Trade Price
£517.13
Per
1
Unit
EA
Pack Quantity
1
VarPlus logic is a simple and efficient Power Controller for a automatic power factor correction equipment to maintain the power factor. It is a simple and intelligent relay which measures,monitor and Controls the reactive energy. It comes with Easy Commisioning , Step Size detection and monitoring along with the variour alarms. VPL06 can be used for 6 steps in a PFC equippment
Range
PowerLogic
Product name
PowerLogic PFC Controller
Device short name
VPL6
Product or component type
Power factor controller
Number of step output contacts
6
[Us] rated supply voltage
90...550 V AC <= 999 kV AC with external VT
Measurement current
0…5 A
Measurement voltage
90…550 V AC 50/60 Hz
Operating mode
Manual or automatic
Number of quadrant operation for generator application
4
Device connection
Communication protocol: Modbus interface: RS485
Input function
Switch: 1 x dry contact
Colour code
Front: dark grey RAL 7016
Display type
Backlit LCD
Display size
56 x 25 mm
Function available
Automatic detection Advanced programming (expert) Manual programming Any step sequence Automatic initialisation
Metering type
Power factor and displacement PF (signed, four quadrant) Total current harmonic distortion THD (I) Power factor average over lifetime Temperature maximum Phase current I1, I2, I3 RMS on load Active power P, P1, P2, P3 on load Reactive power Q, Q1, Q2, Q3 on load Apparent power S, S1, S2, S3 on load Voltage U21, U32, U13, V1, V2, V3 on load
Type of measurement
Ambient temperature inside the cubicle Tan φ Individual voltage harmonic Cos φ Operating time Power factor Capacitor current overload Irms/I1
Information displayed
Number of switching cycles per step Remaining step capacity in % Individual step size in kVAr
Type of alarms
Step power loss (< 75 %) / Action: message and alarm contact + step blocked Step faulty / Action: message and alarm contact + step blocked High current (> 6 A CT) / Action: message and alarm contact Hunting (unstable regulation) / Action: message and alarm contact + step blocked Low current (< 15 mA CT) / Action: message and alarm contact Overcompensation / Action: message and alarm contact Capacitor current overload (Irms/I1) (> 130 % I1) / Action: message and alarm contact + step switched off Overtemperature (50 °C) / Action: message and alarm contact + step switched off Overtemperature (30 °C) / Action: fan switch Overvoltage (+/- 10 %) / Action: message and alarm contact + control stopped Total harmonic distortion (> 7 %) / Action: message and alarm contact + step switched off
data recording
5 alarms
Operational Hours alarm
100000 h without maintenance
Operational counter alarm
65000 cycles without maintenance
input type
Insensitive to phase rotation polarity Insensitive to CT polarity Phase to neutral Current input CT...X/5 A and X/1 A Phase to phase
Output type
Control relay: 0.2 A 110 V DC Control relay: 1 A 48 V DC Control relay: 2 A 400 V AC 50/60 Hz Control relay: 1 A 24 V DC Control relay: 5 A 250 V AC 50/60 Hz Control relay: 5 A 120 V AC 50/60 Hz Fan: 5 A 250 V AC 50/60 Hz Fan: 1 A 48 V DC Alarm relay: 5 A 250 V AC 50/60 Hz Alarm relay: 1 A 48 V DC
Maximum at the common terminal
10 A
Settings operating mode
Manual Automatic
Type of setting
Choice of stepping programs: auto Choice of stepping programs: LIFO Choice of stepping programs: linear Delay between 2 successive switch on the same step: 5...1200 s Step configuration programming: auto Step configuration programming: off Step configuration programming: fixed Target cos phi: 0.7 inductive...0.7 capacitive Target cos phi: dual cos φ
Measurement accuracy
Voltage +/- 1 % Current +/- 1 % Frequency +/- 1 % Energy (P,Q,S) +/- 2 % Cos φ +/- 2 % Total voltage harmonic distortion THD (U) +/- 2 % Individual voltage harmonic +/- 3 % Temperature +/- 3 °C
Time delay range
1...6500 s (on reconnection) 1...6500 s (on response)
Provided equipment
User manual
Mounting mode
Flush-mounted
Mounting support
Panel - thickness: 1…3 mm
Mounting location
In cabinet
Cut-out dimensions
138 x 138 mm
height
144 mm
Width
144 mm
Depth
58 mm
Net weight
0.6 kg
standards
IEC 61000-6-2 EN 61010-1 IEC 61000-6-4 IEC 61326-1 UL 61010-1
product certifications
EAC NRTL cNRTL CE
IP degree of protection
Front face: IP41 Rear face: IP20
Operating altitude
<= 2000 m
Ambient air temperature for operation
-20…60 °C
Ambient air temperature for storage
-40…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
9.200 cm
Package 1 Width
17.800 cm
Package 1 Length
18.400 cm
Package 1 Weight
696.000 g
Unit Type of Package 2
S03
Number of Units in Package 2
8
Package 2 Height
30.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
6.050 kg
Unit Type of Package 3
P06
Number of Units in Package 3
64
Package 3 Height
75.000 cm
Package 3 Width
60.000 cm
Package 3 Length
80.000 cm
Package 3 Weight
60.348 kg
Warranty
18 months
Datasheet