2CSS255101R0101

SN201D10 SP&N MCB D10 6KA (SN201-D10)

Trade Price

£31.40

Per

1

Unit

EA

Pack Quantity

1

2CSS255101R0101
2CSS255101R0101
2CSS255101R0101
2CSS255101R0101

Information

Series SN201 6kA single pole+switched neutral * Part number: SN201-D10 * Rated Current (A): 10

Technical Specifications

Standards

IEC/EN 60898-1

Tripping Characteristic

D

Rated Voltage (Ur)

230 V AC

Rated Operational Voltage

acc. to IEC 60898-1 230 V

Rated Insulation Voltage (Ui)

acc. to IEC/EN 60664-1 500 V

Rated Impulse Withstand Voltage (Uimp)

4 kV

Dielectric Test Voltage

2 kV

Primary Rated Impulse Withstand Voltage

4 kV

Input Voltage Type

AC

Rated Current (In)

10 A

Rated Short-Circuit Capacity

(230 V) 6 kA

Rated Ultimate Short-Circuit Breaking Capacity (Icu)

(230 V) 10 kA

Rated Service Short-Circuit Breaking Capacity (Ics)

(230 V AC) 6 kA

Rated Frequency (f)

50/60 Hz

Power Loss

1.9 W

Power Supply Connection

Arbitrary

Contact Position Indication

Red ON / Green OFF

Energy Limiting Class

3

Electrical Endurance

10000 cycle

Mechanical Endurance

20000 cycle

Number of Poles

1+N

Number of Protected Poles

1

Number of Modular Spacings per DIN Rail

1

Overvoltage Category

III

Position of Neutral Terminals

Right

Tightening Torque

1.2 N·m

Accessory Type

Auxiliary contactSignal contact / auxiliary contactShunt tripUndervoltage release

Actuator Type

Toggle - Insulation group IIIA, black, sealable in ON-OFF positions

Housing Type

Insulation group II, RAL 7035

Screw Terminal Type

Cage Terminal

Mounting Position

Any

Accessories Available

Yes

Connecting Capacity

Flexible 1 … 10 mm²Rigid 1 … 16 mm²

Wire Stripping Length

11 mm

Terminal Type

Screw Terminals

Ambient Temperature

-25...55 °C

Ambient Air Temperature

Operation -25 … 55 °C

Reference Ambient Air Temperature

30 °C

Degree of Protection

IP20

Pollution Degree

2

Environmental Conditions

28 cycles;with 55 °C / 90-96 %;and 25 °C / 95-100 %

Resistance to Vibrations acc. to IEC 60068-2-6

0.35mm or 5g - 20 cycles at 5…150…5 Hz without load

Resistance to Shock acc. to IEC 60068-2-27

30g 2 shocks 13 ms

RoHS Status

Following EU Directive 2011/65/EU

Width in Number of Modular Spacings

1

Product Net Width

0.018 m

Product Net Height

0.085 m

Product Net Depth / Length

0.069 m

Product Net Weight

0.110 kg

Built-In Depth (t2)

69 mm

Minimum Order Quantity

1 piece

Package Level 1 Units

box 6 piece

Package Level 1 Gross Weight

0.684 kg

ETIM 8

EC000042 - Miniature circuit breaker (MCB)

ETIM 9

EC000042 - Miniature circuit breaker (MCB)

WEEE Category

5. Small Equipment (No External Dimension More Than 50 cm)

WEEE B2C / B2B

Business To Consumer

CN8

85362010

eClass

V11.0 : 27141901

Object Classification Code

F