The VarPlus detuned reactor are designed to protect the capacitor by preventing the amplification of the harmonics present in the system. Capacitors and Reactors are configured in Series resonant circuit. Tuned so that the series resonant frequency is below the lowest harmonic frequency present in the system. This reactor is rated for 100 kVar output power with 3.8/190 Hz tuning order at 400V AC at 50 Hz. Relative impedance, 7 %. This component meet the standards IEC 60068. This component require a forced convection, a fan need to be added. The case dimensions are 350mm in height, 350mm in width and 220mm in depth. For a product weight of 37 kg.
Range
PowerLogic
Device short name
DR
Product or component type
Detuned reactor
Network frequency
50 Hz
Reactive power rating
100 kvar for 400 V AC 50 Hz
Network rated voltage
400 V AC 50 Hz
Tuning order
3.8 - 190 Hz - 7 % - 50 Hz
power losses (max)
480 W
Value of inductance
0.375 mH
Inductance tolerance
- 5 % to 5 % per phase
Fundamental current rating
144.3 A
RMS current rating
155.9 A
Electrical insulation class
Class H
[Ui] rated insulation voltage
1.1 kV
Dielectric test voltage
4 kV 50 Hz 1 minute
[Imp] maximum permanent current
1.2 x I1
Harmonic current spectrum
3.7 % x I3 38.2 % x I5 13.6 % x I7 4.9 % x I11
dynamic withstand current
2.2 x Isc
[Ith] conventional free air thermal current
2 A at 250 V AC 50 Hz
Type of installation
Indoor installation
Type of cooling
Forced convection
Connections - terminals
Pad terminal
Fixing center
200 x 125 mm
height
350 mm
Width
350 mm
Depth
220 mm
Net weight
37 kg
standards
IEC 60068
IP degree of protection
IP00
Operating altitude
<= 2000 m
Ambient air temperature for operation
0…55 °C at <= 1000 m 0…50 °C at > 1000...2000 m
Average ambient air temperature for operation
50 °C at <= 1000 m (average over 24 hours) 40 °C at <= 1000 m (average over 1 year) 45 °C at > 1000...2000 m (average over 24 hours) 35 °C at > 1000...2000 m (average over 1 year)
Climatic withstand
Relative humidity: 20...80 % Salt mist (400 V/50 Hz) : 250 hours
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
56.0 cm
Package 1 Width
40.0 cm
Package 1 Length
60.0 cm
Package 1 Weight
44.0 kg
Unit Type of Package 2
P06
Number of Units in Package 2
2
Package 2 Height
50.0 cm
Package 2 Width
80.0 cm
Package 2 Length
60.0 cm
Package 2 Weight
96.5 kg
Warranty
18 months