 60947-2

[Ue] rated operational voltage

525 V AC 50/60 Hz conforming to IEC 60947-2 690 V AC 50/60 Hz conforming to IEC 947-2 600 V AC 50/60 Hz conforming to UL 489

Breaking capacity code

HD

Suitability for isolation

Yes

utilisation category

Category A

Mechanical durability

4000 cycles

Electrical durability

4000 cycles

Connection pitch

45 mm

Local signalling

ON/OFF indication

Contact position indicator

Yes

Trip unit name

TM

Trip unit technology

Thermal-magnetic

Trip unit protection functions

Basic protection

Trip unit rating

125 A

Display type

3 LEDs

Breaking capacity

Icu: 25 kA at 220/240 V - AC conforming to IEC 947-2 Icu: 18 kA at 380/415 V - AC conforming to IEC 947-2 Icu: 18 kA at 440/480 V - AC conforming to IEC 947-2 Icu: 14 kA at 500/525 V - AC conforming to IEC 947-2 25 kA at 240 V - AC conforming to UL 489 18 kA at 480 V - AC conforming to UL 489 14 kA at 600 V - AC conforming to UL 489

[Ics] rated service breaking capacity

Ics: 25 kA at 220/240 V - AC conforming to IEC 947-2 Ics: 18 kA at 380/415 V - AC conforming to IEC 947-2 Ics: 18 kA at 440/480 V - AC conforming to IEC 947-2 Ics: 14 kA at 500/525 V - AC conforming to IEC 947-2

Long time pick-up adjustment type Ir

Fixed

long time pick-up adjustment range

1 In

Short-time pick-up adjustment type Isd

Fixed

[Isd] short-time pick-up adjustment range

1700 A

Overvoltage category

II

Provision for padlocking

Non padlockable

height

163 mm

Width

104 mm

Depth

86 mm

standards

NMX J-266 NEMA AB1 CSA C22.2 No 5 W-C-375B/GEN UL 489 IEC 60947-2

product certifications

CE CCC

Net weight

2.2 kg

IP degree of protection

IP40 conforming to IEC 60529

IK degree of protection

IK07 conforming to IEC 62262

Pollution degree

3 conforming to IEC 60947-1 3 conforming to IEC 60664-1

Ambient air temperature for operation

40 °C

Ambient air temperature for storage

-50…85 °C

Warranty

18 months