Trade Price
£497.68
Per
1
Unit
EA
Pack Quantity
1
The AF96-30-00-12 is a 3 pole - 1000 V IEC or 600 UL contactor with screw terminals, controlling motors up to 45 kW / 400 V AC (AC-3) or 60 hp / 480 V UL and switching power circuits up to 130 A (AC-1) or 115 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity:
1 piece
Customs Tariff Number:
85364900
Product Net Width:
70 mm
Product Net Depth / Length:
116 mm
Product Net Height:
125.5 mm
Product Net Weight:
1.22 kg
Number of Main Contacts NO:
3
Number of Main Contacts NC:
0
Number of Auxiliary Contacts NO:
0
Number of Auxiliary Contacts NC:
0
Standards:
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational Voltage:
Main Circuit 1000 V
Rated Frequency (f):
Control Circuit 50 / 60 HzMain Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith):
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 130 A
Rated Operational Current AC-1 (Ie):
(690 V) 40 °C 130 A(690 V) 60 °C 105 A(690 V) 70 °C 90 A
Rated Operational Current AC-3 (Ie):
(415 V) 60 °C 96 A(440 V) 60 °C 96 A(500 V) 60 °C 80 A(690 V) 60 °C 57 A(1000 V) 60 °C 30 A(380 / 400 V) 60 °C 105 A(220 / 230 / 240 V) 60 °C 105 A
Rated Operational Current AC-3e (Ie):
(415 V) 60 °C 96 A(440 V) 60 °C 96 A(500 V) 60 °C 80 A(690 V) 60 °C 57 A(380 / 400 V) 60 °C 105 A(220 / 230 / 240 V) 60 °C 105 A
Rated Operational Power AC-3 (Pe):
(415 V) 55 kW(440 V) 55 kW(500 V) 55 kW(690 V) 55 kW(1000 V) 40 kW(380 / 400 V) 45 kW(380 / 400 V) 55 kW(220 / 230 / 240 V) 25 kW(220 / 230 / 240 V) 30 kW
Rated Operational Power AC-3e (Pe):
(415 V) 55 kW(440 V) 55 kW(500 V) 55 kW(690 V) 55 kW(380 / 400 V) 45 kW(380 / 400 V) 55 kW(220 / 230 / 240 V) 25 kW(220 / 230 / 240 V) 30 kW
Rated Short-time Withstand Current Low Voltage (Icw):
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 840 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A
Maximum Breaking Capacity:
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A
Maximum Electrical Switching Frequency:
(AC-1) 600 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 1200 cycles per hour
Rated Operational Current DC-1 (Ie):
(110 V) 2 Poles in Series, 40 °C 130 A(110 V) 2 Poles in Series, 60 °C 105 A(110 V) 2 Poles in Series, 70 °C 90 A(110 V) 3 Poles in Series, 40 °C 130 A(110 V) 3 Poles in Series, 60 °C 105 A(110 V) 3 Poles in Series, 70 °C 90 A(220 V) 3 Poles in Series, 40 °C 125 A(220 V) 3 Poles in Series, 60 °C 105 A(220 V) 3 Poles in Series, 70 °C 90 A(72 V) 1-Pole, 40 °C 130 A(72 V) 1-Pole, 60 °C 105 A(72 V) 1-Pole, 70 °C 90 A(72 V) 2 Poles in Series, 40 °C 130 A(72 V) 2 Poles in Series, 60 °C 105 A(72 V) 2 Poles in Series, 70 °C 90 A(72 V) 3 Poles in Series, 40 °C 130 A(72 V) 3 Poles in Series, 60 °C 105 A(72 V) 3 Poles in Series, 70 °C 90 A
Rated Operational Current DC-3 (Ie):
(110 V) 2 Poles in Series, 40 °C 130 A(110 V) 2 Poles in Series, 60 °C 105 A(110 V) 2 Poles in Series, 70 °C 90 A(110 V) 3 Poles in Series, 40 °C 130 A(110 V) 3 Poles in Series, 60 °C 105 A(110 V) 3 Poles in Series, 70 °C 90 A(220 V) 3 Poles in Series, 40 °C 130 A(220 V) 3 Poles in Series, 60 °C 105 A(220 V) 3 Poles in Series, 70 °C 90 A(72 V) 1-Pole, 40 °C 130 A(72 V) 1-Pole, 60 °C 105 A(72 V) 1-Pole, 70 °C 90 A(72 V) 2 Poles in Series, 40 °C 130 A(72 V) 2 Poles in Series, 60 °C 105 A(72 V) 2 Poles in Series, 70 °C 90 A(72 V) 3 Poles in Series, 40 °C 130 A(72 V) 3 Poles in Series, 60 °C 105 A(72 V) 3 Poles in Series, 70 °C 90 A
Rated Operational Current DC-5 (Ie):
(110 V) 2 Poles in Series, 40 °C 130 A(110 V) 2 Poles in Series, 60 °C 105 A(110 V) 2 Poles in Series, 70 °C 90 A(110 V) 3 Poles in Series, 40 °C 130 A(110 V) 3 Poles in Series, 60 °C 105 A(110 V) 3 Poles in Series, 70 °C 90 A(220 V) 3 Poles in Series, 40 °C 130 A(220 V) 3 Poles in Series, 60 °C 105 A(220 V) 3 Poles in Series, 70 °C 90 A(72 V) 1-Pole, 40 °C 130 A(72 V) 1-Pole, 60 °C 105 A(72 V) 1-Pole, 70 °C 90 A(72 V) 2 Poles in Series, 40 °C 130 A(72 V) 2 Poles in Series, 60 °C 105 A(72 V) 2 Poles in Series, 70 °C 90 A(72 V) 3 Poles in Series, 40 °C 130 A(72 V) 3 Poles in Series, 60 °C 105 A(72 V) 3 Poles in Series, 70 °C 90 A
Rated Insulation Voltage (Ui):
acc. to IEC 60947-4-1 1000 Vacc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp):
8 kV
Maximum Mechanical Switching Frequency:
3600 cycles per hour
Rated Control Circuit Voltage (Uc):
50 Hz 48 ... 130 V60 Hz 48 ... 130 VDC Operation 48 ... 130 V
Coil Consumption:
Average Holding Value 50 / 60 Hz 4 V·AAverage Holding Value 50 Hz 4 V·AAverage Holding Value 60 Hz 4 V·AAverage Holding Value DC 2 WAverage Holding Value, from Warm State 2 W
Operate Time:
Between Coil De-energization and NC Contact Closing 19 ... 105 msBetween Coil De-energization and NO Contact Opening 17 ... 100 msBetween Coil Energization and NC Contact Opening 38 ... 95 msBetween Coil Energization and NO Contact Closing 42 ... 100 ms
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied):
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit:
Flexible with Ferrule 1/2x 6 ... 50 mm²Flexible with Insulated Ferrule 1/2x 6 ... 50 mm²Rigid Stranded 1x 6 ... 70 mm²Rigid Stranded 2x 6 ... 50 mm²
Connecting Capacity Control Circuit:
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²Rigid Solid 1/2x 1 ... 2.5 mm²Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length:
Control Circuit 10 mmMain Circuit 17 mm
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Terminal Type:
Screw Terminals
Maximum Operating Voltage UL/CSA:
Main Circuit 600 V
General Use Rating UL/CSA:
(600 V AC) 115 A
Horsepower Rating UL/CSA:
(120 V AC) Single Phase 7-1/2 hp(200 ... 208 V AC) Three Phase 30 hp(220 ... 240 V AC) Three Phase 40 hp(240 V AC) Single Phase 20 hp(440 ... 480 V AC) Three Phase 75 hp(550 ... 600 V AC) Three Phase 75 hp
Connecting Capacity Main Circuit UL/CSA:
Rigid Stranded 1/2x 6-1 AWG
Connecting Capacity Control Circuit UL/CSA:
Rigid Solid 1/2x 18-14 AWGRigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA:
Control Circuit 11 in·lbMain Circuit 53 in·lb
Ambient Air Temperature:
Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °CClose to Contactor without Thermal O/L Relay -40 ... 70 °CClose to Contactor for Storage -60 ... +80 °C
Climatic Withstand:
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible:
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27:
Closed, Shock Direction: A 25 gClosed, Shock Direction: B1 25 gClosed, Shock Direction: B2 15 gClosed, Shock Direction: C1 25 gClosed, Shock Direction: C2 25 gOpen, Shock Direction: B1 5 g
Resistance to Vibrations:
3g Closed Position & 3g Open Position 5 … 300 Hz
RoHS Status:
Following EU Directive 2011/65/EU
Package Level 1 Units:
box 1 piece
Package Level 1 Width:
150 mm
Package Level 1 Depth / Length:
150 mm
Package Level 1 Height:
103 mm
Package Level 1 Gross Weight:
1.34 kg
Package Level 1 EAN:
3471523133228
Package Level 2 Units:
box 8 piece
Package Level 2 Width:
250 mm
Package Level 2 Depth / Length:
300 mm
Package Level 2 Height:
300 mm
Package Level 2 Gross Weight:
10.72 kg
Package Level 3 Units:
192 piece
Object Classification Code:
Q
ETIM 4:
EC000066 - Magnet contactor, AC-switching
ETIM 5:
EC000066 - Magnet contactor, AC-switching
ETIM 6:
EC000066 - Power contactor, AC switching
ETIM 7:
EC000066 - Power contactor, AC switching
ETIM 8:
EC000066 - Power contactor, AC switching
eClass:
V11.0 : 27371003
UNSPSC:
39121529
IDEA Granular Category Code (IGCC):
4758 >> Iec Contactors
E-Number (Finland):
3707136
E-Number (Sweden):
3210056