33536

TRIP UNIT MICROLOGIC 2.0E FOR COMPACT NS

Trade Price

£1,212.51

Per

1

Unit

EA

Pack Quantity

1

33536

Information

Micrologic 2.0E (Energy meter) is an electronic control unit used on Compact NS630b to NS1600 drawout circuit breakers. This control unit has a basic protection (LI) and is designed to protect power circuits and loads. It embeds adjustable long time protection against overloads. It provides also adjustable instantaneous protection against short-circuits. Micrologic 2.0E indicates overloads with an Alarm LED. It is able to display the trip cause through 3 others LEDs. Micrologic 2.0E is equipped with a digital LCD screen that displays the active energy with 2% accuracy. This control unit can be associated with drawout Compact NS basic frame.

Technical Specifications

Range

ComPact

Range of product

ComPact NS630b...1600

Product or component type

Trip unit

Trip unit name

MicroLogic 2.0 E

Trip unit technology

Electronic

Range compatibility

ComPact NS630b...1600

Device application

Distribution

Number of poles

4P 3P

Protected poles description

3t 3t + N/2 4t

Trip unit protection functions

Basic protection

Protection type

for overload protection (long time) for instantaneous short-circuit protection

Trip unit rating

630 A at 50 °C 800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C

Network type

AC

Network frequency

50/60 Hz

Circuit breaker mounting mode

Drawout

Long-time pick-up adjustment type Ir (thermal protection)

Adjustable 9 settings

[Ir] long-time protection pick-up adjustment range

0.4...1 x In

Long-time protection delay adjustment type tr

Adjustable 9 settings

[tr] long-time protection delay adjustment range

0.7…16.6 s at 7.2 x Ir 0.7…24 s at 6 x Ir 12.5…600 s at 1.5 x Ir

Thermal memory

20 mn

Instantaneous protection pick-up adjustment type Ii

Adjustable 9 settings

[Ii] instantaneous protection pick-up adjustment range

1.5...10 x Ir

earth-leakage protection

Without

Zone selective interlocking ZSI

Without

Local signalling

3 LEDs (red) for electrical fault 1 LED (red) for internal error

Display type

Digital display

Type of measurement

Energy meter

communication of data

Measurement readout Protection and alarm settings

Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-40…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

13.500 cm

Package 1 Width

14.000 cm

Package 1 Length

38.000 cm

Package 1 Weight

452.000 g

Unit Type of Package 2

P12

Number of Units in Package 2

32

Package 2 Height

45.000 cm

Package 2 Width

80.000 cm

Package 2 Length

120.000 cm

Package 2 Weight

32.864 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet