LVR07250A40T

Detuning Reactor 400V 50Hz 25kVAr 190Hz

Trade Price

POA

Per

1

Unit

EA

Pack Quantity

1

LVR07250A40T

Information

The VarPlus detuned reactor are designed to protect the capacitor by preventing the amplification of the harmonics present in the system. Capacitors and Reactors are configured in Series resonant circuit. Tuned so that the series resonant frequency is below the lowest harmonic frequency present in the system. This reactor is rated for 25 kVar output power with 3.8/190 Hz tuning order at 400V AC at 50 Hz. Relative impedance, 7 %. This component meet the standards IEC 60068. This component require a forced convection, a fan need to be added. The case dimensions are 220mm in height, 240mm in width and 160mm in depth. For a product weight of 15 kg.

Technical Specifications

Range

PowerLogic

Device short name

DR

Product or component type

Detuned reactor

Network frequency

50 Hz

Reactive power rating

25 kvar for 400 V AC 50 Hz

Network rated voltage

400 V AC 50 Hz

Tuning order

3.8 - 190 Hz - 7 % - 50 Hz

power losses (max)

200 W

Value of inductance

1.499 mH

Inductance tolerance

- 5 % to 5 % per phase

Fundamental current rating

36.1 A

RMS current rating

39 A

Electrical insulation class

Class H

[Ui] rated insulation voltage

1.1 kV

Dielectric test voltage

4 kV 50 Hz 1 minute

[Imp] maximum permanent current

1.2 x I1

Harmonic current spectrum

3.7 % x I3 38.2 % x I5 13.6 % x I7 4.9 % x I11

dynamic withstand current

2.2 x Isc

[Ith] conventional free air thermal current

2 A at 250 V AC 50 Hz

Type of installation

Indoor installation

Type of cooling

Forced convection

Connections - terminals

Pad terminal

Fixing center

200 x 125 mm

height

220 mm

Width

240 mm

Depth

160 mm

Net weight

15 kg

standards

IEC 60068

IP degree of protection

IP00

Operating altitude

<= 2000 m

Ambient air temperature for operation

0…55 °C at <= 1000 m 0…50 °C at > 1000...2000 m

Average ambient air temperature for operation

50 °C at <= 1000 m (average over 24 hours) 40 °C at <= 1000 m (average over 1 year) 45 °C at > 1000...2000 m (average over 24 hours) 35 °C at > 1000...2000 m (average over 1 year)

Climatic withstand

Relative humidity: 20...80 % Salt mist (400 V/50 Hz) : 250 hours

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

25.0 cm

Package 1 Width

29.5 cm

Package 1 Length

31.0 cm

Package 1 Weight

14.45 kg

Unit Type of Package 2

P12

Number of Units in Package 2

24

Package 2 Height

105.0 cm

Package 2 Width

80.0 cm

Package 2 Length

120.0 cm

Package 2 Weight

400.0 kg

Warranty

18 months

Document Links

Datasheet