AF1250...AF2650 3 Pole contactor * Part number: AF1650-30-11 * AF1250 ... AF2050 contactors are mainly used for controlling power circuits up to 1000 V AC or 850 V DC, AF2650 for controlling power up to 1000 V AC. These contactors are of the block type design with 3 main poles. * Control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage range - can manage large control voltage variations - reduced panel energy consumption - very distinct closing and opening - can withstand short voltage dips and voltages sags (SEMI F47 conditions of use on request). * Built-in surge suppression * Add-on auxiliary contact blocks for side mounting and a wide range of accessories
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Product Net Width
438 mm
Product Net Depth / Length
244 mm
Product Net Height
392 mm
Product Net Weight
33 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Rated Operational Voltage
Main Circuit 1000 V
Rated Frequency (f)
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 1650 A
Rated Operational Current AC-1 (Ie)
(1000 V) 40 °C 1650 A(1000 V) 55 °C 1450 A(1000 V) 70 °C 1270 A(690 V) 40 °C 1650 A(690 V) 55 °C 1450 A(690 V) 70 °C 1270 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 1060 A(440 V) 55 °C 1060 A(500 V) 55 °C 970 A(690 V) 55 °C 970 A(1000 V) 55 °C 400 A(380 / 400 V) 55 °C 1060 A(220 / 230 / 240 V) 55 °C 1060
Rated Operational Power AC-3 (Pe)
(415 V) 630 kW(440 V) 710 kW(500 V) 710 kW(690 V) 1000 kW(1000 V) 600 kW(380 / 400 V) 560 kW(220 / 230 / 240 V) 315 kW
Rated Making Capacity AC-3
10 x Ie AC-3
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 10000 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 2200 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 5500 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 12000 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 7500 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 12000 A
Maximum Electrical Switching Frequency
(AC-1) 60 cycles per hour(AC-2 / AC-4) 60 cycles per hour(AC-3) 60 cycles per hour
Rated Operational Current DC-1 (Ie)
(110 V) 1-Pole, 40 °C 1650 A(110 V) 2 Poles in Series, 40 °C 1650 A(220 V) 3 Poles in Series, 40 °C 1650 A(600 V) 3 Poles in Series, 40 °C 1650 A(850 V) 3 Poles in Series, 40 °C 1650 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 1000 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Mechanical Durability
0.5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ <= 70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 100 ... 250 V60 Hz 100 ... 250 VDC Operation 100 ... 250 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 48 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 48 V·AHolding at Max. Rated Control Circuit Voltage DC 20.5 V·APull-in at Max. Rated Control Circuit Voltage 50 Hz 2450 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 2450 V·APull-in at Max. Rated Control Circuit Voltage DC 2290 V·A
Operate Time
Between Coil De-energization and NC Contact Closing 35 ... 55 msBetween Coil De-energization and NO Contact Opening 35 ... 55 msBetween Coil Energization and NC Contact Opening 50 ... 80 msBetween Coil Energization and NO Contact Closing 50 ... 80 ms
Connecting Capacity Main Circuit
Bar 100 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 2 x 1 ... 4 mm²Stranded 2 x 1 .... 4 mm²
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type
Main Circuit: Bars
NEMA Size
8
Horsepower Rating NEMA
(230 V AC) Three Phase 450 Hp(460 V AC) Three Phase 900 Hp(575 V AC) Three Phase 900 Hp
Maximum Operating Voltage UL/CSA
Main Circuit 1000 V
General Use Rating UL/CSA
(1000 V AC) 1650 A(600 V AC) 1650 A
Horsepower Rating UL/CSA
(220 ... 240 V AC) Three Phase 450 hp(440 ... 480 V AC) Three Phase 900 hp(550 ... 600 V AC) Three Phase 1150 hp
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °CClose to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °CClose to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Package Level 1 Units
box 1 piece
Package Level 1 Width
555 mm
Package Level 1 Depth / Length
365 mm
Package Level 1 Height
500 mm
Package Level 1 Gross Weight
35 kg
Package Level 1 EAN
7320500249703
Package Level 2 Units
1 piece
Object Classification Code
Q
ETIM 4
EC000066 - Magnet contactor, AC-switching
ETIM 5
EC000066 - Magnet contactor, AC-switching
ETIM 6
EC000066 - Power contactor, AC switching
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3709258
E-Number (Norway)
4115390
E-Number (Sweden)
4115390