Trade Price
£372.26
Per
1
Unit
EA
Pack Quantity
1
AF40...AF96 3 Pole contactors - 18.5 to 45kW AC/DC operated * Part number: AF65-30-00-11 * AF40 ... AF96 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC and 220 V DC. These contactors are of the block type design with 3 main poles. * Control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage range (e.g. 100...250 V AC and DC), only 4 control voltage ranges covering 24...500 V 50/60 Hz and 20...500 V DC - can manage large control voltage variations - reduced panel energy consumption - very distinct closing and opening. * Built-in surge suppression * Add-on auxiliary contact blocks for front or side mounting and a wide range of accessories. * Not suitable for direct control by PLC-output.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Product Net Width
55 mm
Product Net Depth / Length
111 mm
Product Net Height
125.5 mm
Product Net Weight
0.97 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Control Circuit 50 / 60 HzMain Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 105 A(690 V) 60 °C 90 A(690 V) 70 °C 80 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 65 A(440 V) 60 °C 65 A(500 V) 60 °C 55 A(690 V) 60 °C 39 A(380 / 400 V) 60 °C 65 A(220 / 230 / 240 V) 60 °C 65 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 65 A(440 V) 60 °C 65 A(500 V) 60 °C 55 A(690 V) 60 °C 39 A(380 / 400 V) 60 °C 65 A(220 / 230 / 240 V) 60 °C 65 A
Rated Operational Power AC-3 (Pe)
(400 V) 30 kW(415 V) 37 kW(440 V) 37 kW(500 V) 37 kW(690 V) 37 kW(380 / 400 V) 30 kW(220 / 230 / 240 V) 18.5 kW
Rated Operational Power AC-3e (Pe)
(415 V) 37 kW(440 V) 37 kW(500 V) 37 kW(690 V) 37 kW(380 / 400 V) 30 kW(220 / 230 / 240 V) 18.5 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 1200 cycles per hour
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 105 A(110 V) 2 Poles in Series, 60 °C 90 A(110 V) 2 Poles in Series, 70 °C 80 A(110 V) 3 Poles in Series, 40 °C 105 A(110 V) 3 Poles in Series, 60 °C 90 A(110 V) 3 Poles in Series, 70 °C 80 A(220 V) 3 Poles in Series, 40 °C 105 A(220 V) 3 Poles in Series, 60 °C 90 A(220 V) 3 Poles in Series, 70 °C 80 A(72 V) 1-Pole, 40 °C 105 A(72 V) 1-Pole, 60 °C 90 A(72 V) 1-Pole, 70 °C 80 A(72 V) 2 Poles in Series, 40 °C 105 A(72 V) 2 Poles in Series, 60 °C 90 A(72 V) 2 Poles in Series, 70 °C 80 A(72 V) 3 Poles in Series, 40 °C 105 A(72 V) 3 Poles in Series, 60 °C 90 A(72 V) 3 Poles in Series, 70 °C 80 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 105 A(110 V) 2 Poles in Series, 60 °C 90 A(110 V) 2 Poles in Series, 70 °C 80 A(110 V) 3 Poles in Series, 40 °C 105 A(110 V) 3 Poles in Series, 60 °C 90 A(110 V) 3 Poles in Series, 70 °C 80 A(220 V) 3 Poles in Series, 40 °C 105 A(220 V) 3 Poles in Series, 60 °C 90 A(220 V) 3 Poles in Series, 70 °C 80 A(72 V) 1-Pole, 40 °C 105 A(72 V) 1-Pole, 60 °C 90 A(72 V) 1-Pole, 70 °C 80 A(72 V) 2 Poles in Series, 40 °C 105 A(72 V) 2 Poles in Series, 60 °C 90 A(72 V) 2 Poles in Series, 70 °C 80 A(72 V) 3 Poles in Series, 40 °C 105 A(72 V) 3 Poles in Series, 60 °C 90 A(72 V) 3 Poles in Series, 70 °C 80 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 105 A(110 V) 2 Poles in Series, 60 °C 90 A(110 V) 2 Poles in Series, 70 °C 80 A(110 V) 3 Poles in Series, 40 °C 105 A(110 V) 3 Poles in Series, 60 °C 90 A(110 V) 3 Poles in Series, 70 °C 80 A(220 V) 3 Poles in Series, 40 °C 105 A(220 V) 3 Poles in Series, 60 °C 90 A(220 V) 3 Poles in Series, 70 °C 80 A(72 V) 1-Pole, 40 °C 105 A(72 V) 1-Pole, 60 °C 90 A(72 V) 1-Pole, 70 °C 80 A(72 V) 2 Poles in Series, 40 °C 105 A(72 V) 2 Poles in Series, 60 °C 90 A(72 V) 2 Poles in Series, 70 °C 80 A(72 V) 3 Poles in Series, 40 °C 105 A(72 V) 3 Poles in Series, 60 °C 90 A(72 V) 3 Poles in Series, 70 °C 80 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 Vacc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 24 ... 60 V60 Hz 24 ... 60 VDC Operation 20 ... 60 V
Coil Consumption
Average Holding Value 50 / 60 Hz 4 V·AAverage Holding Value 50 Hz 4 V·AAverage Holding Value 60 Hz 4 V·AAverage Holding Value DC 2 WAverage Holding Value, from Warm State 2 W
Operate Time
Between Coil De-energization and NC Contact Closing 19 ... 105 msBetween Coil De-energization and NO Contact Opening 17 ... 100 msBetween Coil Energization and NC Contact Opening 38 ... 95 msBetween Coil Energization and NO Contact Closing 42 ... 100 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 4 ... 35 mm²Flexible with Insulated Ferrule 1/2x 4 ... 35 mm²Rigid Stranded 1/2x 6 ... 35 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²Rigid Solid 1/2x 1 ... 2.5 mm²Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Control Circuit 10 mmMain Circuit 16 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Terminal Type
Screw Terminals
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 90 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 5 hp(200 ... 208 V AC) Three Phase 20 hp(220 ... 240 V AC) Three Phase 25 hp(240 V AC) Single Phase 15 hp(440 ... 480 V AC) Three Phase 50 hp(550 ... 600 V AC) Three Phase 60 hp
Connecting Capacity Main Circuit UL/CSA
Rigid Stranded 1/2x 10-2 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWGRigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Control Circuit 11 in·lbMain Circuit 35 in·lb
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °CClose to Contactor without Thermal O/L Relay -40 ... 70 °CClose to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Closed, Shock Direction: A 25 gClosed, Shock Direction: B1 25 gClosed, Shock Direction: B2 15 gClosed, Shock Direction: C1 25 gClosed, Shock Direction: C2 25 gOpen, Shock Direction: B1 5 g
Resistance to Vibrations acc. to IEC 60068-2-6
5 ... 300 Hz 3 g closed position / 3 g open position
RoHS Status
Following EU Directive 2011/65/EU
Package Level 1 Units
box 1 piece
Package Level 1 Width
150 mm
Package Level 1 Depth / Length
150 mm
Package Level 1 Height
97 mm
Package Level 1 Gross Weight
1.07 kg
Package Level 1 EAN
3471523132610
Package Level 2 Units
box 10 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
300 mm
Package Level 2 Gross Weight
10.7 kg
Package Level 3 Units
240 piece
Object Classification Code
Q
ETIM 4
EC000066 - Magnet contactor, AC-switching
ETIM 5
EC000066 - Magnet contactor, AC-switching
ETIM 6
EC000066 - Power contactor, AC switching
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3707046
E-Number (Sweden)
3210042