VLVAF3P03513AB

VarSet Auto 225k DR3,8 400V-50

Trade Price

£19,048.42

Per

1

Unit

EA

Pack Quantity

1

VLVAF3P03513AB

Information

Low voltage power factor correction solution, from VarSet family, helps to eliminate utility penalties. To do energy savings, to lower capital costs, and to reduce CO² emissions by the reactive power compensation of inductive loads. This hardware is compatible with power management software to take advantage of the IoT digital power installation and allow a seemless integration to EcoStruxture Power. Smart monitoring and measurement features are available to secure operations. To optimize perfomance and maintenance, across a broad range of applications, commercial or industrial. This capacitor bank version, suitable for network voltage 400 to 415V 50Hz is providing a reactive power up to 225kvar with a tuning frequency of 190Hz. The compensation is automatically adjusted by the Power factor controller from VarplusLogic family. It is designed for network harmonic voltage up to 7% or network harmonic current up to 20%, network defined as a polluted harmonic network. VarSet range is certified to CE, IEC 61921, IEC 61439 part 1 & IEC61439 part 2. It is embedding high life expectancy capacitors from Varplus family designed as per IEC831 part 1 and IEC831 part 2. And include a smart controller with modbus communication RS485. The enclosure RAL7035 is a floor standing type with a bottom entry incoming connection. Frame exterior dimensions are 800 millimetres in width, 600 millimetres in depth, 2000 millimetres height and a max product weight of 400kg. As a standard, the enclosures are IP31. Optionnal kits are available to transform them easily into a IP54. This product is particularly adapted for power factor correction applications with variable or unstable loads.

Technical Specifications

Network rated voltage

400 V AC 50 Hz 415 V AC 50 Hz

Reactive power rating

225 kvar

Operating mode

Automatic

Range

PowerLogic

Device short name

automatic capacitor bank with detuned reactor

Product or component type

Capacitor bank

Network pollution level

Polluted

[Gh/Sn] harmonic pollution rate

25…50 %

[THDU] total harmonic distorsion of voltage

4…7 %

Tuning factor

3.8

Tuning frequency

190 Hz

Power per step

25 kvar

Step composition

25 + 2x50 + 100

Location of connection

Bottom

Controller type

PowerLogic PFC Controller VPL6

capacitor technology

PowerLogic PFC Capacitor + Detuned Reactor

Poles description

3P

capacitance tolerance

- 5 % to 10 %

[Ui] rated insulation voltage

800 V

[Uimp] rated impulse withstand voltage

8 kV

Maximum permissible voltage

1.1 x Un (8 hours over 24 hours) conforming to IEC 60831

[Imp] maximum permanent current

Capacitor: 1.8 x In at 480 V conforming to IEC 60831 Battery: 1.19 x In at 400 V conforming to IEC 61439-2 Battery: 1.19 x In at 415 V conforming to IEC 61439-2

main incomer protection

Without protection

[Icw] rated short-time withstand current

35 kA at 1 s (Icw)

Step protection type

Overload: harmonic control from PowerLogic PFC Controller Short-circuit: fuse

accessibility for operation

Front

Colour

Grey (RAL 7035)

maximum weight

400 kg

height

2000 mm

Width

800 mm

Depth

600 mm

Provided equipment

Auxiliary transformer

Internal voltage transformer

400/230 V - 630 VA

Function available

GenSet shedding contact Alarm contact

standards

IEC 61439-2 IEC 61921 IEC 61439-1

product certifications

ASEFA CE EAC

Mounting location

Indoor

IP degree of protection

Environment: IP31 Safety: IPxx B

IK degree of protection

IK10

Relative humidity

0…95 %

Operating altitude

<= 2000 m

Ambient air temperature for operation

-5…45 °C

Average ambient air temperature for operation

35 °C (annual) 45 °C (over 24 hours)

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

80.0 cm

Package 1 Width

120.0 cm

Package 1 Length

210.0 cm

Package 1 Weight

412.0 kg

Warranty

18 months

Document Links

Datasheet