This Acti9 iPRD40 surge arrester protects 1P+N installations. It allows quick replacement of damaged cartridges. Modular design (cartridge type) DIN rail mounted The associated circuit breaker Isc breaking capacity can go up to 50kA. This Acti9 iPRD40 is compatible with TT and TN-S earthing system. The Uc maximum continuous operating voltage in common mode is 260VAC between neutral and earth, and 350VAC between phase and earth. The Uc maximum continuous operating voltage in differential mode (between phase and neutral) is 350VAC. The Up Voltage protection level is 1.4kV in common mode (N/PE) and in differential mode (L/N). The Ue rated operational voltage is 230VAC +/- 10%. The product colour is white (RAL9003).The dimensions are (W) 36mm x (H) 85mm x (D) 69mm. The weight is 0.211kg. The degree of protection is IP20 and IP40 in modular enclosure. The operating temperature is -25°C to 60°C. The storage temperature is -40°C to 85°C. This product is compliant with EN 61643-11 and IEC 61643-11 standard.
range of product
Acti9
Product name
Acti9 iPRD
Product or component type
Surge arrester with pluggable cartridge
Device short name
iPRD40
Device application
Distribution
Standards
EN 61643-11:2012 IEC 61643-11:2011
product certifications
CE
Quality labels
KEMA-KEUR NF
Poles description
1P + N
Remote signalling
Without
Surge arrester type
Electrical distribution network
Earthing system
TN-S TT
Surge arrester class type
Type 2
Surge arrester technology
MOV + GDT
[Ue] rated operational voltage
230/400 V AC (+/- 10 %) at 50/60 Hz
[In] nominal discharge current
Common mode: 15 kA (L/PE) Common mode: 15 kA (N/PE) Differential mode: 15 kA (L/N)
[Imax] maximum discharge current
Common mode: 40 kA L/PE Common mode: 40 kA N/PE Differential mode: 40 kA L/N
[Uc] maximum continuous operating voltage
Common mode: 260 V N/PE Common mode: 350 V L/PE Differential mode: 350 V L/N
Maximum [Up] voltage protection level
Common mode <1.4 kV type 2 N/PE Differential mode <1.4 kV type 2 L/N
[Ut] temporary overvoltage
337 V L/N 5 s withstand 1200 V N/PE 200 ms safe failure mode 442 V L/PE 5 s withstand 1453 V L/PE 200 ms safe failure mode
Disconnector device type
Associated circuit breaker iC60H 40 A curve C - Icu 15 kA Associated circuit breaker IC60N 40 A curve C - Icu 10 kA Associated circuit breaker NG125H 40 A curve C - Icu 36 kA Associated circuit breaker NG125L 40 A curve C - Icu 50 kA Associated circuit breaker NG125N 40 A curve C - Icu 25 kA Associated fuse gG 63 A - Icu 15 kA Associated fuse gG 80 A - Icu 50 kA
Mounting mode
Clip-on (DIN rail)
9 mm pitches
4
height
85 mm
Width
36 mm
Depth
69 mm
Net weight
0.211 kg
Colour
White (RAL 9003)
[Ipe] Ground residual current
0.6 mA 0.003 mA
Connections - terminals
Tunnel type terminal (downside) 2.5…35 mm² Tunnel type terminal (upside) 2.5…35 mm²
Tightening torque
2.5 N.m
IK degree of protection
IK03 conforming to IEC 62262
Relative humidity
5…95 %
Operating altitude
2000 m
Ambient air temperature for operation
-25…60 °C
Ambient air temperature for storage
-40…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
5.0 cm
Package 1 Width
8.0 cm
Package 1 Length
9.0 cm
Package 1 Weight
238.0 g
Unit Type of Package 2
BB1
Number of Units in Package 2
6
Package 2 Height
9 cm
Package 2 Width
10 cm
Package 2 Length
28 cm
Package 2 Weight
1.489 kg
Unit Type of Package 3
S03
Number of Units in Package 3
54
Package 3 Height
30 cm
Package 3 Width
30 cm
Package 3 Length
40 cm
Package 3 Weight
13.97 kg
Warranty
18 months