Trade Price
£62.91
Per
1
Unit
EA
Pack Quantity
1
The MS116-0.63 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 0.63 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 50 kA at 400 VAC and trip class 10A. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single-phase applications. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks and locking devices for protection against unauthorized changes are available as accessory.
Minimum Order Quantity:
1 piece
Customs Tariff Number:
85362010
Product Net Width:
45 mm
Product Net Height:
90 mm
Product Net Depth / Length:
85.6 mm
Product Net Weight:
0.225 kg
Rated Service Short-Circuit Breaking Capacity (Ics):
(230 V AC) 50 kA(400 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 30 kA(690 V AC) 30 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(230 V AC) 100 kA(400 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 100 kA(690 V AC) 100 kA
Rated Instantaneous Short-Circuit Current Setting (Ii):
7.9 A
Setting Range:
0.40 ... 0.63 A
Rated Operational Power AC-3 (Pe):
(400 V) Three Phase 0.18 kW
Rated Operational Power AC-3e (Pe):
(400 V) Three Phase 0.18 kW
Rated Operational Voltage:
Main Circuit 690 V AC
Rated Operational Current (Ie):
0.63 A
Rated Operational Current AC-3 (Ie):
0.63 A
Rated Operational Current AC-3e (Ie):
0.63 A
Rated Frequency (f):
Main Circuit 50 HzMain Circuit 60 Hz
Rated Impulse Withstand Voltage (Uimp):
Main Circuit 6 kV
Rated Insulation Voltage (Ui):
690 V
Power Loss:
at Rated Operating Conditions per Pole 0.7 ... 1.7 W
Number of Poles:
3
Conventional Free-air Thermal Current (Ith):
Main Circuit 0.63 A
Degree of Protection:
Housing IP20Main Circuit Terminals IP10
Pollution Degree:
3
Electrical Durability:
100000 cycle
Mechanical Durability:
100000 cycle
Terminal Type:
Screw Terminals
Connecting Capacity Main Circuit:
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²Flexible 1/2x 0.75 ... 2.5 mm²Rigid 1/2x 1 ... 4 mm²
Tightening Torque:
Main Circuit 0.8 ... 1.2 N·m
Wire Stripping Length:
Main Circuit 9 mm
Recommended Screw Driver:
Pozidriv 2
Mounting Position:
any1 ... 6
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting Distance:
Electrical Conductive Board, Horizontal - Up to 400 V 0 mmElectrical Conductive Board, Horizontal - Up to 690 V 1.5 mmElectrical Conductive Board, Vertical 75 mmOther Device Same Type, Horizontal 0 mmOther Device Same Type, Vertical 150 mm
Actuator Type:
Rotary Handle
Contact Position Indication:
ON / OFF
Standards:
IEC/EN 60947-1IEC/EN 60947-2IEC/EN 60947-4-1UL 60947-1UL 60947-4-1
Short-Circuit Current Rating (SCCR):
Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 5 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 5 kA
Maximum Operating Voltage UL/CSA:
Main Circuit 600 V AC
Full Load Amps Motor Use:
(110 ... 120 V AC) Three Phase 0.63 A(200 V AC) Three Phase 0.63 A(208 V AC) Three Phase 0.63 A(220 ... 240 V AC) Three Phase 0.63 A(440 ... 480 V AC) Three Phase 0.63 A(550 ... 600 V AC) Three Phase 0.63 A
Locked Rotor Amps:
(110 ... 120 V AC) Three Phase 3.78 A(200 V AC) Three Phase 3.78 A(208 V AC) Three Phase 3.78 A(220 ... 240 V AC) Three Phase 3.78 A(440 ... 480 V AC) Three Phase 3.78 A(550 ... 600 V AC) Three Phase 3.78 A
General Use Rating UL/CSA:
(600 V AC) 0.63 A
Connecting Capacity Main Circuit UL/CSA:
Flexible 1/2x 16-12 AWGStranded 1/2x 16-12 AWG
Tightening Torque UL/CSA:
Main Circuit 10 in·lb
Ambient Air Temperature:
Around the Enclosure 0 ... +40 °COperation -25 ... +70 °COperation Compensated -25 ... +55 °CStorage -50 ... +80 °C
Ambient Air Temperature Compensation:
Yes
Maximum Operating Altitude Permissible:
2000 m
Resistance to Shock acc. to IEC 60068-2-27:
11 ms Pulse 25g
Resistance to Vibrations:
5g 3 … 150 Hz
RoHS Status:
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Package Level 1 Units:
box 1 piece
Package Level 1 Width:
92 mm
Package Level 1 Depth / Length:
95 mm
Package Level 1 Height:
50 mm
Package Level 1 Gross Weight:
0.24 kg
Package Level 1 EAN:
4013614320279
Package Level 2 Units:
carton 40 piece
Package Level 2 Width:
280 mm
Package Level 2 Depth / Length:
395 mm
Package Level 2 Height:
210 mm
Package Level 2 Gross Weight:
9.986 kg
Package Level 2 EAN:
4013614408649
Object Classification Code:
F
ETIM 4:
EC000074 - Motor protective circuit-breaker
ETIM 5:
EC000074 - Motor protective circuit-breaker
ETIM 6:
EC000074 - Motor protection circuit-breaker
ETIM 7:
EC000074 - Motor protection circuit-breaker
ETIM 8:
EC000074 - Motor protection circuit-breaker
eClass:
V11.0 : 27370401
UNSPSC:
39121521
IDEA Granular Category Code (IGCC):
4731 >> Manual Starters
E-Number (Finland):
3706004
E-Number (Sweden):
3111936