Trade Price
£612.25
Per
1
Unit
EA
Pack Quantity
1
VarPlus logic is a simple and efficient Power Controller for a automatic power factor correction equipment to maintain the power factor. It is a simple and intelligent relay which measures,monitor and Controls the reactive energy. It comes with Easy Commisioning , Step Size detection and monitoring along with the variour alarms. VPL12 can be used for 12 steps in a PFC equippment.
Range
PowerLogic
Product name
PowerLogic PFC Controller
Device short name
VPL12
Product or component type
Power factor controller
Number of step output contacts
12
[Us] rated supply voltage
90...550 V AC <= 999 kV AC with external VT
Measurement current
0…5 A
Measurement voltage
90…550 V AC 50/60 Hz
Operating mode
Manual or automatic
Number of quadrant operation for generator application
4
Device connection
Communication protocol: Modbus interface: RS485
Input function
Switch: 1 x dry contact
Colour code
Front: dark grey RAL 7016
Display type
Backlit LCD
Display size
56 x 25 mm
Function available
Manual programming Automatic initialisation Automatic detection Advanced programming (expert) Any step sequence
Metering type
Power factor and displacement PF (signed, four quadrant) Total current harmonic distortion THD (I) Power factor average over lifetime Temperature maximum Phase current I1, I2, I3 RMS on load Active power P, P1, P2, P3 on load Reactive power Q, Q1, Q2, Q3 on load Apparent power S, S1, S2, S3 on load Voltage U21, U32, U13, V1, V2, V3 on load
Type of measurement
Capacitor current overload Irms/I1 Individual voltage harmonic Power factor Operating time Cos φ Ambient temperature inside the cubicle Tan φ
Information displayed
Number of switching cycles per step Individual step size in kVAr Remaining step capacity in %
Type of alarms
Step power loss (< 75 %) / Action: message and alarm contact + step blocked Step faulty / Action: message and alarm contact + step blocked High current (> 6 A CT) / Action: message and alarm contact Hunting (unstable regulation) / Action: message and alarm contact + step blocked Low current (< 15 mA CT) / Action: message and alarm contact Overcompensation / Action: message and alarm contact Capacitor current overload (Irms/I1) (> 130 % I1) / Action: message and alarm contact + step switched off Overtemperature (50 °C) / Action: message and alarm contact + step switched off Overtemperature (30 °C) / Action: fan switch Overvoltage (+/- 10 %) / Action: message and alarm contact + control stopped Total harmonic distortion (> 7 %) / Action: message and alarm contact + step switched off
data recording
5 alarms
Operational Hours alarm
100000 h without maintenance
Operational counter alarm
65000 cycles without maintenance
input type
Phase to phase Phase to neutral Insensitive to CT polarity Insensitive to phase rotation polarity Current input CT...X/5 A and X/1 A
Output type
Control relay: 0.2 A 110 V DC Control relay: 1 A 48 V DC Control relay: 2 A 400 V AC 50/60 Hz Control relay: 1 A 24 V DC Control relay: 5 A 250 V AC 50/60 Hz Control relay: 5 A 120 V AC 50/60 Hz Fan: 5 A 250 V AC 50/60 Hz Fan: 1 A 48 V DC Alarm relay: 5 A 250 V AC 50/60 Hz Alarm relay: 1 A 48 V DC
Maximum at the common terminal
10 A
Settings operating mode
Automatic Manual
Type of setting
Choice of stepping programs: auto Choice of stepping programs: LIFO Choice of stepping programs: linear Delay between 2 successive switch on the same step: 5...1200 s Step configuration programming: auto Step configuration programming: off Step configuration programming: fixed Target cos phi: 0.7 inductive...0.7 capacitive Target cos phi: dual cos φ
Measurement accuracy
Voltage +/- 1 % Current +/- 1 % Frequency +/- 1 % Energy (P,Q,S) +/- 2 % Cos φ +/- 2 % Total voltage harmonic distortion THD (U) +/- 2 % Individual voltage harmonic +/- 3 % Temperature +/- 3 °C
Time delay range
1...6500 s (on reconnection) 1...6500 s (on response)
Provided equipment
User manual
Mounting mode
Flush-mounted
Mounting support
Panel - thickness: 1…3 mm
Mounting location
In cabinet
Cut-out dimensions
138 x 138 mm
height
144 mm
Width
144 mm
Depth
58 mm
Net weight
0.6 kg
standards
IEC 61000-6-4 UL 61010-1 EN 61010-1 IEC 61000-6-2 IEC 61326-1
product certifications
EAC NRTL cNRTL CE
IP degree of protection
Front face: IP41 Rear face: IP20
Operating altitude
<= 2000 m
Ambient air temperature for operation
-20…60 °C
Ambient air temperature for storage
-40…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
9.200 cm
Package 1 Width
17.700 cm
Package 1 Length
18.400 cm
Package 1 Weight
724.000 g
Unit Type of Package 2
S03
Number of Units in Package 2
8
Package 2 Height
30.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
6.155 kg
Unit Type of Package 3
P06
Number of Units in Package 3
64
Package 3 Height
75.000 cm
Package 3 Width
60.000 cm
Package 3 Length
80.000 cm
Package 3 Weight
58.408 kg
Warranty
18 months