18674

125A 4P 25kA NG125N mcb curve type D

Trade Price

POA

Per

1

Unit

Pack Quantity

18674

Information

This Acti9 NG125N is a low voltage circuit breaker. It is a 4P circuit breaker with 4 protected poles, 125A rated current and D tripping curve. The rated short circuit breaking capacity goes up to 25kA at 380VAC to 415VAC conforming to EN/IEC 60947-2 standard and 25kA at 380VAC to 415VAC conforming to EN/IEC 60947-2 standard. It complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. This miniature circuit breaker protects circuits against short circuit and overload current. It is suitable for isolation in the industrial sector according to IEC/EN 60947-2 standard. The fault tripping is indicated by a red mechanical state indicator light on the front face of the circuit breaker. It has an electrical endurance going up to 5000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is going from 380VAC to 415VAC. The Ui rated insulation voltage is 690VAC. The Uimp rated impulse withstand voltage is 8kV. The operating frequency is 50Hz or 60Hz. It is DIN rail mountable. Its width is 12 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The dimensions are (W) 108mm x (H) 103mm x (D) 81mm. The weight is 0.96kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals in enclosure. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 70°C.

Technical Specifications

Range of produc

NG125

Range

Acti9

Product name

Acti9 NG125

Product or component type

Miniature circuit-breaker

Device short name

NG125N

Device application

Distribution

Poles description

4P

Number of protected poles

4

[In] rated current

125 A at 40 °C

Network type

DC AC

Trip unit technology

Thermal-magnetic

Curve code

D

Breaking capacity

20 kA Icu at <= 500 V DC conforming to EN/IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2

Utilisation category

Category A conforming to IEC 60947-2

Suitability for isolation

Yes conforming to IEC 60947-2

Network frequency

50/60 Hz

[Ue] rated operational voltage

380...415 V AC 50/60 Hz 500 V AC 50/60 Hz <= 500 V DC 220...240 V AC 50/60 Hz 440 V AC 50/60 Hz

Magnetic tripping limit

12 x In

[Ics] rated service breaking capacity

37.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 18.75 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V AC 50/60 Hz 20 kA 100 % conforming to EN/IEC 60947-2 - <= 500 V DC

[Ui] rated insulation voltage

690 V AC 50/60 Hz conforming to EN/IEC 60947-2

[Uimp] rated impulse withstand voltage

8 kV conforming to EN/IEC 60947-2

Contact position indicator

Yes

control type

Manual tripping test Toggle

local signalling

Trip indicator ON/OFF indication

Mounting mode

Clip-on

mounting support

35 mm symmetrical DIN rail

Comb busbar and distribution block compatibility

NO

9 mm pitches

12

height

103 mm

Width

108 mm

Depth

81 mm

Net weight

0.96 kg

Mechanical durability

20000 cycles

Electrical durability

5000 cycles

Provision for padlocking

Padlockable

Locking options description

Integrated padlocking

Connections - terminals

Tunnel type terminals16…70 mm² rigid Tunnel type terminals10…50 mm² flexible

Wire stripping length

20 mm

Tightening torque

6 N.m

earth-leakage protection

Separate block

Standards

EN/IEC 60947-2

IP degree of protection

IP20 conforming to IEC 60529

IK degree of protection

IK05 conforming to EN/IEC 62262

Pollution degree

3 conforming to IEC 60947-2

Overvoltage category

IV

Tropicalisation

2 conforming to IEC 60068-1

Relative humidity

95 % at 55 °C

ambient air temperature for operation

-30…70 °C

Ambient air temperature for storage

-40…70 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

8.4 cm

Package 1 Width

12.2 cm

Package 1 Length

15.6 cm

Package 1 Weight

1.038 kg

Unit Type of Package 2

S03

Number of Units in Package 2

12

Package 2 Height

30.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

12.956 kg

Warranty

18 months

Document Links

Datasheet