Trade Price
£343.54
Per
1
Unit
EA
Pack Quantity
1
This Acti9 NG125N is a low voltage circuit breaker. It is a 3P circuit breaker with 3 protected poles, 63A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 25kA at 380VAC to 415VAC conforming to EN/IEC 60947-2 standard and 25kA at 380VAC to 415VAC conforming to EN/IEC 60947-2 standard. It complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. This miniature circuit breaker protects circuits against short circuit and overload current. It is suitable for isolation in the industrial sector according to IEC/EN 60947-2 standard. The fault tripping is indicated by a red mechanical state indicator light on the front face of the circuit breaker. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is equal or below 375VDC, 220VAC to 240VAC, 380VAC to 415VAC, 440VAC or 500VAC. The Ui rated insulation voltage is 690VAC. The Uimp rated impulse withstand voltage is 8kV. The operating frequency is 50Hz or 60Hz. It is DIN rail mountable. Its width is 9 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The dimensions are (W) 81mm x (H) 103mm x (D) 81mm. The weight is 0.72kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals in enclosure. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 70°C.
Range of produc
NG125
Range
Acti9
Product name
Acti9 NG125
Product or component type
Miniature circuit-breaker
Device short name
NG125N
Device application
Distribution
Poles description
3P
Number of protected poles
3
[In] rated current
63 A at 40 °C
Network type
AC DC
Trip unit technology
Thermal-magnetic
Curve code
C
Breaking capacity
20 kA Icu at <= 375 V DC conforming to EN/IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
Utilisation category
Category A conforming to IEC 60947-2
Suitability for isolation
Yes conforming to IEC 60947-2
Network frequency
50/60 Hz
[Ue] rated operational voltage
<= 375 V DC 380...415 V AC 50/60 Hz 500 V AC 50/60 Hz 220...240 V AC 50/60 Hz 440 V AC 50/60 Hz
Magnetic tripping limit
8 x In
[Ics] rated service breaking capacity
37.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 18.75 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V AC 50/60 Hz 20 kA 100 % conforming to EN/IEC 60947-2 - <= 375 V DC
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
8 kV conforming to EN/IEC 60947-2
Contact position indicator
Yes
control type
Toggle Manual tripping test
local signalling
ON/OFF indication Trip indicator
Mounting mode
Clip-on
mounting support
35 mm symmetrical DIN rail
Comb busbar and distribution block compatibility
YES
9 mm pitches
9
height
103 mm
Width
81 mm
Depth
81 mm
Net weight
0.72 kg
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Provision for padlocking
Padlockable
Locking options description
Integrated padlocking
Connections - terminals
Tunnel type terminals1.5…50 mm² rigid Tunnel type terminals1…35 mm² flexible
Wire stripping length
20 mm
Tightening torque
3.5 N.m
earth-leakage protection
Separate block
Standards
EN/IEC 60947-2
IP degree of protection
IP20 conforming to IEC 60529
IK degree of protection
IK05 conforming to EN/IEC 62262
Pollution degree
3 conforming to IEC 60947-2
Overvoltage category
IV
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
ambient air temperature for operation
-30…70 °C
Ambient air temperature for storage
-40…70 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
8.6 cm
Package 1 Width
12.1 cm
Package 1 Length
12.9 cm
Package 1 Weight
758 g
Unit Type of Package 2
S03
Number of Units in Package 2
18
Package 2 Height
30 cm
Package 2 Width
30 cm
Package 2 Length
40 cm
Package 2 Weight
14.16 kg
Warranty
18 months
Datasheet