Trade Price
£74.90
Per
1
Unit
EA
Pack Quantity
1
The MO132-2.5 manual motor starter magnetic only is a compact 45 mm width device with a rated operational current of Ie = 2.50 A. This device is used to manually switch on and off loads/motors and to protect them reliably and without the need for a fuse from short-circuits. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 100 kA at 400 V AC. A combination together with overload relays or motor controllers allows the protection of motors. Further features are the built-in disconnect function, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter magnetic only is suitable for three- and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signalling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks are available as accessory.
Minimum Order Quantity:
1 piece
Customs Tariff Number:
85362010
Product Net Width:
45 mm
Product Net Height:
90 mm
Product Net Depth / Length:
86.75 mm
Product Net Weight:
0.265 kg
Rated Service Short-Circuit Breaking Capacity (Ics):
(230 V AC) 100 kA(400 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 100 kA(690 V AC) 100 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(230 V AC) 100 kA(400 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 100 kA(690 V AC) 100 kA
Rated Instantaneous Short-Circuit Current Setting (Ii):
31.3 A
Setting Range:
None
Rated Operational Power AC-3 (Pe):
(400 V) Three Phase 0.75 kW
Rated Operational Power AC-3e (Pe):
(400 V) Three Phase 0.75 kW
Rated Operational Voltage:
Main Circuit 690 V AC
Rated Operational Current (Ie):
2.5 A
Rated Operational Current AC-3 (Ie):
2.5 A
Rated Operational Current AC-3e (Ie):
2.5 A
Rated Frequency (f):
Main Circuit 50 HzMain Circuit 60 Hz
Operating Frequency (fsw):
0 ... 400 Hz
Rated Impulse Withstand Voltage (Uimp):
Main Circuit 6 kV
Rated Insulation Voltage (Ui):
690 V
Power Loss:
at Rated Operating Conditions per Pole 1.7 W
Number of Poles:
3
Conventional Free-air Thermal Current (Ith):
Main Circuit 2.5 A
Degree of Protection:
Housing IP20Main Circuit Terminals IP10
Pollution Degree:
3
Electrical Durability:
50000 cycle
Mechanical Durability:
100000 cycle
Terminal Type:
Screw Terminals
Connecting Capacity Main Circuit:
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²Flexible 1/2x 0.75 ... 2.5 mm²Rigid 1/2x 1 ... 4 mm²
Tightening Torque:
Main Circuit 0.8 ... 1.2 N·m
Wire Stripping Length:
Main Circuit 9 mm
Recommended Screw Driver:
Pozidriv 2
Mounting Position:
1 ... 6
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting Distance:
Electrical Conductive Board, Horizontal - Up to 400 V 0 mmElectrical Conductive Board, Horizontal - Up to 690 V 1.5 mmElectrical Conductive Board, Vertical 75 mmOther Device Same Type, Horizontal 0 mmOther Device Same Type, Vertical 150 mm
Actuator Type:
Rotary Handle
Contact Position Indication:
ON / OFF / TRIP
Standards:
IEC/EN 60947-1IEC/EN 60947-2IEC/EN 60947-4-1UL 60947-1UL 60947-4-1
Remarks:
For overload protection of the motors, an appropriate thermal or electronic overload relays must be used
Short-Circuit Current Rating (SCCR):
Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 47 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 47 kAAny UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 47 kA
Maximum Operating Voltage UL/CSA:
Main Circuit 600 V AC
Horsepower Rating UL/CSA:
(200 V AC) Three Phase 0.5 Hp(208 V AC) Three Phase 0.5 Hp(220 ... 240 V AC) Three Phase 0.5 Hp(440 ... 480 V AC) Three Phase 1 Hp(550 ... 600 V AC) Three Phase 1.5 Hp
Full Load Amps Motor Use:
(200 V AC) Three Phase 2.5 A(208 V AC) Three Phase 2.5 A(220 ... 240 V AC) Three Phase 2.5 A(440 ... 480 V AC) Three Phase 2.5 A(550 ... 600 V AC) Three Phase 2.5 A
Locked Rotor Amps:
(200 V AC) Three Phase 15 A(208 V AC) Three Phase 15 A(220 ... 240 V AC) Three Phase 15 A(440 ... 480 V AC) Three Phase 15 A(550 ... 600 V AC) Three Phase 15 A
General Use Rating UL/CSA:
(600 V AC) 2.5 A
Connecting Capacity Main Circuit UL/CSA:
Flexible 1/2x 16-12 AWGStranded 1/2x 16-12 AWG
Tightening Torque UL/CSA:
Main Circuit 10 in·lb
Ambient Air Temperature:
Around the Enclosure 0 ... +40 °COperation -25 ... +60 °CStorage -50 ... +80 °C
Ambient Air Temperature Compensation:
No
Maximum Operating Altitude Permissible:
2000 m
Resistance to Shock acc. to IEC 60068-2-27:
11 ms Pulse 25g
Resistance to Vibrations:
5g 3 … 150 Hz
RoHS Status:
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Package Level 1 Units:
box 1 piece
Package Level 1 Width:
92 mm
Package Level 1 Depth / Length:
95 mm
Package Level 1 Height:
50 mm
Package Level 1 Gross Weight:
0.28 kg
Package Level 1 EAN:
4013614400223
Package Level 2 Units:
carton 40 piece
Package Level 2 Width:
280 mm
Package Level 2 Depth / Length:
395 mm
Package Level 2 Height:
210 mm
Package Level 2 Gross Weight:
11.586 kg
Package Level 2 EAN:
4013614443671
Object Classification Code:
F
ETIM 4:
EC000074 - Motor protective circuit-breaker
ETIM 5:
EC000074 - Motor protective circuit-breaker
ETIM 6:
EC000074 - Motor protection circuit-breaker
ETIM 7:
EC000074 - Motor protection circuit-breaker
ETIM 8:
EC000074 - Motor protection circuit-breaker
eClass:
V11.0 : 27370401
UNSPSC:
39121521
IDEA Granular Category Code (IGCC):
4731 >> Manual Starters
E-Number (Finland):
3705885
E-Number (Sweden):
3110035