1SFL597001R7011

AF460-30-11 100-250V AC/DC Contactor (AF460-30-11-100)

Trade Price

£2,411.70

Per

1

Unit

EA

Pack Quantity

1

1SFL597001R7011

Information

AF400...AF750 3 Pole contactor * Part number: AF460-30-11 * AF400 ... AF750 contactors are mainly used for controlling 3-phase motors and power circuits up to 1000 V AC or 600 V DC. These contactors are of the block type design with 3 main poles. * Control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage range - can manage large control voltage variations - reduced panel energy consumption - very distinct closing and opening - can withstand short voltage dips and voltages sags (SEMI F47 conditions of use on request). * Built-in surge suppression * Add-on auxiliary contact blocks for side mounting and a wide range of accessories * AF400 ... AF750 are equipped with low voltage inputs for control, for example by a PLC.

Technical Specifications

Minimum Order Quantity

1 piece

Customs Tariff Number

85364900

Product Net Width

186 mm

Product Net Depth / Length

216 mm

Product Net Height

278 mm

Product Net Weight

10.6 kg

Number of Main Contacts NO

3

Number of Main Contacts NC

0

Number of Auxiliary Contacts NO

1

Number of Auxiliary Contacts NC

1

Rated Operational Voltage

Main Circuit 1000 V

Rated Frequency (f)

Main Circuit 50 / 60 Hz

Conventional Free-air Thermal Current (Ith)

acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 700 A

Rated Operational Current AC-1 (Ie)

(1000 V) 40 °C 700 A(1000 V) 55 °C 600 A(1000 V) 60 °C 600 A(1000 V) 70 °C 480 A(690 V) 40 °C 700 A(690 V) 55 °C 600 A(690 V) 70 °C 480 A

Rated Operational Current AC-3 (Ie)

(415 V) 55 °C 460 A(440 V) 55 °C 460 A(500 V) 55 °C 460 A(690 V) 55 °C 400 A(1000 V) 55 °C 200 A(380 / 400 V) 55 °C 460 A(220 / 230 / 240 V) 55 °C 460

Rated Operational Power AC-3 (Pe)

(415 V) 250 kW(440 V) 250 kW(500 V) 315 kW(690 V) 355 kW(1000 V) 280 kW(380 / 400 V) 250 kW(220 / 230 / 240 V) 132 kW

Rated Breaking Capacity AC-3

8 x Ie AC-3

Rated Making Capacity AC-3

10 x Ie AC-3

Short-Circuit Protective Devices

gG Type Fuses 800 A

Rated Short-time Withstand Current Low Voltage (Icw)

at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 4400 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 840 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 2500 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 4600 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 3100 A

Maximum Breaking Capacity

cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 5000 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 4500 A

Maximum Electrical Switching Frequency

(AC-1) 300 cycles per hour(AC-2 / AC-4) 60 cycles per hour(AC-3) 300 cycles per hour

Rated Operational Current DC-1 (Ie)

(110 V) 1-Pole, 40 °C 700 A(110 V) 2 Poles in Series, 40 °C 700 A(220 V) 3 Poles in Series, 40 °C 700 A(600 V) 3 Poles in Series, 40 °C 700 A

Rated Operational Current DC-3 (Ie)

(110 V) 1-Pole, 40 °C 700 A(110 V) 2 Poles in Series, 40 °C 700 A(220 V) 3 Poles in Series, 40 °C 700 A(600 V) 3 Poles in Series, 40 °C 700 A

Rated Operational Current DC-5 (Ie)

(110 V) 1-Pole, 40 °C 700 A(110 V) 2 Poles in Series, 40 °C 700 A(220 V) 3 Poles in Series, 40 °C 700 A(600 V) 3 Poles in Series, 40 °C 700 A

Rated Insulation Voltage (Ui)

acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V

Rated Impulse Withstand Voltage (Uimp)

Main Circuit 8 kV

Mechanical Durability

3 million

Maximum Mechanical Switching Frequency

300 cycles per hour

Coil Operating Limits

(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ <= 70 °C)

Rated Control Circuit Voltage (Uc)

50 Hz 100 ... 250 V60 Hz 100 ... 250 VDC Operation 100 ... 250 V

Coil Consumption

Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 12 V·AHolding at Max. Rated Control Circuit Voltage DC 5 V·APull-in at Max. Rated Control Circuit Voltage 50 Hz 955 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 955 V·APull-in at Max. Rated Control Circuit Voltage DC 895 V·A

Operate Time

Between Coil De-energization and NC Contact Closing 45 ... 55 msBetween Coil De-energization and NO Contact Opening 48 ... 58 msBetween Coil Energization and NC Contact Opening 45 ... 115 msBetween Coil Energization and NO Contact Closing 50 ... 120 ms

Connecting Capacity Main Circuit

Bar 47 mm²Rigid Al-Cable 2x240 mm²Rigid Cu-Cable 240 mm²

Connecting Capacity Auxiliary Circuit

Flexible with Ferrule 2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 2 x 1 ... 4 mm²Stranded 2 x 1 .... 4 mm²

Degree of Protection

acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00

Terminal Type

Main Circuit: Bars

NEMA Size

6

Horsepower Rating NEMA

(200 V AC) Three Phase 150 Hp(230 V AC) Three Phase 200 Hp(460 V AC) Three Phase 400 Hp(575 V AC) Three Phase 400 Hp

Maximum Operating Voltage UL/CSA

Main Circuit 1000 V

General Use Rating UL/CSA

(600 V AC) 650 A

Horsepower Rating UL/CSA

(200 V AC) Three Phase 150 hp(208 V AC) Three Phase 150 hp(220 ... 240 V AC) Three Phase 200 hp(440 ... 480 V AC) Three Phase 400 hp(550 ... 600 V AC) Three Phase 500 hp

Ambient Air Temperature

Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °CClose to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °CClose to Contactor for Storage -40 ... 70 °C

Maximum Operating Altitude Permissible

Without Derating 3000 m

Resistance to Shock acc. to IEC 60068-2-27

Shock Direction: A 5 gShock Direction: B1 5 gShock Direction: B2 5 gShock Direction: C1 5 gShock Direction: C2 5 g

RoHS Status

Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

ABB EcoSolutions

Yes

Circular Design Principles Recyclability Rate

Design for Closing Resource Loops - Standard EN45555 - 63.1 %

Group Waste to Landfill Target

Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility

Improved Resource Efficiency for Customers

Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line

Sustainable Material Content

Recycled Metal - 37 %

Package Level 1 Units

box 1 piece

Package Level 1 Width

280 mm

Package Level 1 Depth / Length

375 mm

Package Level 1 Height

310 mm

Package Level 1 Gross Weight

12 kg

Package Level 1 EAN

7320500217658

Object Classification Code

Q

ETIM 4

EC000066 - Magnet contactor, AC-switching

ETIM 5

EC000066 - Magnet contactor, AC-switching

ETIM 6

EC000066 - Power contactor, AC switching

ETIM 7

EC000066 - Power contactor, AC switching

ETIM 8

EC000066 - Power contactor, AC switching

eClass

V11.0 : 27371003

UNSPSC

39121529

IDEA Granular Category Code (IGCC)

4758 >> Iec Contactors

E-Number (Finland)

3709333

E-Number (Norway)

4115292

E-Number (Sweden)

3228346

Document Links