1SAM250000R1002

MS116-0.25 Man Motor Starter(0.16-0.25A) (MS116-0.25)

Trade Price

£62.50

Per

1

Unit

EA

Pack Quantity

1

1SAM250000R1002

Information

The MS116-0.25 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 0.25 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 50 kA at 400 VAC and trip class 10A. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single-phase applications. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks and locking devices for protection against unauthorized changes are available as accessory.

Technical Specifications

Minimum Order Quantity:

1 piece

Customs Tariff Number:

85362010

Product Net Width:

45 mm

Product Net Height:

90 mm

Product Net Depth / Length:

85.6 mm

Product Net Weight:

0.225 kg

Rated Service Short-Circuit Breaking Capacity (Ics):

(230 V AC) 50 kA(400 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 30 kA(690 V AC) 30 kA

Rated Ultimate Short-Circuit Breaking Capacity (Icu):

(230 V AC) 100 kA(400 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 100 kA(690 V AC) 100 kA

Rated Instantaneous Short-Circuit Current Setting (Ii):

3.1 A

Setting Range:

0.16 ... 0.25 A

Rated Operational Power AC-3 (Pe):

(400 V) Three Phase 0.06 kW

Rated Operational Power AC-3e (Pe):

(400 V) Three Phase 0.06 kW

Rated Operational Voltage:

Main Circuit 690 V AC

Rated Operational Current (Ie):

0.25 A

Rated Operational Current AC-3 (Ie):

0.25 A

Rated Operational Current AC-3e (Ie):

0.25 A

Rated Frequency (f):

Main Circuit 50 HzMain Circuit 60 Hz

Rated Impulse Withstand Voltage (Uimp):

Main Circuit 6 kV

Rated Insulation Voltage (Ui):

690 V

Power Loss:

at Rated Operating Conditions per Pole 0.7 ... 1.6 W

Number of Poles:

3

Conventional Free-air Thermal Current (Ith):

Main Circuit 0.25 A

Degree of Protection:

Housing IP20Main Circuit Terminals IP10

Pollution Degree:

3

Electrical Durability:

100000 cycle

Mechanical Durability:

100000 cycle

Terminal Type:

Screw Terminals

Connecting Capacity Main Circuit:

Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²Flexible 1/2x 0.75 ... 2.5 mm²Rigid 1/2x 1 ... 4 mm²

Tightening Torque:

Main Circuit 0.8 ... 1.2 N·m

Wire Stripping Length:

Main Circuit 9 mm

Recommended Screw Driver:

Pozidriv 2

Mounting Position:

any1 ... 6

Mounting on DIN Rail:

TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715

Minimum Mounting Distance:

Electrical Conductive Board, Horizontal - Up to 400 V 0 mmElectrical Conductive Board, Horizontal - Up to 690 V 1.5 mmElectrical Conductive Board, Vertical 75 mmOther Device Same Type, Horizontal 0 mmOther Device Same Type, Vertical 150 mm

Actuator Type:

Rotary Handle

Contact Position Indication:

ON / OFF

Standards:

IEC/EN 60947-1IEC/EN 60947-2IEC/EN 60947-4-1UL 60947-1UL 60947-4-1

Short-Circuit Current Rating (SCCR):

Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 5 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 5 kA

Maximum Operating Voltage UL/CSA:

Main Circuit 600 V AC

Full Load Amps Motor Use:

(110 ... 120 V AC) Three Phase 0.25 A(200 V AC) Three Phase 0.25 A(208 V AC) Three Phase 0.25 A(220 ... 240 V AC) Three Phase 0.25 A(440 ... 480 V AC) Three Phase 0.25 A(550 ... 600 V AC) Three Phase 0.25 A

Locked Rotor Amps:

(110 ... 120 V AC) Three Phase 1.5 A(200 V AC) Three Phase 1.5 A(208 V AC) Three Phase 1.5 A(220 ... 240 V AC) Three Phase 1.5 A(440 ... 480 V AC) Three Phase 1.5 A(550 ... 600 V AC) Three Phase 1.5 A

General Use Rating UL/CSA:

(600 V AC) 0.25 A

Connecting Capacity Main Circuit UL/CSA:

Flexible 1/2x 16-12 AWGStranded 1/2x 16-12 AWG

Tightening Torque UL/CSA:

Main Circuit 10 in·lb

Ambient Air Temperature:

Around the Enclosure 0 ... +40 °COperation -25 ... +70 °COperation Compensated -25 ... +55 °CStorage -50 ... +80 °C

Ambient Air Temperature Compensation:

Yes

Maximum Operating Altitude Permissible:

2000 m

Resistance to Shock acc. to IEC 60068-2-27:

11 ms Pulse 25g

Resistance to Vibrations:

5g 3 … 150 Hz

RoHS Status:

Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Package Level 1 Units:

box 1 piece

Package Level 1 Width:

92 mm

Package Level 1 Depth / Length:

95 mm

Package Level 1 Height:

50 mm

Package Level 1 Gross Weight:

0.24 kg

Package Level 1 EAN:

4013614320255

Package Level 2 Units:

carton 40 piece

Package Level 2 Width:

280 mm

Package Level 2 Depth / Length:

395 mm

Package Level 2 Height:

210 mm

Package Level 2 Gross Weight:

9.986 kg

Package Level 2 EAN:

4013614408625

Object Classification Code:

F

ETIM 4:

EC000074 - Motor protective circuit-breaker

ETIM 5:

EC000074 - Motor protective circuit-breaker

ETIM 6:

EC000074 - Motor protection circuit-breaker

ETIM 7:

EC000074 - Motor protection circuit-breaker

ETIM 8:

EC000074 - Motor protection circuit-breaker

eClass:

V11.0 : 27370401

UNSPSC:

39121521

IDEA Granular Category Code (IGCC):

4731 >> Manual Starters

E-Number (Finland):

3706002

E-Number (Sweden):

3111932

Document Links