1SAM461000R1013

MO165-25 Manual motor starter (MO165-25)

Trade Price

£148.77

Per

1

Unit

EA

Pack Quantity

1

1SAM461000R1013

Information

The MO165 manual motor starter magnetic only is a compact and powerful range for motor protection up to 45 kW (400 V) in width of 55 mm. The devices are used to manually switch on and off loads/motors and to protect them reliably and without the need for a fuse from short-circuits. The manual motor starter offers a rated service short-circuit breaking capacity up to 100 kA at 400 V AC. A combination together with overload relays or motor controllers allows the protection of motors. Further features are the built-in disconnect function, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starters magnetic only are suitable for three- and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars and power in-feed blocks are available as accessory.

Technical Specifications

Minimum Order Quantity:

1 piece

Customs Tariff Number:

85362010

Product Net Width:

55 mm

Product Net Height:

142.65 mm

Product Net Depth / Length:

122.1 mm

Product Net Weight:

0.96 kg

Rated Service Short-Circuit Breaking Capacity (Ics):

(230 V AC) 100 kA(250 V DC) 3 Poles in Series 100 kA(400 V AC) 100 kA(440 V AC) 50 kA(500 V AC) 30 kA(690 V AC) 10 kA

Rated Ultimate Short-Circuit Breaking Capacity (Icu):

(230 V AC) 100 kA(250 V DC) 100 kA(400 V AC) 100 kA(440 V AC) 50 kA(500 V AC) 30 kA(690 V AC) 10 kA

Rated Instantaneous Short-Circuit Current Setting (Ii):

375 A

Setting Range:

None

Rated Operational Power AC-3 (Pe):

(400 V) Three Phase 11 kW

Rated Operational Power AC-3e (Pe):

(400 V) Three Phase 11 kW

Rated Operational Voltage:

Main Circuit 690 V ACMain Circuit 250 V DC

Rated Operational Current (Ie):

25 A

Rated Operational Current AC-3 (Ie):

25 A

Rated Operational Current AC-3e (Ie):

25 A

Rated Operational Current DC-5 (Ie):

25 A

Rated Frequency (f):

Main Circuit 50 HzMain Circuit 60 Hz

Operating Frequency (fsw):

0 ... 415 Hz

Rated Impulse Withstand Voltage (Uimp):

Main Circuit 8 kV

Rated Insulation Voltage (Ui):

1000 V

Power Loss:

3.63 W

Number of Poles:

3

Conventional Free-air Thermal Current (Ith):

Main Circuit 25 A

Degree of Protection:

Housing IP20Main Circuit Terminals IP10

Pollution Degree:

3

Electrical Durability:

25000 cycle

Mechanical Durability:

50000 cycle

Terminal Type:

Screw Terminals

Connecting Capacity Main Circuit:

Flexible with Ferrule 1/2x 1 ... 35 mm²Flexible with Insulated Ferrule 1/2x 1 ... 35 mm²Flexible 1/2x 1 ... 35 mm²Rigid 1/2x 1 ... 4 mm²Solid 1/2x 1 ... 4 mm²Stranded 1/2x 1 ... 50 mm²

Tightening Torque:

Main Circuit 4 N·m

Wire Stripping Length:

Main Circuit 16 mm

Recommended Screw Driver:

Pozidriv 2

Mounting Position:

1 ... 6

Mounting on DIN Rail:

TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715

Minimum Mounting Distance:

Electrical Conductive Board, Horizontal - Up to 1000 V 1.5 mmElectrical Conductive Board, Horizontal - Up to 400 V 0 mmElectrical Conductive Board, Horizontal - Up to 690 V 1.5 mmElectrical Conductive Board, Vertical 75 mmOther Device Same Type, Horizontal 0 mmOther Device Same Type, Vertical 150 mm

Actuator Type:

Rotary Handle

Contact Position Indication:

ON / OFF / TRIP

Standards:

CSA 22.2 No. 14IEC/EN 60947-1IEC/EN 60947-2IEC/EN 60947-4-1UL 60947-4-1

Remarks:

For overload protection of the motors, an appropriate thermal or electronic overload relays must be used

Short-Circuit Current Rating (SCCR):

Manual Self-Protected Combination Controllers (Type E), (480Y / 277 V AC) 65 kAManual Self-Protected Combination Controllers (Type E), (600Y / 347 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 30 kA

Maximum Operating Voltage UL/CSA:

Main Circuit 600 V AC

Horsepower Rating UL/CSA:

(200 V AC) Three Phase 5 Hp(208 V AC) Three Phase 7.5 Hp(220 ... 240 V AC) Three Phase 7.5 Hp(440 ... 480 V AC) Three Phase 15 Hp(550 ... 600 V AC) Three Phase 20 Hp

Full Load Amps Motor Use:

(200 V AC) Three Phase 17.5 A(208 V AC) Three Phase 24.2 A(220 ... 240 V AC) Three Phase 22 A(440 ... 480 V AC) Three Phase 21 A(550 ... 600 V AC) Three Phase 22 A

Locked Rotor Amps:

(200 V AC) Three Phase 105.8 A(208 V AC) Three Phase 140 A(220 ... 240 V AC) Three Phase 127 A(440 ... 480 V AC) Three Phase 116 A(550 ... 600 V AC) Three Phase 116 A

General Use Rating UL/CSA:

(600 V AC) 25 A

Connecting Capacity Main Circuit UL/CSA:

Flexible 1/2x 16-0 AWGStranded 1/2x 16-0 AWG

Tightening Torque UL/CSA:

Main Circuit 35 in·lb

Ambient Air Temperature:

Operation -25 ... +60 °COperation Compensated -25 ... +60 °CStorage -50 ... +80 °C

Ambient Air Temperature Compensation:

No

Maximum Operating Altitude Permissible:

2000 m

Resistance to Shock acc. to IEC 60068-2-27:

11 ms Pulse 25g

Resistance to Vibrations:

Mounted on DIN-Rail: 4g 3 … 160 Hz

RoHS Status:

Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Package Level 1 Units:

box 1 piece

Package Level 1 Width:

64 mm

Package Level 1 Depth / Length:

177 mm

Package Level 1 Height:

140 mm

Package Level 1 Gross Weight:

1.1 kg

Package Level 1 EAN:

4013614486142

Package Level 2 Units:

carton 12 piece

Package Level 2 Width:

330 mm

Package Level 2 Depth / Length:

400 mm

Package Level 2 Height:

320 mm

Package Level 2 Gross Weight:

13 kg

Package Level 2 EAN:

4013614504006

Object Classification Code:

F

ETIM 5:

EC000074 - Motor protective circuit-breaker

ETIM 6:

EC000074 - Motor protection circuit-breaker

ETIM 7:

EC000074 - Motor protection circuit-breaker

ETIM 8:

EC000074 - Motor protection circuit-breaker

eClass:

V11.0 : 27370401

UNSPSC:

39121521

IDEA Granular Category Code (IGCC):

4731 >> Manual Starters

E-Number (Finland):

3707293

E-Number (Sweden):

3110060

Document Links