Information

DDA800 A_ Type 2 Pole RCBO * Part number: DDA802A-100/0,03 AP-R * Rated Current (A): 100 * Type: AP-R * Tripping mA: 30

Technical Specifications

Standards

IEC EN 60947-2 Ann. B

Type of Residual Current

A type

Suitable For

S800SS800NS800CS800B

Rated Voltage (Ur)

230 V AC240 V AC400 V AC

Rated Operational Voltage

400/690 V

Rated Insulation Voltage (Ui)

690 V

Rated Impulse Withstand Voltage (Uimp)

6 kV

Rated Current (In)

100 A

Rated Residual Current

30 mA

Maximum Surge Current

3 kA

Leakage Current Type

A

Rated Frequency (f)

50 … 60 Hz

Power Loss

7 W

Number of Poles

2

Operating Characteristic

Instantaneous (APR High Immunity)

Options Provided

-

Connecting Capacity

Rigid 6 … 50 mm²Flexible 6 … 70 mm²

Ambient Temperature

-25...60 °C

Ambient Air Temperature

Operation -25...60 °C

Degree of Protection

IP2X

RoHS Status

Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Short-Circuit Current Rating (SCCR)

0.03 ... 0.03 A

Width in Number of Modular Spacings

4.5

Product Net Width

81 mm

Product Net Height

108.2 mm

Product Net Depth / Length

82.3 mm

Product Net Weight

0.300 kg

Minimum Order Quantity

1 piece

Package Level 1 Units

box 1 piece

Package Level 1 Gross Weight

0.4 kg

ETIM 8

EC002297 - Residual current circuit breaker (RCCB) module

ETIM 9

EC002297 - Residual current circuit breaker (RCCB) module

WEEE Category

5. Small Equipment (No External Dimension More Than 50 cm)

WEEE B2C / B2B

Business To Business

CN8

85363030

eClass

V11.0 : 27142210

Object Classification Code

F

Document Links