1SBL276001R2300

AF30Z-30-00-23 100-250V50/60HZ-DC Cont (AF30Z-30-00-23)

Trade Price

£162.37

Per

1

Unit

EA

Pack Quantity

1

1SBL276001R2300

Information

AF09Z...AF38Z 3 Pole contactors - 4 to 18.5kW AC/DC operated, low consumption * Part number: AF30Z-30-00-23 * AF09Z ... AF38Z contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC and 220 V DC. These contactors are of the block type design with 3 main poles. * Control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage range (e.g. 100...250 V AC and DC), only 4 control voltage ranges covering 24...250 V 50/60 Hz and 12...250 V DC - can manage large control voltage variations - allow direct control by PLC-output = 24 V DC 500 mA - reduced panel energy consumption - very distinct closing and opening - can withstand short voltage dips and voltage sags (SEMI F47-0706 conditions of use on request). * Built-in surge suppression * Add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.

Technical Specifications

Minimum Order Quantity

1 piece

Customs Tariff Number

85364900

Product Net Width

45 mm

Product Net Depth / Length

86 mm

Product Net Height

86 mm

Product Net Weight

0.35 kg

Number of Main Contacts NO

3

Number of Main Contacts NC

0

Number of Auxiliary Contacts NO

0

Number of Auxiliary Contacts NC

0

Standards

IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1

Rated Operational Voltage

Main Circuit 690 V

Rated Frequency (f)

Control Circuit 50 / 60 HzMain Circuit 50 / 60 Hz

Conventional Free-air Thermal Current (Ith)

acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 50 A

Rated Operational Current AC-1 (Ie)

(690 V) 40 °C 50 A(690 V) 60 °C 42 A(690 V) 70 °C 37 A

Rated Operational Current AC-3 (Ie)

(415 V) 60 °C 32 A(440 V) 60 °C 32 A(500 V) 60 °C 28 A(690 V) 60 °C 21 A(380 / 400 V) 60 °C 32 A(220 / 230 / 240 V) 60 °C 33 A

Rated Operational Current AC-3e (Ie)

(415 V) 60 °C 32 A(440 V) 60 °C 32 A(500 V) 60 °C 28 A(690 V) 60 °C 21 A(380 / 400 V) 60 °C 32 A(220 / 230 / 240 V) 60 °C 33 A

Rated Operational Power AC-3 (Pe)

(400 V) 15 kW(415 V) 15 kW(440 V) 18.5 kW(500 V) 18.5 kW(690 V) 18.5 kW(380 / 400 V) 15 kW(220 / 230 / 240 V) 9 kW

Rated Operational Power AC-3e (Pe)

(415 V) 15 kW(440 V) 18.5 kW(500 V) 18.5 kW(690 V) 18.5 kW(380 / 400 V) 15 kW(220 / 230 / 240 V) 9 kW

Rated Short-time Withstand Current Low Voltage (Icw)

at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 350 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 50 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 700 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A

Maximum Breaking Capacity

cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 500 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 200 A

Maximum Electrical Switching Frequency

(AC-1) 600 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 1200 cycles per hour

Rated Operational Current DC-1 (Ie)

(110 V) 2 Poles in Series, 40 °C 50 A(110 V) 2 Poles in Series, 60 °C 42 A(110 V) 2 Poles in Series, 70 °C 37 A(110 V) 3 Poles in Series, 40 °C 50 A(110 V) 3 Poles in Series, 60 °C 42 A(110 V) 3 Poles in Series, 70 °C 37 A(220 V) 3 Poles in Series, 40 °C 50 A(220 V) 3 Poles in Series, 60 °C 42 A(220 V) 3 Poles in Series, 70 °C 37 A(72 V) 1-Pole, 40 °C 50 A(72 V) 1-Pole, 60 °C 42 A(72 V) 1-Pole, 70 °C 37 A(72 V) 2 Poles in Series, 40 °C 50 A(72 V) 2 Poles in Series, 60 °C 42 A(72 V) 2 Poles in Series, 70 °C 37 A(72 V) 3 Poles in Series, 40 °C 50 A(72 V) 3 Poles in Series, 60 °C 42 A(72 V) 3 Poles in Series, 70 °C 37 A

Rated Operational Current DC-3 (Ie)

(110 V) 2 Poles in Series, 40 °C 50 A(110 V) 2 Poles in Series, 60 °C 42 A(110 V) 2 Poles in Series, 70 °C 37 A(110 V) 3 Poles in Series, 40 °C 50 A(110 V) 3 Poles in Series, 60 °C 42 A(110 V) 3 Poles in Series, 70 °C 37 A(220 V) 3 Poles in Series, 40 °C 50 A(220 V) 3 Poles in Series, 60 °C 42 A(220 V) 3 Poles in Series, 70 °C 37 A(72 V) 1-Pole, 40 °C 50 A(72 V) 1-Pole, 60 °C 42 A(72 V) 1-Pole, 70 °C 37 A(72 V) 2 Poles in Series, 40 °C 50 A(72 V) 2 Poles in Series, 60 °C 42 A(72 V) 2 Poles in Series, 70 °C 37 A(72 V) 3 Poles in Series, 40 °C 50 A(72 V) 3 Poles in Series, 60 °C 42 A(72 V) 3 Poles in Series, 70 °C 37 A

Rated Operational Current DC-5 (Ie)

(110 V) 2 Poles in Series, 40 °C 50 A(110 V) 2 Poles in Series, 60 °C 42 A(110 V) 2 Poles in Series, 70 °C 37 A(110 V) 3 Poles in Series, 40 °C 50 A(110 V) 3 Poles in Series, 60 °C 42 A(110 V) 3 Poles in Series, 70 °C 37 A(220 V) 3 Poles in Series, 40 °C 25 A(220 V) 3 Poles in Series, 60 °C 25 A(220 V) 3 Poles in Series, 70 °C 25 A(72 V) 1-Pole, 40 °C 25 A(72 V) 1-Pole, 60 °C 25 A(72 V) 1-Pole, 70 °C 25 A(72 V) 2 Poles in Series, 40 °C 50 A(72 V) 2 Poles in Series, 60 °C 42 A(72 V) 2 Poles in Series, 70 °C 37 A(72 V) 3 Poles in Series, 40 °C 50 A(72 V) 3 Poles in Series, 60 °C 42 A(72 V) 3 Poles in Series, 70 °C 37 A

Rated Insulation Voltage (Ui)

acc. to IEC 60947-4-1 690 Vacc. to UL/CSA 600 V

Rated Impulse Withstand Voltage (Uimp)

6 kV

Maximum Mechanical Switching Frequency

3600 cycles per hour

Rated Control Circuit Voltage (Uc)

50 Hz 100 ... 250 V60 Hz 100 ... 250 VDC Operation 100 ... 250 V

Operate Time

Between Coil De-energization and NC Contact Closing 13 ... 98 msBetween Coil De-energization and NO Contact Opening 11 ... 95 msBetween Coil Energization and NC Contact Opening 38 ... 90 msBetween Coil Energization and NO Contact Closing 40 ... 95 ms

Mounting on DIN Rail

TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715

Mounting by Screws (not supplied)

2 x M4 screws placed diagonally

Connecting Capacity Main Circuit

Flexible with Ferrule 1/2x 1.5 ... 10 mm²Flexible with Insulated Ferrule 1x 1.5 ... 10 mm²Flexible with Insulated Ferrule 2x 1.5 ... 4 mm²Rigid Solid 1/2x 2.5 ... 4 mm²Rigid Stranded 1/2x 2.5 ... 10 mm²

Connecting Capacity Control Circuit

Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²Rigid Solid 1/2x 1 ... 2.5 mm²Rigid Stranded 1/2x 1 ... 2.5 mm²

Wire Stripping Length

Control Circuit 10 mmMain Circuit 14 mm

Degree of Protection

acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20

Terminal Type

Screw Terminals

Maximum Operating Voltage UL/CSA

Main Circuit 600 V

General Use Rating UL/CSA

(600 V AC) 50 A

Horsepower Rating UL/CSA

(120 V AC) Single Phase 2 hp(200 ... 208 V AC) Three Phase 10 hp(220 ... 240 V AC) Three Phase 10 hp(240 V AC) Single Phase 5 hp(440 ... 480 V AC) Three Phase 20 hp(550 ... 600 V AC) Three Phase 25 hp

Connecting Capacity Main Circuit UL/CSA

Rigid Solid 1/2x 14-10 AWGRigid Stranded 1/2x 14-8 AWG

Connecting Capacity Control Circuit UL/CSA

Rigid Solid 1/2x 18-14 AWGRigid Stranded 1/2x 18-14 AWG

Tightening Torque UL/CSA

Control Circuit 11 in·lbMain Circuit 22 in·lb

Ambient Air Temperature

Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °CClose to Contactor without Thermal O/L Relay -40 ... 70 °CClose to Contactor for Storage -60 ... +80 °C

Climatic Withstand

Category B according to IEC 60947-1 Annex Q

Maximum Operating Altitude Permissible

Without Derating 3000 m

Resistance to Shock acc. to IEC 60068-2-27

Closed, Shock Direction: B1 25 gOpen, Shock Direction: B1 5 gShock Direction: A 30 gShock Direction: B2 15 gShock Direction: C1 25 gShock Direction: C2 25 g

Resistance to Vibrations acc. to IEC 60068-2-6

5 ... 300 Hz 4 g closed position / 2 g open position

RoHS Status

Following EU Directive 2011/65/EU

Package Level 1 Units

box 1 piece

Package Level 1 Width

87 mm

Package Level 1 Depth / Length

87 mm

Package Level 1 Height

47 mm

Package Level 1 Gross Weight

0.35 kg

Package Level 1 EAN

3471523114432

Package Level 2 Units

box 21 piece

Package Level 2 Width

250 mm

Package Level 2 Depth / Length

300 mm

Package Level 2 Height

315 mm

Package Level 2 Gross Weight

15.75 kg

Package Level 3 Units

1080 piece

Object Classification Code

Q

ETIM 4

EC000066 - Magnet contactor, AC-switching

ETIM 5

EC000066 - Magnet contactor, AC-switching

ETIM 6

EC000066 - Power contactor, AC switching

ETIM 7

EC000066 - Power contactor, AC switching

ETIM 8

EC000066 - Power contactor, AC switching

eClass

V11.0 : 27371003

UNSPSC

39121529

IDEA Granular Category Code (IGCC)

4758 >> Iec Contactors

E-Number (Finland)

3706296

Document Links