Trade Price
£2,290.07
Per
1
Unit
EA
Pack Quantity
1
GAF185...GAF300 3 pole contactor - 250 to 1750A DC-1 AC/DC operated 1NO+1NC aux * Part number: GAF300-10-11 * GAF185 ... GAF2050 contactors are designed for controlling resistive or slightly inductive loads up to 1000 V DC. * These contactors are of the block type design with 3 main poles for connection in series by the user according to conductor cross-sectional area or by using LP connection bars to be ordered separately.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Product Net Width
140 mm
Product Net Depth / Length
180.5 mm
Product Net Height
227 mm
Product Net Weight
5.5 kg
Number of Main Contacts NO
1
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Rated Operational Voltage
Main Circuit 1000 V
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 500 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2500 A
Rated Operational Current DC-1 (Ie)
(1000 V) 3 Poles in Series, 40 °C 500 A(1000 V) 3 Poles in Series, 55 °C 400 A(1000 V) 3 Poles in Series, 70 °C 325 A(220 V) 3 Poles in Series, 40 °C 500 A(220 V) 3 Poles in Series, 55 °C 400 A(220 V) 3 Poles in Series, 70 °C 325 A(400 V) 3 Poles in Series, 40 °C 500 A(400 V) 3 Poles in Series, 55 °C 400 A(400 V) 3 Poles in Series, 70 °C 325 A(600 V) 3 Poles in Series, 40 °C 500 A(600 V) 3 Poles in Series, 55 °C 400 A(600 V) 3 Poles in Series, 70 °C 325 A
Rated Insulation Voltage (Ui)
acc. to UL/CSA 1000 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Mechanical Durability
5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ <= 70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V60 Hz 48 ... 130 VDC Operation 48 ... 130 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 10 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 10 V·AHolding at Max. Rated Control Circuit Voltage DC 2 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 470 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 470 V·APull-in at Max. Rated Control Circuit Voltage DC 520 V·A
Connecting Capacity Main Circuit
Bar 32 mm²Rigid Al-Cable 2 x 95 ... 120 mm²Rigid Cu-Cable 16 ... 240 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 2 x 1 ... 4 mm²Stranded 2 x 1 .... 4 mm²
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type
Main Circuit: Bars
Maximum Operating Voltage UL/CSA
Main Circuit 1000 V
General Use Rating UL/CSA
(1000 V DC) 400 A(440 V DC) 400 A(600 V DC) 400 A
Ambient Air Temperature
Operation -40 ... +80 °CStorage -40 ... +70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Shock Direction: A 5 gShock Direction: B1 5 gShock Direction: B2 5 gShock Direction: C1 5 gShock Direction: C2 5 g
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Package Level 1 Units
box 1 piece
Package Level 1 Width
203 mm
Package Level 1 Depth / Length
245 mm
Package Level 1 Height
188 mm
Package Level 1 Gross Weight
6.2 kg
Package Level 1 EAN
7320500400869
Object Classification Code
Q
ETIM 4
EC002552 - Power contactor, DC switching
ETIM 5
EC002552 - Power contactor, DC switching
ETIM 6
EC002552 - Power contactor, DC switching
ETIM 7
EC002552 - Power contactor, DC switching
ETIM 8
EC002552 - Power contactor, DC switching
eClass
V11.0 : 27371018
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4763 >> Power contactor, DC switching