The MO165 manual motor starter magnetic only is a compact and powerful range for motor protection up to 45 kW (400 V) in width of 55 mm. The devices are used to manually switch on and off loads/motors and to protect them reliably and without the need for a fuse from short-circuits. The manual motor starter offers a rated service short-circuit breaking capacity up to 100 kA at 400 V AC. A combination together with overload relays or motor controllers allows the protection of motors. Further features are the built-in disconnect function, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starters magnetic only are suitable for three- and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars and power in-feed blocks are available as accessory.
Minimum Order Quantity:
1 piece
Customs Tariff Number:
85362010
Product Net Width:
55 mm
Product Net Height:
142.65 mm
Product Net Depth / Length:
122.1 mm
Product Net Weight:
0.97 kg
Rated Service Short-Circuit Breaking Capacity (Ics):
(230 V AC) 50 kA(250 V DC) 3 Poles in Series 100 kA(400 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 30 kA(690 V AC) 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(230 V AC) 50 kA(250 V DC) 100 kA(400 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 30 kA(690 V AC) 10 kA
Rated Instantaneous Short-Circuit Current Setting (Ii):
630 A
Setting Range:
None
Rated Operational Power AC-3 (Pe):
(400 V) Three Phase 22 kW
Rated Operational Power AC-3e (Pe):
(400 V) Three Phase 22 kW
Rated Operational Voltage:
Main Circuit 690 V ACMain Circuit 250 V DC
Rated Operational Current (Ie):
42 A
Rated Operational Current AC-3 (Ie):
42 A
Rated Operational Current AC-3e (Ie):
42 A
Rated Operational Current DC-5 (Ie):
42 A
Rated Frequency (f):
Main Circuit 50 HzMain Circuit 60 Hz
Operating Frequency (fsw):
0 ... 415 Hz
Rated Impulse Withstand Voltage (Uimp):
Main Circuit 8 kV
Rated Insulation Voltage (Ui):
1000 V
Power Loss:
5.47 W
Number of Poles:
3
Conventional Free-air Thermal Current (Ith):
Main Circuit 42 A
Degree of Protection:
Housing IP20Main Circuit Terminals IP10
Pollution Degree:
3
Electrical Durability:
25000 cycle
Mechanical Durability:
50000 cycle
Terminal Type:
Screw Terminals
Connecting Capacity Main Circuit:
Flexible with Ferrule 1/2x 1 ... 35 mm²Flexible with Insulated Ferrule 1/2x 1 ... 35 mm²Flexible 1/2x 1 ... 35 mm²Rigid 1/2x 1 ... 4 mm²Solid 1/2x 1 ... 4 mm²Stranded 1/2x 1 ... 50 mm²
Tightening Torque:
Main Circuit 4 N·m
Wire Stripping Length:
Main Circuit 16 mm
Recommended Screw Driver:
Pozidriv 2
Mounting Position:
1 ... 6
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting Distance:
Electrical Conductive Board, Horizontal - Up to 1000 V 1.5 mmElectrical Conductive Board, Horizontal - Up to 400 V 0 mmElectrical Conductive Board, Horizontal - Up to 690 V 1.5 mmElectrical Conductive Board, Vertical 75 mmOther Device Same Type, Horizontal 0 mmOther Device Same Type, Vertical 150 mm
Actuator Type:
Rotary Handle
Contact Position Indication:
ON / OFF / TRIP
Standards:
CSA 22.2 No. 14IEC/EN 60947-1IEC/EN 60947-2IEC/EN 60947-4-1UL 60947-4-1
Remarks:
For overload protection of the motors, an appropriate thermal or electronic overload relays must be used
Short-Circuit Current Rating (SCCR):
Manual Self-Protected Combination Controllers (Type E), (480Y / 277 V AC) 65 kAManual Self-Protected Combination Controllers (Type E), (600Y / 347 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 30 kA
Maximum Operating Voltage UL/CSA:
Main Circuit 600 V AC
Horsepower Rating UL/CSA:
(200 V AC) Three Phase 10 Hp(208 V AC) Three Phase 10 Hp(220 ... 240 V AC) Three Phase 15 Hp(440 ... 480 V AC) Three Phase 30 Hp(550 ... 600 V AC) Three Phase 40 Hp
Full Load Amps Motor Use:
(200 V AC) Three Phase 32.2 A(208 V AC) Three Phase 30.8 A(220 ... 240 V AC) Three Phase 42 A(440 ... 480 V AC) Three Phase 40 A(550 ... 600 V AC) Three Phase 41 A
Locked Rotor Amps:
(200 V AC) Three Phase 186.3 A(208 V AC) Three Phase 179 A(220 ... 240 V AC) Three Phase 232 A(440 ... 480 V AC) Three Phase 218 A(550 ... 600 V AC) Three Phase 232 A
General Use Rating UL/CSA:
(600 V AC) 42 A
Connecting Capacity Main Circuit UL/CSA:
Flexible 1/2x 16-0 AWGStranded 1/2x 16-0 AWG
Tightening Torque UL/CSA:
Main Circuit 35 in·lb
Ambient Air Temperature:
Operation -25 ... +60 °COperation Compensated -25 ... +60 °CStorage -50 ... +80 °C
Ambient Air Temperature Compensation:
No
Maximum Operating Altitude Permissible:
2000 m
Resistance to Shock acc. to IEC 60068-2-27:
11 ms Pulse 25g
Resistance to Vibrations:
Mounted on DIN-Rail: 4g 3 … 160 Hz
RoHS Status:
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Package Level 1 Units:
box 1 piece
Package Level 1 Width:
64 mm
Package Level 1 Depth / Length:
177 mm
Package Level 1 Height:
140 mm
Package Level 1 Gross Weight:
1.1 kg
Package Level 1 EAN:
4013614486166
Package Level 2 Units:
carton 12 piece
Package Level 2 Width:
330 mm
Package Level 2 Depth / Length:
400 mm
Package Level 2 Height:
320 mm
Package Level 2 Gross Weight:
13 kg
Package Level 2 EAN:
4013614504020
Object Classification Code:
F
ETIM 5:
EC000074 - Motor protective circuit-breaker
ETIM 6:
EC000074 - Motor protection circuit-breaker
ETIM 7:
EC000074 - Motor protection circuit-breaker
ETIM 8:
EC000074 - Motor protection circuit-breaker
eClass:
V11.0 : 27370401
UNSPSC:
39121521
IDEA Granular Category Code (IGCC):
4731 >> Manual Starters
E-Number (Finland):
3707295
E-Number (Sweden):
3110142