Trade Price
£31.40
Per
1
Unit
EA
Pack Quantity
1
Series SN201 6kA single pole+switched neutral * Part number: SN201-D10 * Rated Current (A): 10
Standards
IEC/EN 60898-1
Tripping Characteristic
D
Rated Voltage (Ur)
230 V AC
Rated Operational Voltage
acc. to IEC 60898-1 230 V
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 500 V
Rated Impulse Withstand Voltage (Uimp)
4 kV
Dielectric Test Voltage
2 kV
Primary Rated Impulse Withstand Voltage
4 kV
Input Voltage Type
AC
Rated Current (In)
10 A
Rated Short-Circuit Capacity
(230 V) 6 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(230 V) 10 kA
Rated Service Short-Circuit Breaking Capacity (Ics)
(230 V AC) 6 kA
Rated Frequency (f)
50/60 Hz
Power Loss
1.9 W
Power Supply Connection
Arbitrary
Contact Position Indication
Red ON / Green OFF
Energy Limiting Class
3
Electrical Endurance
10000 cycle
Mechanical Endurance
20000 cycle
Number of Poles
1+N
Number of Protected Poles
1
Number of Modular Spacings per DIN Rail
1
Overvoltage Category
III
Position of Neutral Terminals
Right
Tightening Torque
1.2 N·m
Accessory Type
Auxiliary contactSignal contact / auxiliary contactShunt tripUndervoltage release
Actuator Type
Toggle - Insulation group IIIA, black, sealable in ON-OFF positions
Housing Type
Insulation group II, RAL 7035
Screw Terminal Type
Cage Terminal
Mounting Position
Any
Accessories Available
Yes
Connecting Capacity
Flexible 1 … 10 mm²Rigid 1 … 16 mm²
Wire Stripping Length
11 mm
Terminal Type
Screw Terminals
Ambient Temperature
-25...55 °C
Ambient Air Temperature
Operation -25 … 55 °C
Reference Ambient Air Temperature
30 °C
Degree of Protection
IP20
Pollution Degree
2
Environmental Conditions
28 cycles;with 55 °C / 90-96 %;and 25 °C / 95-100 %
Resistance to Vibrations acc. to IEC 60068-2-6
0.35mm or 5g - 20 cycles at 5…150…5 Hz without load
Resistance to Shock acc. to IEC 60068-2-27
30g 2 shocks 13 ms
RoHS Status
Following EU Directive 2011/65/EU
Width in Number of Modular Spacings
1
Product Net Width
0.018 m
Product Net Height
0.085 m
Product Net Depth / Length
0.069 m
Product Net Weight
0.110 kg
Built-In Depth (t2)
69 mm
Minimum Order Quantity
1 piece
Package Level 1 Units
box 6 piece
Package Level 1 Gross Weight
0.684 kg
ETIM 8
EC000042 - Miniature circuit breaker (MCB)
ETIM 9
EC000042 - Miniature circuit breaker (MCB)
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B
Business To Consumer
CN8
85362010
eClass
V11.0 : 27141901
Object Classification Code
F